Distributed energy

Solar PV monitoring

An independent meter on the PV output, another at the grid connection, and the inverter's own registers beside them for context.

ZEM-65 Wireless 3-Phase Electricity Monitor
ZEM-65Electricity metering
ZGW-20 Gateway
ZGW-20Gateway with Edge
Measure
PV AC output, site import and export, inverter state, and irradiance where performance has to be normalised
Calculate
Solar generation, self-consumption and export, from monitoring that reconciles
Sensors
ZEM-65, Class 0.5S to IEC 62053-22, import and export in both directions ZEM-63 datasheet (PDF, opens in a new tab)
On site
ZGW-20 Gateway, the energy balance, calculated where the meters are ZGW-20 datasheet (PDF, opens in a new tab)

Hardware for commercial solar monitoring

Two meters make the balance: one on the generation and one at the connection. The inverter adds detail that the meters cannot see.

If performance ratio is being calculated

ZMB-31 and ZIO-20 share one enclosure with different terminals inside, so the ordering code is what you specify.

The measurements a solar energy balance needs

Generation, import and export are three numbers that have to agree. Measure two of them and the third is arithmetic.

The measurements a solar energy balance needsOne meter at the connection and one on the PV output. Everything else on the board is the site's own load. Grid connection Site board Solar PV inverter Battery and inverter Generator EV charging board Import is positive and export is negative, at the connection ZGW-20 GatewayEdge on site ZEM-65 · connection ZEM-65 · PV output ZMB-31 The measurements a solar energy balance needsOne meter at the connection and one on the PV output. Everything else on the board is the site's own load. Grid connection Site board Solar PV Battery Generator EV charging ZGW-20 GatewayEdge on site ZEM-65 · connection ZEM-65 · PV output ZMB-31
One meter at the connection and one on the PV output. Everything else on the board is the site's own load.
Sensor positions for the measurements a solar energy balance needs
PositionWhat it tells youReferenceSensor
PV AC output What the plant generated, measured independently of the inverter State whether the meter covers one inverter, a group or the whole plant ZEM-63 datasheet (PDF, opens in a new tab) ZEM-65 (on this page), PV output
Grid connection Import and export, and the sign convention everything else is read against Confirm CT direction under both import and export ZEM-65 (on this page), connection
Inverter registers DC strings, operating state and alarms that no AC meter can see Register availability is model and firmware specific ZMB-3X datasheet (PDF, opens in a new tab) ZMB-31 (on this page)
Irradiance Whether a low day was the plant or the weather The transmitter's own range, scaling and maintenance plan ZIO-2X datasheet (PDF, opens in a new tab) ZIO-20 (on this page)
  • Inverter and meter will differ. They measure at different points with different losses between them. A stable difference is normal; a changing one is worth investigating.

  • Sign convention, once. Decide that import is positive and export negative, write it down, and check every meter against it during a known export period.

The energy balance in Edge

Self-consumption is not measured directly. It is what the balance leaves over, so the balance has to be right.

Self-consumption is derived
A calculated sensor takes generation minus export, on the same interval, with both inputs explicit.
A plant that has stopped
A limit rule on generation during daylight, or a no-data rule on the inverter, catches a plant that stopped without anybody noticing.
Both directions are kept
Import and export stay as separate points rather than one net figure, because a net number hides both.
Onward wherever it is needed
Edge exports the balance over MQTT or HTTP to a portfolio system, without the site depending on it.

Commissioning checks

Most solar monitoring arguments are about signs and boundaries. Settle both at commissioning.

  • Each meter is on its stated boundary

    Trace both meters on the single-line diagram and write what each one includes.

    Pass when the boundaries are on the drawing, and nothing is measured twice.

  • Signs are right in both directions

    Watch the connection meter during a known import period and during a known export period.

    Pass when import is positive and export negative, on every phase.

  • Meter and inverter are compared

    Compare the independent AC meter with the inverter's own total over a full day.

    Pass when the difference is stable and explained by the measurement points, not drifting.

  • Night and full output both look right

    Check the readings at night, at low generation and at full output.

    Pass when night generation is zero rather than a small positive or negative number.

  • Derived numbers are labelled

    Look at where self-consumption, performance ratio or avoided carbon appear.

    Pass when each one says what it was calculated from, and which system calculated it.

What this measurement does not tell you

A meter reports energy at a point. The rest is interpretation, and it needs its method stated.

  • Inverter data and an independent AC meter can legitimately differ, because they measure at different points.
  • Monitoring does not replace inverter protection, grid-code controls or a revenue meter's obligations.
  • Performance ratio and avoided-carbon figures need declared methods, reference data and matching periods.
  • A string-level fault may not be visible in the AC total at all.

Sources and related guides

Sources

Related

  • Battery demand response Application guide Measure the connection and the battery separately, read state of charge and limits from the BMS, and record events at the resolution the programme wants.
  • Generator remote monitoring Application guide Independent electrical measurement of what the generator carried, controller states for why, and fuel level, with the protection boundary left alone.
  • Three-phase power calculator Engineering tool Work out active, reactive and apparent power for a balanced three-phase load from voltage, current and power factor.
  • Interval demand calculator Engineering tool Turn the energy recorded in one demand interval into average demand in kW.

Reviewed by EpiSensor Engineering on . Revision 4.

Balance generation, import and export on one site

We will place the meters, check the inverter can be read, and write the balance with you.

Contact us