Siemens SENTRON PAC4200
Power monitoring device
The PAC4200 provides built-in Ethernet and Modbus TCP for an installed meter estate. Siemens publishes voltage, current, frequency, power and energy offsets. Start with the two-register frequency and voltage reads below, use the meter display to establish the decoder once, then expand the point list. The published manual does not specify multi-register ordering; the procedure explains how to resolve that during commissioning.
Compatibility
Compatible with EpiSensor Edge over Modbus TCP
Siemens publishes a PAC4200 system manual with built-in Modbus TCP, Float measurement offsets and functions 03 and 04. Edge reads the meter over Ethernet as a Modbus TCP client. The manual does not state the multi-register word order, so the setup procedure selects it once against the meter display.
Installed PAC4200 with the complete 7KM order code, firmware and expansion modules recorded. Site check: select the Float32 byte order from the frequency and voltage reads before adding points. Siemens names PAC4220 as the successor for relevant order codes; do not transfer a PAC3220 decoder to this meter.
Connect it with
For the standard PAC4200 Ethernet interface
- Modbus
- Edge
- Platforms
Models
| Models | Interface | Route into Edge |
|---|---|---|
| SENTRON PAC4200 | Built-in 10/100 Ethernet with Modbus TCP and web server | Edge reads the built-in Modbus TCP interface. Record the exact identity and firmware and select the Float32 order once against the display. |
| PAC4200 with PAC RS485 expansion | Optional serial module and Modbus TCP to RTU gateway role | Treat the module, its slot and the downstream RTU topology as separate evidence. |
| SENTRON PAC4220 | Current successor named in Siemens product records | Use a PAC4220 guide and its own manual. Do not assume register or firmware equivalence. |
Specifications
The May 2019 manual documents Ethernet, Modbus TCP, web access, time synchronisation and an optional RS485 module. Appendix A.2.1 lists two-register Float measurements and permits functions 03 and 04. It does not explicitly state multi-register ordering; the setup procedure uses two display comparisons to select the decoder without assuming another meter’s representation.1
- Serial option
- Optional PAC RS485 expansion module; module and slot-specific gateway settings apply1
- Measurement update
- 200 ms update for instantaneous values and energy according to the retained manual1
- Access controls
- Password, hardware write protection, IP filtering and configurable Modbus TCP port are described in Siemens material12
- Lifecycle
- Legacy PAC4200 installed estate; check the exact order-code replacement record for PAC42202
Interface
Documented measurements and integration boundaries for SENTRON PAC4200.
- Voltage, current, frequency, active, reactive and apparent power are two-register Float values; select the byte order once during commissioning.
- Potential import and export energy counters must preserve direction, tariff, unit and reset behavior from the exact firmware map.
- Power quality, harmonics, demand and diagnostic values must remain distinct from billing, settlement and protection evidence.
- No configuration or control write is approved by this guide.
Assessment
Exact installed PAC4200 with retained firmware and order code, read over Modbus TCP; no writes and no billing, settlement or protection claim.
- InteroperabilityLimited
- Built-in Modbus TCP and offsets are published. The retained manual does not state the multi-register order, so it is selected against the display.1
- AccuracyNot yet assessed
- The measurement groups and Float offsets are documented. The byte order is chosen from two display comparisons and kept with the point list.1
- SecuritySupported with conditions
- Siemens documents passwords, write protection, IP filtering and configurable ports; the site must commission and retain those controls.12
- ReliabilityNot yet assessed
- Reject stale or partial reads and keep the selected decoder with the point list. The retained manual does not describe recovery after a communication loss.
- RuggednessSupported with conditions
- Panel-meter installation and environmental limits are published; the complete installed order code and enclosure still govern suitability.1
- ScalabilityLimited
- Ethernet and optional gateway roles are documented. Siemens publishes no concurrent-client limit, so use one bounded polling client.1
Setup
-
Record the installed identity
Capture the complete 7KM order code, firmware, serial number, supply variant, measurement wiring and every installed expansion module. Do not identify the meter from the PAC4200 family name alone.
-
Map the existing network
Record the Ethernet address, Modbus TCP port, unit identifier, web access, time source and any RS485 expansion-module gateway use. Preserve existing metering, commissioning and security ownership.
-
Read frequency and voltage
Use the May 2019 manual, Appendix A.2.1, pages 146–147. Function 03 or 04 reads line frequency at offset 55, voltage L1-N at 1, current L1 at 13 and total active power at 65. Each is a two-register Float in Hz, V, A or W respectively. Enter these published offsets in a zero-based client; a client requesting one-based register numbers needs 56, 2, 14 and 66. The frequency request PDU using function 04 is 04 00 37 00 02.
-
Prove a bounded read
Capture both registers in one read. Try the four common IEEE 754 Float32 byte arrangements ABCD, CDAB, BADC and DCBA in the Modbus data decoder, using the returned bytes in their original order. Select the arrangement that agrees with frequency and L1-N voltage on the simultaneous meter display, then confirm total active power and its sign. Synthetic bytes 42 48 00 00 decode to 50 Hz in ABCD order; this illustrates the decoder and does not establish the PAC4200 wire order. Save the selected arrangement with the site point list.
-
Keep writes outside monitoring
Use the meter's access controls and a read-only client design. Configuration changes, resets and gateway settings require a separate authorised commissioning procedure.
Common questions
- Can Edge read an installed Siemens PAC4200 today?
- Yes. Edge reads the built-in Modbus TCP interface with the published measurement offsets. Use the frequency and voltage read procedure on this page to select the decoder against the meter display, then configure a read-only point list.1
- Is a PAC4200 the same as a PAC4220 or PAC3220?
- No. PAC4220 is named as a successor for relevant legacy PAC4200 order codes, while PAC3220 is a different family. Each meter needs its own order-code, firmware and interface evidence.2
- Should Edge use the optional RS485 module?
- Use the built-in Modbus TCP interface. The optional module, its slot and its client or gateway role are separate installed equipment, and this page does not reuse another module's settings.1
Sources
- SENTRON PAC4200 system manual A5E02316180B-05 (opens in a new tab) (PDF)
- PAC4200 power monitoring device tender specification (opens in a new tab)
Further reading
Product names and trademarks belong to their owners. Publication does not imply endorsement or a commercial relationship.