Siemens PXC4.E16-2

Building automation controller

PXC4.E16-2, order S55375-C150, combines 16 onboard I/O points with TXM expansion and field-device integration. ABT Site defines the application and BACnet objects. Use the commissioned object schedule to read measurements; the limited E16S-2 variant and earlier E16 hardware are not interchangeable.

Siemens Desigo PXC4.E16-2
  • BACnet/IP

Building automation controller

Compatibility

BACnet/IP integration, build check required

The manufacturer documents BACnet/IP and the inspected Edge source contains a BACnet client. This guide applies only to Edge builds containing that client; a minimum released Edge version and physical controller pairing have not been verified.

Exact PXC4.E16-2 S55375-C150 with a commissioned BACnet/IP application. PXC4.E16S-2 has different field-integration limits. The supplied guide has no fixed object instances or Modbus register template. Edge build availability and physical pairing are not verified; this path requires a build containing its BACnet client. BACnet/SC is outside the proposed connection.

Connect it with

The commissioned controller exposes the required local or integrated points

  • BACnet
  • Edge
  • Platforms
Building automation controller
Interface
Gateway
Edge
Output
PXC4.E16-2PXC4.E16-2 BACnet/IP objects
Protected EthernetSegmented LAN
ZGW-20 GatewayHosts Edge locally
EpiSensor EdgeEdge BACnet client
Customer platformMQTT · API · files
BACnet/IP
Protected Ethernet
Runs locally
Optional onward data
Read the object identities from the commissioned application. A downstream Modbus meter may feed a BACnet I/O object, but its original register address is not the BACnet object instance. The source meter’s communications, scaling and refresh interval remain part of the project handover. The customer-platform output is optional; Edge remains the local system of record.

Models

Download
ModelsInterfaceRoute into Edge
PXC4.E16-2 · S55375-C15016 onboard points; TXM expansion; up to 40 M-Bus/Modbus integration points; KNX PL-LinkThis guide covers commissioned BACnet/IP measurements from the full -2 variant.
PXC4.E16S-2 · S55375-C15216 onboard points and TXM expansion; zero listed M-Bus/Modbus integration points and no KNX PL-Link devicesDo not use the full variant’s field-meter integration capacity for this limited variant.
Earlier PXC4.E16 and regional variantsDifferent hardware/order codes and documentationConfirm the exact datasheet and application; this guide is limited to the -2 generation.

Specifications

The full E16-2 has 12 universal I/O and 4 relay outputs. Its point budget separates physical I/O from integrated field data: up to 50 onboard plus TXM points and up to 40 integration points, for 90 combined. The apparent 250 M-Bus device address capacity does not create 250 freely usable measurement points.1

Exact hardware
PXC4.E16-2, S55375-C150; not PXC4.E16S-2 S55375-C1521
Supply and installation
AC or DC 24 V; DIN-rail or screw mounting; plug-in screw terminals1
Physical I/O
16 onboard: 12 UIO and 4 relays. Up to 50 onboard plus TXM points.1
Integrated measurements
Up to 40 total M-Bus, Modbus TCP and Modbus RTU data points; up to 90 combined I/O and integration points1
Serial field network
One configured RS-485 network for Modbus RTU or M-Bus level converters. M-Bus needs a level converter; device count is constrained by point and object capacity.1
KNX PL-Link
Up to 64 devices on the full E16-2. These do not count as integration points, but BACnet object limits still apply.1
BACnet and engineering
BACnet/IP or BACnet/SC; B-BC Rev 1.20. SC node only, not hub. ABT Site engineers and commissions the application.1
Networking
Two-port Ethernet switch and WLAN for engineering/commissioning; this guide uses the commissioned wired BACnet/IP network1
Installation envelope
Front parts in DIN cut-out: IP30; terminals: IP20. Operating ambient -5 to +45 °C or +50 °C depending on mounting orientation; follow the datasheet mounting table. Humidity 5–95%, non-condensing.1

Interface

Documented measurements and integration boundaries for PXC4.E16-2.

  • Measured temperatures or other local inputs exposed by the commissioned application.
  • Meter readings integrated over Modbus or M-Bus and mapped by the engineer to BACnet objects.
  • Object name, description, type, instance, engineering unit and source refresh interval.
  • Controller-side reliability or quality information used to distinguish a source failure from a valid reading.

Assessment

PXC4.E16-2 S55375-C150 over BACnet/IP. This is source-qualified guidance, not physical Edge/controller validation.

