Siemens SENTRON PAC3200

Power monitoring device

A 96 × 96 mm panel meter for low-voltage distribution, on 1 A or 5 A current transformers, with Class 0.5S active energy and more than 50 measured values. It speaks Modbus TCP on its own Ethernet port, and Modbus RTU through the PAC RS485 expansion module.

Siemens SENTRON PAC3200
  • Modbus RTU
  • Modbus TCP

Power monitoring device

Download Edge template

Compatibility

Compatible with EpiSensor Edge over Modbus RTU and Modbus TCP.

Connect its RS-485 port to a Modbus Interface or to a serial interface on the Gateway, or use its Ethernet port for Modbus TCP. Edge polls it with its Modbus client.

Edge reads 32 values from it, listed under Interface.

Connect it with

Specifications

The SENTRON PAC3200 is Siemens' panel-mounted power monitoring device for low-voltage switchboards. It fits a 96 × 96 mm cutout, 51 mm deep, and measures single-phase, two-phase and three-phase systems with two, three or four wires, in TN, TT and IT networks. The multi-range supply version connects directly to systems up to 690 V between phases; the extra-low voltage version up to 500 V. Current always comes from x/1 A or x/5 A transformers.1

Power
Mains. Auxiliary supply on L/+ and N/-: 95 to 240 V AC or 110 to 340 V DC on the multi-range version, 22 to 65 V DC on the extra-low voltage version, typically 8 VA. Do not take it from the voltage transformers.1
Active energy accuracy
Class 0.5S (IEC 62053-22)1
Reactive energy accuracy
Class 2 (IEC 62053-23)1
Measuring accuracy
Voltage ±0.3 %, current ±0.2 %, power ±0.5 %, frequency ±0.05 %1
Voltage inputs (multi-range supply)
Up to 400 V L-N and 690 V L-L (+20 %), 347 V and 600 V for UL1
Voltage inputs (extra-low voltage supply)
Up to 289 V L-N and 500 V L-L (+20 %)1
Current inputs
x/1 A or x/5 A current transformers, 100 A for 1 s1
Communication
Ethernet (RJ45) for Modbus TCP or SEAbus TCP; Modbus RTU with the PAC RS485 expansion module1
Dimensions
96 × 96 × 51 mm; 73 mm deep with an expansion module1
Protection
IP65 front; IP20 rear with screw terminals, IP10 with ring lugs1
Operating temperature
-10 to 55 °C1
Order numbers
7KM2112-0BA00-3AA0 (multi-range supply, screw terminals), 7KM2112-0BA00-2AA0 (ring lugs), 7KM2111-1BA00-3AA0 (extra-low voltage supply)1

Where it is used

Interface

This register map is for the 7KM2112-0BA00-3AA0 (firmware 2.4.2).

Communication settings

Ethernet protocol
Modbus TCP on port 502; the meter ships set to SEAbus TCP
Network settings
IP address, subnet and gateway, set on the display
RS-485
Modbus RTU with the PAC RS485 expansion module
Baud rate (RS-485)
4800, 9600, 19200 or 38400 bit/s; 19200 by default
Framing (RS-485)
8N2 (default), 8E1, 8O1 or 8N1
Unit address (RS-485)
126 by default
Response delay (RS-485)
0 to 255 ms; 0, the default, is automatic
Read functions
FC03 and FC04 on every measured value
Write function
FC16, for settings only
Read with
FC03 (holding registers)
Word order
High word first on every value
Addresses
Zero-based PDU addresses, as sent on the bus

From SENTRON PAC3200 Power Monitoring Device manual (A5E01168664B-04, 02/2008)1.

