Compatible through Modbus RTU

Eastron · Three-phase energy meterSDM630-Modbus

The SDM630-Modbus V2 is a direct-connected three-phase meter with RS-485 Modbus RTU and two pulse outputs. Edge can acquire its documented electrical measurements through ZMB-31 or an approved serial interface.

1documented interface
2Edge connection paths
7/8criteria evidenced
CAD-style illustration of an Eastron SDM630-Modbus V2 DIN-rail energy meter
SDM630-Modbus V2 form shown as a restrained editorial CAD-style illustration.

Choose the connection that matches the model

This guide covers the direct-connected SDM630-Modbus V2 over RS-485. SDM630-TCP, SDM630-Mbus, pulse-only, dual-tariff and SDM630MCT variants are separate products; do not assume their interfaces, wiring or register maps are interchangeable.

System architecture

RS-485 through ZMB-31

For a remote meter where a wireless bridge avoids a new long data-cable route

Modbus RTU · RS-485
EpiSensor wireless
Runs locally
Optional onward data
Field measurement
Interface
Gateway
Local Edge
Optional output
EastronSDM630-ModbusSDM630-Modbus RS-485
EpiSensor interfaceZMB-31Modbus RTU to the EpiSensor wireless network
EpiSensor GatewayZGW-20 GatewayHosts Edge locally
Local softwareEpiSensor EdgeModbus client + register map
Optional outputCustomer platformMQTT · API · files
Connect the commissioned two-wire RS-485 bus to ZMB-31, retain the meter's installed address and framing, and map only reviewed read-only points in Edge. Confirm the bus owner before adding another interface. The customer-platform output is optional; Edge remains the local system of record.

System architecture

Direct serial Modbus client

When an approved isolated serial interface is available at the Gateway

Modbus RTU · RS-485
Isolated serial
Runs locally
Optional onward data
Field measurement
Interface
Gateway
Local Edge
Optional output
EastronSDM630-ModbusSDM630-Modbus RS-485
Site interfaceIsolated serial interfaceApproved RS-485-to-host adapter
EpiSensor GatewayZGW-20 GatewayHosts Edge locally
Local softwareEpiSensor EdgeEdge Modbus client
Optional outputCustomer platformMQTT · API · files
Use the installed slave address, baud rate, parity and stop bits. A TCP-to-RTU bridge is another engineered boundary and does not make this product a native Modbus TCP meter. The customer-platform output is optional; Edge remains the local system of record.

Match the exact model to its interface

Use the complete catalogue number, not the family name, when selecting an Edge connection.

ModelsDocumented interfaceEpiSensor route
SDM630-Modbus V2RS-485 Modbus RTU · two pulse outputs · direct connection up to 100 AZMB-31 wireless bridge or an approved direct serial interface
SDM630-TCPEthernet Modbus TCP · separate productEngineer and document as a separate Ethernet integration
SDM630-Mbus / Mbus-2TWired M-Bus · separate productUse a qualified M-Bus master path; this Modbus map does not apply
SDM630MCT family1 A / 5 A CT-operated variants with their own wiring and documentsSelect and qualify the exact MCT model independently

What Edge can exchange

The exact list depends on the model and its published data map. Start with the monitoring and control points the project will actually use.

  • Phase-to-neutral voltage for 1P2W and 3P4W systems; the protocol marks these values unavailable for 3P3W where applicable
  • Phase current and neutral current where the wiring mode supports the measurement
  • Active, reactive and apparent power, power factor, phase angle and frequency
  • Import, export and total energy values from the register set matched to the installed model
  • Demand values and total harmonic distortion where the exact protocol revision exposes them
  • Freshness and communications state so a stale value or failed poll is never presented as a measured zero

Commission the interface, then preserve the map

A successful network connection is the start of the check, not the end.

Read-only verification

Read phase 1 line-to-neutral voltage

Use this check on an already installed 1P2W or 3P4W meter whose exact register map matches Eastron's V1.8 protocol document. It makes the 30001 display reference and the wire address explicit.

