Voltage drop calculator

Work out the voltage drop on a cable run from its size, length and load, and the smallest cable that keeps it within 3% or 5%.

Cables and conductors Updated Free, no sign-up

100over100of35 mm² copperat400three-phase

390.5at the load2.38drop126.1longest run within 3%

501001502002500route length, m7.5%10%3%5%25 mm²50 mm²126.1 m210.1 m

Every copper size on this run

  • 6 mm²13%23.12 m
  • 10 mm²7.79%38.5 m
  • 16 mm²4.97%60.31 mSmallest within 5%
  • 25 mm²3.22%93.14 m
  • 35 mm²2.38%126.1 mSmallest within 3%
  • 50 mm²1.81%165.6 m
  • 70 mm²1.32%227.5 m
Example values
Circuit

Common supplies

Circuit
V
Load and route
A

From the supply to the load

Cable
Cable data
Conductor
Conductor temperature

Per conductor, at operating temperature

Ω/km

Per conductor; 0.08 if not stated

Ω/km
More options
Copper conductor

Typically 0.8 to 1.0

Load

Voltage drop, line-to-line

9.519V

2.38% of the 400 V nominal, balanced three-phase, 35 mm² copper.

Voltage at the load, line-to-line
390.5 V
Longest run within 3%
126.1 m
Smallest size within 3%
35 mm²
Smallest size within 5%
16 mm²
Conductor resistance at 70 °C
0.6269 Ω/km
  • Pass: Within the 3% design target0.62% spare
  • Pass: Within the 5% design target2.62% spare
How it’s calculated
  1. R70 = R20 × (234.5 + T) ÷ (234.5 + 20)=0.524 × (234.5 + 70) ÷ 254.5=0.6269 Ω/km
  2. ΔU = √3 × I × L × (R cos φ + X sin φ)=1.732 × 100 × 0.1 × (0.6269 × 0.8 + 0.08 × 0.6)=9.519 V
  3. ΔU% = ΔU ÷ U × 100=9.519 ÷ 400 × 100=2.38%

100 A in each line over 100 m of 35 mm² copper at 400 V balanced three-phase drops 9.519 V, 2.38% of the supply. The smallest size within 3% is 35 mm².

Tip: 3% and 5% are common design targets, not limits. Your wiring rules set the limit for each type of circuit.

How to calculate voltage drop

Voltage drop is the current times the cable’s resistance and reactance over the route length, counted twice on a single-phase or DC circuit and multiplied by √3 on a balanced three-phase circuit. The calculator works it out for a standard IEC 60228 cable size or for the resistance and reactance the manufacturer states, and names the smallest standard size that keeps the run within 3% and within 5%.

Single-phase AC

ΔU = 2 × I × L × (R cos φ + X sin φ)

Current flows out on the line and back on the neutral, so the route length counts twice. L is the one-way route length in km, R and X are per conductor in Ω/km, and cos φ is the power factor.

Balanced three-phase AC

ΔU = √3 × I × L × (R cos φ + X sin φ)

This is the drop between lines. A balanced load puts no current in the neutral, and √3 converts the drop in one line to a line-to-line figure.

DC

ΔU = 2 × I × L × R

There is no reactance and no power factor, so the drop is the current times the loop resistance. On a 24 V supply, a 1.2 V drop is already 5%.

As a percentage

ΔU% = ΔU ÷ U0 × 100

Divide by the nominal supply voltage, line-to-line for three-phase. Wiring rules state their limits in this form, from the origin of the installation to the load.

For a standard size, R is the IEC 60228 maximum resistance at 20 °C, corrected to the operating temperature: 70 °C for PVC insulation and 90 °C for XLPE. Copper at 70 °C has 19.6% more resistance than at 20 °C. X is fixed at 0.08 Ω/km for every size, the value the Schneider Electric Electrical Installation Guide gives for use when the manufacturer states none.

Voltage drop examples

A 63 A three-phase sub-main over 80 m

A sub-main to a plant room carries 63 A in each line at a power factor of 0.8. It runs 80 m from the main board on 16 mm² copper PVC cable. The drop is 10.03 V, or 2.51% of 400 V. 10 mm² gives 3.93% and 25 mm² gives 1.62%.

The 2.51% comes out of the budget for the whole installation. Final circuits fed from the plant-room board have 2.49% left against a 5% target, and 0.49% against 3% for lighting.

Voltage drop, line-to-line 10.03 V Open in the calculator

A 15 kW motor starting direct on line

A 15 kW pump motor at 400 V, 92% efficient with a power factor of 0.85, draws 27.69 A at full load (see the motor full-load current calculator). Direct on line, it starts at 5 to 7 times that current, at a power factor near 0.35. Take 6 times, 166 A.

On 60 m of 10 mm² copper, the running drop is 5.477 V, 1.37%. The starting drop is 14.51 V, 3.63%. Six times the current gives only 2.6 times the drop, because R is multiplied by cos φ, and cos φ falls from 0.85 to 0.35. On 6 mm², the formula gives 23.54 V, 5.89%, but the full cable impedance drop, current times impedance, is about 16% of the supply. The first-order formula holds only up to 10%, so the calculator does not show the voltage at the load.

The 3% and 5% limits apply in steady state, not during a start. Check the starting drop against what the motor and its starter need. The dip that other loads see comes from the cables upstream, so run the sub-main at the starting current too.