InteroperabilitySupported with conditions
BACnet/IP and conversion of integrated Modbus data into BACnet I/O are documented; identities belong to the engineered application.12
AccuracyNot applicable
Meter accuracy and local input suitability must be checked for the source measurement. The controller’s integration capacity is not a meter accuracy class.1
SecuritySupported with conditions
The controller documents HTTPS and BACnet/SC capability. This proposed BACnet/IP path needs the approved network boundary and does not claim Edge SC support.1
ReliabilitySupported with conditions
Object view exposes quality and reliability information for commissioning; retain those checks when identifying source failures rather than accepting discovery alone.3
RuggednessSupported with conditions
The datasheet distinguishes IP30 front parts from IP20 terminals and reduces the ambient ceiling for some mounting orientations. Use its mounting table rather than assuming every installation permits +50 °C.1
ScalabilitySupported with conditions
The full variant documents 50 physical I/O, 40 integration points and 64 KNX PL-Link devices with separate object constraints.1
LifecycleSupported with conditions
Current manufacturer documentation identifies the -2 order codes and ABT Site engineering path. Keep the versioned project and exact hardware identity for replacement.1

Setup

Read one commissioned measurement

Use a real object from this project’s approved point schedule. Device and object instances are assigned by the project; this is not a fixed register map or a preconfigured import.

Identity
Match the controller model, firmware, IP endpoint and BACnet device instance before selecting a point.
Object
Use the supplied object type and instance for one measured Analog Input or Analog Value. Record its name, engineering unit and source.
Operation
Read Present_Value only through the inspected Edge client path. Do not issue WriteProperty or change a command priority.
Reference
The controller web interface’s Object view and, for an integrated point, the corresponding field meter or sensor.
Quality
Check source freshness and reliability in the controller. This guide does not claim Edge automatically imports Status_Flags, Reliability, trend history or alarms.

Acceptance: Accept when object identity, unit, sign, value and update timing agree with the controller and original measurement. Discovery alone is not acceptance. If the BACnet client is absent from the installed Edge build, stop here and confirm build availability before planning the connection.

  1. Check the exact controller

    Confirm PXC4.E16-2 S55375-C150 and record firmware and ABT Site project version. Obtain authorised access and the project backup. The E16S-2 has no listed M-Bus/Modbus integration capacity; a visually similar controller is not enough to establish this route.

  2. Trace the source of each measurement

    Identify whether each requested point comes from onboard I/O, TXM, Modbus or M-Bus. For field meters retain their original map, scale and update interval. Siemens documents mapping integrated Modbus data to BACnet I/O objects; the mapping is application-specific, not a fixed controller register table.

  3. Identify the commissioned object

    Use the controller web interface’s Object view to find the point by name, description or type and inspect its properties. Record the BACnet device and object identifiers with the unit and source. Check quality or reliability in the controller before copying the identity into another system.

  4. Check the network and Edge build

    Confirm that the approved network uses BACnet/IP and that the installed Edge build contains its BACnet client. Source inspection does not establish the minimum released version. Do not connect this path directly to BACnet/SC or assume an MS/TP serial client. Retain the existing BMS security design.

  5. Compare one read before adding more

    Discover the intended BACnet device, select the approved measurement object and read Present_Value. Compare against Object view and the source instrument at the same time. Confirm the unit, sign and engineering scale; then add only the agreed list. Preserve the map for checks after application updates.

Common questions

Can it collect 250 M-Bus meters?
The datasheet lists addressing capacity of up to 250 meters via level converters, but also limits the full controller to 40 integration data points and applies BACnet object limits. Size the actual points needed from every meter; 250 addresses is not 250 unrestricted meter integrations.1
Is PXC4.E16S-2 equivalent for metering integration?
No. The type-summary table gives the S variant zero M-Bus/Modbus integration points, zero KNX PL-Link devices and zero configurable RS-485 field networks. Use the exact order code when selecting a controller for existing field meters.1
Does a downstream Modbus register become the same-numbered BACnet object?
No. Siemens maps integrated data into BACnet I/O objects in the engineered application. Use the project’s object list and property view to identify the measurement; do not convert a register address into an object instance by arithmetic.23
Does this require Building X?
The specification documents a local embedded web interface and BACnet/IP alongside Building X connectivity. This guide uses the commissioned local interface, not a cloud connection. Obtain ABT Site engineering access and applicable project entitlements from the system owner; no free engineering-tool licence is implied.1