Function
FC04 Read Input Registers
Document reference
30001
PDU start
0 / 0x0000
Length
2 registers
Decode
IEEE-754 float32 · confirm normal or reversed register order
Engineering unit
V · multiplier 1 · offset 0

Acceptance: Compare the decoded value with the same phase shown on the front panel at the same time. Retain the raw response and confirmed byte/word settings, then observe several fresh timestamps before adding more points.

  1. Confirm the front label says SDM630-Modbus V2 and record the firmware/build display. The reviewed user-manual file is labelled 2023 V1.5 on its cover while its running header says V1.4, so preserve the actual document used.
  2. Have a qualified person confirm the electrical connection mode and installation. The phase-1 line-to-neutral worked check is not valid as a general 3P3W voltage check.
  3. Record the installed slave address, baud rate, parity and stop bits rather than applying defaults. Coordinate with the existing bus master before attaching another interface.
  4. Check RS-485 polarity, common reference, topology, bias and termination across the complete bus. Do not use a communications check as authority to alter live panel wiring.
  5. Configure the read-only voltage point above first. The current user manual says word order is set automatically to normal or reverse and cannot be changed from the front-panel menu. Test Edge's normal and word-swapped decode against a stable non-zero display value, then retain the verified setting without writing the meter.
  6. Do not write holding registers, reset energy counters, alter the meter's word order or deliberately switch electrical loads as part of this check.
  7. Keep one poll within the meter's documented request size and schedule the whole bus using observed response times, not only theoretical serial timing.
  8. Treat missing or stale telemetry as invalid. Do not gap-fill a failed poll with zero, especially in demand, energy and alarm workflows.

Assessment

This assessment applies to Read-only three-phase monitoring from SDM630-Modbus V2 through Edge. It separates protocol compatibility from the quality of public evidence and keeps unsupported criteria visibly unknown.

The assessment covers the direct-connected RS-485 product and the manufacturer's V1.8 Modbus map. It excludes SDM630-TCP, M-Bus, pulse-only, dual-tariff and CT-operated variants.

Measurement fitness

Supported with conditions

The meter publishes a broad three-phase measurement set, but availability changes with wiring mode and the direct-connected product must not be confused with CT-operated or differently certified variants.

Evidence: eastron-sdm630-product, eastron-sdm630-protocol, eastron-sdm630-manual

Reliability and recovery

Not yet assessed

The reviewed public documents do not establish comparable field-failure, bus-recovery or long-duration availability evidence for an Edge deployment.

No criterion-specific public evidence recorded.

Ruggedness

Supported with conditions

The manufacturer publishes DIN-rail dimensions and operating limits; final suitability depends on the panel enclosure, conductor protection, temperature and installation category.

Evidence: eastron-sdm630-product, eastron-sdm630-manual

Scalability

Supported with conditions

Addressable RS-485 supports multi-drop deployment, while bus length, topology, termination, polling schedule, response time and a single-master operating model constrain scale.

Evidence: eastron-sdm630-product, eastron-sdm630-protocol

Lifecycle and maintainability

Supported with conditions

Current product, download and protocol pages are available, but the reviewed user-manual file carries inconsistent visible revision labels. Preserve the exact files and installed identity with the Edge template.

Evidence: eastron-sdm630-product, eastron-sdm630-manual, eastron-sdm630-protocol

Rubric device-integration-v1 · 7 of 8 criteria currently evidenced · no overall score is calculated.

Sources

  1. SDM630-Modbus V2 product page (opens in a new tab)
  2. SDM630-Modbus V2 User Manual, cover 2023 V1.5 (opens in a new tab) (PDF)
  3. SDM630Modbus Smart Meter Modbus Protocol Implementation V1.8 (opens in a new tab) (PDF)
  4. Modbus specifications and implementation guides (opens in a new tab)

Reviewed by EpiSensor technical review on . Revision 1. Product names and trademarks belong to their respective owners; this guide does not imply endorsement or a commercial relationship.