Register map

Download
PointAddressHexFormatScaleUnit
Voltage L1-N 1 0x0001 FLOAT32 ×1 V
Voltage L2-N 3 0x0003 FLOAT32 ×1 V
Voltage L3-N 5 0x0005 FLOAT32 ×1 V
Voltage L1-L2 7 0x0007 FLOAT32 ×1 V
Voltage L2-L3 9 0x0009 FLOAT32 ×1 V
Voltage L3-L1 11 0x000B FLOAT32 ×1 V
Current L1 13 0x000D FLOAT32 ×1 A
Current L2 15 0x000F FLOAT32 ×1 A
Current L3 17 0x0011 FLOAT32 ×1 A
Apparent Power L1 19 0x0013 FLOAT32 ×1 VA
Apparent Power L2 21 0x0015 FLOAT32 ×1 VA
Apparent Power L3 23 0x0017 FLOAT32 ×1 VA
Active Power L1 25 0x0019 FLOAT32 ×1 W
Active Power L2 27 0x001B FLOAT32 ×1 W
Active Power L3 29 0x001D FLOAT32 ×1 W
Reactive Power L1 31 0x001F FLOAT32 ×1 var
Reactive Power L2 33 0x0021 FLOAT32 ×1 var
Reactive Power L3 35 0x0023 FLOAT32 ×1 var
Power Factor L1 37 0x0025 FLOAT32 ×1 -
Power Factor L2 39 0x0027 FLOAT32 ×1 -
Power Factor L3 41 0x0029 FLOAT32 ×1 -
Voltage THD L1 43 0x002B FLOAT32 ×1 %
Voltage THD L2 45 0x002D FLOAT32 ×1 %
Voltage THD L3 47 0x002F FLOAT32 ×1 %
Current THD L1 49 0x0031 FLOAT32 ×1 %
Current THD L2 51 0x0033 FLOAT32 ×1 %
Current THD L3 53 0x0035 FLOAT32 ×1 %
Frequency 55 0x0037 FLOAT32 ×1 Hz
Total Apparent Power 63 0x003F FLOAT32 ×1 VA
Total Active Power 65 0x0041 FLOAT32 ×1 W
Total Reactive Power 67 0x0043 FLOAT32 ×1 var
Total Power Factor 69 0x0045 FLOAT32 ×1 -

Download the 7KM2112-0BA00-3AA0 register map as CSV

Siemens lists each value by offset, and the offset is the address sent on the bus: total active power is offset 65, which a 40001-style master shows as 40066. A read must start on the first register of a value, or the meter answers with an error.12

The ten energy counters are 64-bit floating-point values in Wh, varh and VAh at offsets 801 to 837, four registers each. The Edge template leaves them out because Edge has no 64-bit float format; the instantaneous values above are all 32-bit.1

Edge template

This JSON file supplies the register map. Applying it to an existing meter replaces its sensor list while retaining the site connection, unit ID and enable state.

ModelConnectionPointsVersionUpdatedDownload
7KM2112-0BA00-3AA0 Modbus RTU over RS-485, Modbus TCP 32 1.0.0 Download

Downloads need a signed-in account with Edge download access.

Use the template in Edge

  1. Import the JSON file

    On the target Gateway in Edge, open Settings, then Device Templates. Choose Import and select the downloaded JSON file. Confirm that the model and template name match your device.

  2. Load the map for your meter

    In the Modbus device wizard, choose the site connection and unit ID, then use Load Template to select the imported map. For an existing device, apply the template to that exact model. Its connection, unit ID and enable state are retained.

  3. Test a reading

    Use Test in the wizard and compare a known reading with the meter display. Check its unit, sign and scale, then confirm that timestamps keep advancing. These starter maps are read-only and leave exports off until you configure them.

Setup

  1. Choose the port

    Use the built-in Ethernet port for Modbus TCP, or fit a PAC RS485 expansion module for Modbus RTU on an RS-485 bus through a ZMB-31 or the Gateway's serial interface.1

  2. Set the network or bus

    For Ethernet, enter the IP address, subnet and gateway under Settings > Communication, then change Protocol from SEAbus TCP to MODBUS TCP and restart the meter. For RS-485, set the address, baud rate and framing under Settings > RS485 Module: the module starts at address 126, 19200 bit/s and 8N2.1

  3. Point Edge at it

    Add the meter to Edge as a Modbus TCP device on port 502, or as an RTU device with the same address, speed and framing as the module.1

  4. Read one register

    Import the template and read Voltage L1-N at offset 1. It arrives as a float in volts and should match the display.1

  5. Enable the map

    Once voltage, current and total active power match the display, enable the rest of the map and watch several fresh readings before you add exports or alarms.

Common questions

Why does the PAC3200 not answer Modbus TCP?
The Ethernet port ships speaking SEAbus TCP. Enter the network settings, change Protocol to MODBUS TCP under Settings > Communication and restart the meter. Modbus TCP then answers on port 502.1
Which function codes does the PAC3200 support?
Every measured value can be read with function code 3 or 4. Writable settings, such as the communication parameters from offset 63015, are written with function code 16.1
What are the RS-485 settings on the PAC RS485 module?
4800, 9600, 19200 or 38400 bit/s, with 8N2, 8E1, 8O1 or 8N1 framing. The module starts at address 126, 19200 bit/s and 8N2, speaking Modbus RTU with an automatic response time.1