Legrand 412175

Three-phase energy meter

A one-module DIN-rail meter for three-phase supplies from 2 to 125 A per phase, measured with three closed Rogowski coils to ±1 %. Over Zigbee it reports active and apparent power for each phase.

Also sold asDrivia with Netatmo three-phase energy meterBTicino F40T125A

Legrand 412175
  • Zigbee

Three-phase energy meter

Compatibility

Compatible with EpiSensor Edge over Zigbee.

Pair it with the Zigbee radio on an EpiSensor Gateway. Edge reads it locally on the Gateway.

Edge reads 8 values from it, listed under Interface.

Connect it with

Specifications

The 412175 is Legrand's connected three-phase energy meter in the Drivia with Netatmo range. The module is one DIN module (17.7 mm) wide and comes with three closed Rogowski coils on a removable connector. Each coil measures one phase from 2 A to 125 A AC, and the coil set is matched to its module: coils are not interchangeable between meters.23

Power
Mains. Powered at 100 to 240 V AC between neutral and phase 3 of the measured supply, 0.3 W maximum.3
Measured current
2 to 125 A AC per phase2
Accuracy
±1 % for module and coil, above 2 A and cos φ ≥ 0.82
Accuracy class
11
Current sensors
Three closed Rogowski coils, 350 mm leads3
Coil capacity
1 × 50 mm² (12.4 mm) with support; 1 × 70 mm² (15.3 mm) without2
Network
Three-phase, 110 to 500 V AC, 50/60 Hz2
Module supply
100 to 240 V AC between N and V3, 0.3 W maximum3
Supply protection
Three-phase circuit breaker, C2 to C162
Radio
IEEE 802.15.4, 2.4 to 2.4835 GHz, under 100 mW2
Terminals
Cage, 1 to 2.5 mm², 8 mm stripped, 0.5 Nm2
Width
1 DIN module, 17.7 mm2
Dimensions (W × H × D)
17.7 × 101.6 × 67.2 mm1
Weight
109 g2
Protection
IP2X terminals, IP3XD front face, IK04, Class II front face2
Standards
EN/IEC 61010-1; coils insulation class A to IEC 61869-22

Where it is used

Interface

Readings and settings, with units and ranges where Legrand publishes them. readable, readable and writable.5

Download
ReadingUnitRange or valuesAccess
Measurements 6
Active power, phase AInstantaneous active power on the first phase W - Read only
Active power, phase BInstantaneous active power on phase B W - Read only
Active power, phase CInstantaneous active power on phase C W - Read only
Apparent power, phase AInstantaneous apparent power on the first phase VA - Read only
Apparent power, phase BInstantaneous apparent power on phase B VA - Read only
Apparent power, phase CInstantaneous apparent power on phase C VA - Read only
Settings 1
Power alarmTurns the module's power alarm on or off - truefalse Read and write
Diagnostics 1
Power alarm activeTrue while the power alarm threshold is exceeded - truefalse Read only

Zigbee2MQTT reads it through the Electrical Measurement cluster. The first phase appears as power and power_apparent; the other two carry the suffixes phase_b and phase_c.5

Zigbee2MQTT's definition notes that the module forgets its reporting configuration after a restart or power loss, and sets reporting up again each time the module announces itself on the network.5

Over Zigbee it reports power, not an energy counter. Legrand's app builds daily, weekly, monthly and yearly consumption history from the same module.15

Setup

  1. Wire the module with the supply off

    Turn off the main breaker. Connect N, V1, V2 and V3 through a three-phase C2 to C16 breaker, keeping the phase order marked on the connector.3

  2. Fit the coils

    Pass each phase conductor through its coil so that coil I1 is on L1, I2 on L2 and I3 on L3, with the arrow on each coil in the direction of current flow.3

  3. Clear any earlier pairing

    If the module has been used before, hold its setting button for more than 5 seconds until the LED turns steady red. It is then no longer paired with any gateway.2

  4. Open pairing in Edge and switch on

    Open pairing on the Gateway's Zigbee network in Edge, refit the front plate and turn the main breaker on. The LED is steady red until it joins, steady green once it has joined while the network is still open, and off in normal use.2

  5. Check each phase

    Compare active power on each phase with a clamp meter reading on a known load. A negative value on a consuming load means that coil is the wrong way round.

Common questions

Does the 412175 need a Legrand gateway?
Only for Legrand's Home + Control app. Legrand requires a with Netatmo gateway for its own installation, but the module is a Zigbee device and Zigbee2MQTT's definition reads its power directly from the Zigbee network.25
Does it report energy in kWh over Zigbee?
No. Its Zigbee definition reports active and apparent power for each phase and a power alarm. Energy history is kept by Legrand's app.15
Can it measure solar generation or a single-phase supply?
No to both. Legrand states that it is not designed for single-phase networks and does not support photovoltaic installations.2
What size cables fit the coils?
One cable up to 50 mm², 12.4 mm across, with the coil's internal plastic support fitted, or up to 70 mm², 15.3 mm across, with the support removed.2