Engineer inspecting closed distribution switchboards beside a guarded transformer enclosure

Transformer and distribution board monitoring

A meter at the incomer, meters on the feeders worth explaining, and a temperature probe where loading has to be read against heat.

Measure
Incomer active power, energy and per-phase current, then the feeders that carry the decision
Scale
Distribution board energy monitoring and branch circuit monitoring on one Gateway, up to 250 devices Gateway datasheet
Sensors
ZEM-65, 0.1 A to 3 kA, with ZEM-paired split-core CTs or Rogowski coils; the paired Rogowski options need no separate external integrator Wireless 3-Phase Electricity Monitor datasheet
On site
Interval demand and phase imbalance calculated where the meters are

How far down the board to go

Metering every way in a board costs more than it explains. Start at the incomer, add the feeders whose consumption changes a decision, and leave the rest until a question needs them.

How far down the board to go
Incomer onlyIncomer and selected feeders
Answers Total loading, demand and imbalanceWhich loads drive the peak, and what changed
Reconciles Against the supply meterFeeders against the incomer, with the unmetered remainder named
Typical kit One meterOne meter per feeder, on the same Gateway

Hardware for a board or transformer measurement

One meter per measured point. The CT choice is set by the current and by what will physically fit around the conductor.

If loading has to be read against temperature

Where the meters go on the hierarchy

Draw the hierarchy first. Each meter's parent decides what its reading can be compared with.

From field measurement to Edge

Each field signal reaches its named EpiSensor interface, reports through the site Gateway and is handled locally in Edge.

  • Wired
  • Zigbee
  • Edge
  • Platforms
Field measurement
Interface
Gateway
Local Edge
Optional output
Incomer
Material feeders
Per-phase detail
Enclosure temperature
ZEM-65Wireless 3-Phase Electricity Monitor
TES-21Probe Temperature Sensor
ZGW-20Gateway
EdgeLocal data, monitoring and rules
Customer platformOptional onward data
Voltage + CT inputs
Zigbee mesh
Probe measurement
Runs locally
Configured MQTTS / HTTPS
Customer platformOptional onward data
EdgeLocal data, monitoring and rules
ZGW-20Gateway
ZEM-65Voltage + CT inputs
Incomer
Material feeders
Per-phase detail
TES-21Probe measurement
Enclosure temperature
Configured MQTTS / HTTPS
Runs locally
Zigbee mesh
Sending data on to a customer platform is optional; Edge keeps working on site without one.
Where the meters go on the hierarchy
PositionWhat it tells youReferenceSensor
Incomer Total active power, energy, demand and per-phase current for the board State whether the measurement is on the primary or the secondary side, and use the matching voltage reference ZEM-65 (on this page), incomer
Material feeders Which loads drive the peak, and how they move against it Chosen by consequence: a spare way with no load explains nothing ZEM-65 (on this page), one per feeder
Per-phase detail Imbalance that a three-phase total hides Keep the per-phase currents; neutral current cannot be inferred from active power ZEM-65 (on this page)
Enclosure temperature How hot the panel or transformer room runs while it is loaded Equipment limits come from the equipment, not from a general room threshold Probe Temperature Sensor datasheet TES-21 (on this page)
  • Check more than the current rating. The aperture selector checks maximum current and the reviewed clear opening only. Output type, burden, accuracy class, insulation and installation category remain separate checks.

  • The ZEM accepts its paired Rogowski coils directly. The EpiSensor-supplied Rogowski options are paired with the ZEM input and need no separate external integrator. Do not generalise that pairing to an arbitrary Rogowski coil.

  • Leave work inside the board to a qualified electrician. Fitting CTs and voltage references is electrical work. Isolation, CT shorting and phase association are the electrician's, not the monitoring plan's.

Loading, demand and imbalance in Edge

The hierarchy lives on the Gateway, so the comparisons happen where the meters are.

Parent against children
A calculated sensor subtracts the metered feeders from the incomer, so the unmetered remainder is a value with a name.
Demand, not just energy
Interval demand is calculated from the same readings, on the interval the supply contract uses.
Imbalance is watched, not derived
Per-phase currents are kept as their own points, and a limit rule can compare them.
A rising panel temperature
A limit rule on the probe raises an alarm when the enclosure runs hotter than the equipment's own limit.

Commissioning checks

A competent person does the electrical work; these are the checks on what it produced.

  • Phase and polarity are confirmed

    With a known load running, compare each phase's current and the power direction against an independent instrument.

    Pass when every phase matches its label, and no channel reads negative when it should be importing.

  • CT ratios are recorded

    Write down the CT type, ratio, aperture and the conductor each one is fitted to, with a photograph.

    Pass when the record would let somebody else replace a CT correctly.

  • The board reconciles

    Compare the incomer with the sum of the measured feeders over one complete interval.

    Pass when the difference is stable and matches the loads known to be unmetered.

  • A load step moves parent and child

    Switch a significant load and watch the feeder and the incomer.

    Pass when both change together, by about the same amount, in the same interval.

  • The temperature point is where it says

    Photograph the probe's position and compare its reading with a handheld instrument at the same surface.

    Pass when the two agree, and the position is on the drawing.

Limits of this measurement

A meter reports what a circuit did. It decides nothing about what the circuit is allowed to do.

  • Monitoring does not establish transformer capacity, conductor ampacity, protection coordination, fault duty or code compliance.
  • A CT is chosen on aperture, output, burden, accuracy and installation category, not on a current rating alone.
  • A temperature reading means nothing without the equipment's own limit and a stated measurement position.
  • Electrical work stays with the qualified person who did it, including isolation and CT safety.

Sources

  1. IEC 61869 instrument transformers (opens in a new tab) (opens in a new tab) IEC
  2. Wireless 3-Phase Electricity Monitor datasheet (opens in a new tab) EpiSensor. Specifications, ranges and ordering codes.

Choose the CTs that will actually fit your board

An engineer can choose the CTs that fit, say which feeders are worth metering, and size the Gateway.

Build this system