Tuya 2CT

Two-clamp energy meter

A two-channel Zigbee energy meter with 80 A current clamps that reports voltage, frequency, and each channel's power, current, power factor and energy, with calibration factors you can trim from Edge.

Tuya 2CT
  • Zigbee

Two-clamp energy meter

Compatibility

Compatible with EpiSensor Edge over Zigbee.

Pair it with the Zigbee radio on an EpiSensor Gateway. Edge reads it locally on the Gateway.

Edge reads 20 values from it, listed under Interface.

Connect it with

Specifications

The 2CT is a single-phase energy meter with two 80 A current clamps. It measures the supply voltage and frequency once, and power, current, power factor and consumed energy separately on channel A and channel B. It also reports the total power of both channels.23

Power
Mains. Reports a single-phase mains supply as its power source when it joins. No supply voltage range is published for it.4
Channels
2 current channels (A and B), one voltage measurement3
Current clamps
80 A3
Update interval
3 to 60 s, 10 s default3
Calibration factors
0.5 to 1.5 in steps of 0.01, for voltage, frequency and each channel's current and power3
Energy totals
Consumed energy per channel, in steps of 0.01 kWh3
Power resolution
0.1 W3
Current resolution
0.001 A3
Voltage resolution
0.1 V3
Frequency resolution
0.01 Hz3
Zigbee role
Router, mains powered4
Data transport
Tuya datapoints on cluster 0xEF001
Zigbee identity
TS0601, _TZE204_dhotiauw3

Where it is used

Interface

On the Zigbee network it joins as a router and extends the mesh for other devices.4

Readings and settings, with units and ranges where Tuya publishes them. readable, readable and writable.

Download
ReadingUnitRange or valuesAccess
Measurements 13
AC frequency Hz - Read only
Voltage V - Read only
Power W - Read only
Power a W - Read only
Power b W - Read only
Current a A - Read only
Current b A - Read only
Power factor a % - Read only
Power factor b % - Read only
Energy a kWh - Read only
Energy b kWh - Read only
Timestamp a - - Read only
Timestamp b - - Read only
Settings 7
Update frequency s 3 to 60 s Read and write
Calibration AC frequency - 0.5 to 1.5 Read and write
Calibration voltage - 0.5 to 1.5 Read and write
Calibration power a - 0.5 to 1.5 Read and write
Calibration current a - 0.5 to 1.5 Read and write
Calibration power b - 0.5 to 1.5 Read and write
Calibration current b - 0.5 to 1.5 Read and write

Every reading and setting travels as a Tuya datapoint on the private cluster 0xEF00 on endpoint 1, not on the standard Zigbee metering clusters. Edge decodes them through the 2CT definition, which is why the manufacturer name has to match.14

Each calibration factor defaults to 1.0. Change one only after comparing that reading with a reference instrument, and record the value you set.3

The definition maps no exported energy total for either channel. Power factor is reported as a percentage.3

Setup

  1. Open pairing in Edge

    Open pairing on the Gateway's Zigbee network in Edge, then put the meter into pairing mode as its instructions describe.

  2. Check the identity

    Edge should report model TS0601 and manufacturer _TZE204_dhotiauw. Other two-clamp meters also report TS0601 but use different datapoints, so the manufacturer name decides which definition applies.3

  3. Set the update interval

    The meter reports every 10 seconds by default. Set it anywhere from 3 to 60 seconds from Edge; a longer interval means less Zigbee traffic.3

  4. Check and trim each channel

    Switch on a known load on each clamped circuit and compare voltage, current and power with a reference meter. If one reads consistently high or low, set its calibration factor from Edge, between 0.5 and 1.5.3