Voltage drop, line-to-line 14.51 V Open in the calculator

A 24 V DC sensor supply over 50 m

5 A on 1.5 mm² copper over a 50 m route loses 7.239 V at 70 °C. That leaves 16.76 V at the far end. IEC 61131-2 sets 20.4 V, 24 V less 15%, as the lowest supply for 24 V DC PLC equipment. At 20 °C the drop is still 6.05 V. A cable carrying 5 A runs well below 70 °C, so the true figure is between the two.

4 mm² keeps the far end at 21.24 V, and 10 mm² keeps the drop within 5%. A power supply near the load is usually cheaper than 10 mm² cable.

Voltage drop 7.239 V Open in the calculator

Voltage drop per ampere per metre (mV/A/m)

Copper cable to IEC 60228 at a power factor of 0.8 lagging. Multiply by the current in amps and the one-way length in metres, then divide by 1000, for the drop in volts. Single-phase figures count both conductors; three-phase figures are line-to-line.

Voltage drop per ampere per metre (mV/A/m), values in mV/A/m
Size (mm²)Single-phase, 70 °C (mV/A/m)Three-phase, 70 °C (mV/A/m)Three-phase, 90 °C (mV/A/m)
1.523.320.121.5
2.514.312.413.2
48.927.738.23
65.995.195.52
103.603.123.32
162.301.992.11
251.491.291.37
351.100.9521.01
500.8370.7250.767
700.6090.5270.557
950.4650.4030.424
1200.3890.3370.353
1500.3330.2890.302
1850.2860.2470.258
2400.2400.2080.216
3000.2110.1830.189

Download this table (CSV)

Maximum conductor resistance at 20 °C (Ω/km)

IEC 60228 maximum DC resistance per kilometre for plain copper and aluminium conductors. A cable that conforms is at or below these values. IEC 60228 lists aluminium conductors from 10 mm².

Size (mm²)Copper, strandedCopper, flexibleAluminium, stranded
0.536.039.0Not listed
0.7524.526.0Not listed
118.119.5Not listed
1.512.113.3Not listed
2.57.417.98Not listed
44.614.95Not listed
63.083.30Not listed
101.831.913.08
161.151.211.91
250.7270.7801.20
350.5240.5540.868
500.3870.3860.641
700.2680.2720.443
950.1930.2060.320
1200.1530.1610.253
1500.1240.1290.206
1850.09910.1060.164
2400.07540.08010.125
3000.06010.06410.100
4000.04700.04860.0778
5000.03660.03840.0605
6300.02830.02870.0469
8000.0221Not listed0.0367
10000.0176Not listed0.0291

Source: Classification of conductors according to IEC 60228, February 2021

Questions about voltage drop

What voltage drop is acceptable?

IEC 60364-5-52 Annex G recommends a maximum from the origin of the installation to any load point. From a public LV network, it is 3% for lighting and 5% for other uses. From a private supply, such as a site’s own HV/LV substation, it is 6% and 8%. BS 7671 Appendix 4 uses the same four figures. The NEC gives 3% for a branch circuit and 5% for feeder and branch together, in informational notes that are advisory. The calculator uses 3% and 5% as design targets. Your wiring rules set the limit.

Does the 5% apply to each cable?

No. The limit runs from the origin of the installation to the load, so the drops of cables in series add. On a balanced three-phase cable, the percentage of line-to-line voltage equals the percentage of line-to-neutral voltage, so a single-phase circuit off a three-phase sub-main adds directly. After the 2.51% sub-main in the first example, a 32 A EV charger 40 m away on 6 mm² copper adds 4.10%, which makes 6.61% in total. On 10 mm² it adds 2.44%, 4.95% in total. The smallest sizes the calculator names assume the whole 3% or 5% is available to one cable.

How much does reactance matter?

On small cables, resistance dominates. At a power factor of 0.8, the reactance term is 9% of the drop on 35 mm² copper, 25% on 120 mm² and 40% on 240 mm². At unity power factor it is zero. The fixed 0.08 Ω/km is typical of multicore cable. Single-core cables, and single-core cables laid apart in particular, have a higher reactance. For a large single-core run, the standard-size result is therefore low. Enter the manufacturer’s R and X instead.

Is this a cable sizing calculation?

It is one of three checks. The cable must also carry the design current in its installation method without exceeding its insulation temperature. Its protective device must also disconnect a fault in the required time. On long runs, 24 V DC circuits and motor circuits, voltage drop often decides the size. On short runs, current-carrying capacity usually decides it.

Limits of this result

  • Standard sizes use the IEC 60228 maximum DC resistance, so a real cable usually drops slightly less. Above about 150 mm², AC resistance rises with skin effect: use the manufacturer’s AC values for large conductors.
  • The AC result is a first-order approximation, valid while the cable impedance drop is no more than 10% of the supply. Outside that range the voltage at the load is not shown.
  • The three-phase formula assumes a balanced load. It does not model neutral current, harmonics, motor starting or loads spread along the route.
  • This is not a current-carrying capacity, protection, fault-level or wiring-rules check.

Measure it continuously

The calculation assumes one steady current at one power factor. A ZEM at the load end measures the voltage that the load actually receives as its current and power factor change.

Related guides

Sources

  1. Calculation of voltage drop in steady load conditions (opens in a new tab) Schneider Electric Electrical Installation Guide, accessed 2026-09-23
  2. IEC 60228:2023 Conductors of insulated cables (opens in a new tab) International Electrotechnical Commission, Edition 4.0, 2023-12
  3. Classification of conductors according to IEC 60228 (opens in a new tab) (PDF) Nexans, February 2021