Fronius Smart Meter TS
Electricity meter
Monitor Smart Meter TS import/export and load data through an existing Fronius Datamanager 2.0. The meter keeps its RS485 connection to Fronius; Edge reads the Datamanager over Ethernet Modbus TCP. Start with meter unit ID 240 for serial address 1, discover its SunSpec meter model and compare readings with the local display.
- Modbus TCP
- Modbus RTU
Electricity meter
Compatibility
Read-only Modbus through Datamanager 2.0
Fronius documents Smart Meter TS installation with Datamanager 2.0 and external access to its connected meter through Modbus TCP. The Datamanager, rather than the meter terminals, supplies the SunSpec register endpoint.
Best-effort monitoring of TS 100A-1, TS 65A-3 and TS 5kA-3 through an installed Datamanager 2.0. Record the installed model and software, compare readings locally and preserve existing inverter controls. Direct polling of the TS serial bus and other Smart Meter families are outside this procedure.
Connect it with
-
Modbus Interface ZMB-3XFrom €399 ex VAT Configure Modbus Interface
-
Gateway ZGW-20From €899 ex VAT Configure Gateway
-
Evaluation Gateway on a Raspberry Pi Edge with one device licensedFree Set up Evaluation Gateway on a Raspberry Pi
Smart Meter TS is commissioned on a Fronius Datamanager 2.0 serial meter connection
- Modbus
- Edge
- Platforms
Models
| Models | Interface | Route into Edge |
|---|---|---|
| Fronius Smart Meter TS 100A-1 | Single-phase direct current measurement up to 100 A, nominal 230 V; RS485 with Modbus RTU. | Select for the appropriate single-phase circuit. CAT5 cabling in the instructions carries the serial link; it does not make this an Ethernet meter. |
| Fronius Smart Meter TS 65A-3 | Direct current measurement up to 65 A per phase, nominal 208 to 400 V; RS485 with Modbus RTU. | Match the wiring arrangement and conductor size to the model instructions. Do not apply the transformer-input configuration of the TS 5kA-3. |
| Fronius Smart Meter TS 5kA-3 | Transformer-connected current measurement with nominal 1 A or 5 A secondary inputs and a maximum input of 6 A; RS485 with Modbus RTU. | The 5kA model name is not a direct terminal-current rating. Select the CT ratio, burden, polarity and voltage configuration before commissioning. |
Specifications
Use the exact suffix to select the electrical connection. The two direct-connected models carry circuit current through the meter; the TS 5kA-3 receives current-transformer secondary signals. Transformer ratios and wiring errors affect the complete measurement chain.123
- TS 100A-1 input
- Single phase: nominal 230 V, operating range 161 to 276 V; maximum direct current 100 A.3
- TS 65A-3 input
- Nominal 208 to 400 V, operating range 166.4 to 480 V; maximum direct current 65 A per phase.1
- TS 5kA-3 input
- Nominal 400 to 480 V phase-phase or 230 to 277 V phase-neutral. CT secondary input 1 A or 5 A nominal, 6 A maximum. Current-output CTs are required; voltage-output sensors are excluded.2
- TS 5kA-3 ratios
- kCT and kVT settings each span 1 to 1000. The technical table limits kVT × kCT to 1000 for CT/5A. Check the complete transformer arrangement rather than multiplying the individual maxima.2
- Serial connection
- Electrically isolated, three-conductor RS485 with Modbus RTU. The Fronius setup specifies 9600 baud with no parity; the technical tables specify 8 data bits and 1 stop bit. Broader baud-rate and address ranges differ between menu and technical tables, so confirm the exact installed configuration.123
- Wiring and response
- CAT5 or higher twisted-pair cable; documented inverter-to-meter cable length up to 300 m. Termination uses 120 ohms at the specified bus ends. Listed serial response time is at most 200 ms; this does not specify measurement freshness.123
Interface
Documented measurements and integration boundaries for Smart Meter TS.
- Datamanager maps serial meter addresses 1, 2, 3, 4 and 5 to TCP unit IDs 240, 241, 242, 243 and 244. Specify the unit ID even when only one meter is connected; the inverter uses a different device identity.
- The direct-connected models distinguish measurement mode A, which totals energy without direction, from mode B, which separates imported and exported energy. Preserve the installed mode and metering location when interpreting a series.
- Datamanager exposes integer SunSpec meter models 201, 202 or 203 with scale factors, or floating-point models 211, 212 or 213. Discover the model ID and length before applying its point offsets. Changing the data-type setting changes subsequent register addresses.
- Start with voltage, current, active power and imported/exported energy in the discovered meter model. Apply each integer point’s scale factor, or its floating-point unit, and compare with Fronius displays. At the grid location positive power means import and negative means export; the load-location convention differs.
Assessment
Best-effort monitoring of TS 100A-1, TS 65A-3 and TS 5kA-3 through an installed Datamanager 2.0. Record the installed model and software, compare readings locally and preserve existing inverter controls. Direct polling of the TS serial bus and other Smart Meter families are outside this procedure.
- InteroperabilitySupported with conditions
- Datamanager exposes its connected serial meter over Modbus TCP with documented unit-ID mapping and SunSpec meter models. The Ethernet endpoint is Datamanager, not the TS meter.1234
- AccuracySupported with conditions
- Model-specific voltage, current and transformer requirements support selection. Correct circuit configuration, polarity and metering location remain essential.123
- SecurityNot yet assessed
- Datamanager has a separate Modbus control setting, but TCP monitoring still needs a protected site network.4
- ReliabilityNot yet assessed
- Datamanager defines unavailable values; compare live data and test meter disconnection and recovery during commissioning.4
- RuggednessSupported with conditions
- The manuals define DIN-rail mounting and model-specific housing and terminal protection. Select the enclosure and installation conditions for the exact meter.123
Setup
Confirm the Datamanager meter endpoint
For a meter configured at serial address 1, this read checks its SunSpec identity through Datamanager. Fronius numbers register 40001 from one; the raw Modbus request starts at 40000.
- Target
- Datamanager local IP; configured TCP port, default 502; unit ID 240
- Function
- FC03 Read Holding Registers
- PDU start
- 40000 decimal (0x9C40); a one-based client displays 40001
- Length
- 2 registers
- Decode
- Expect 0x5375 followed by 0x6E53, the ASCII marker SunS; no measurement unit or scale factor
- Acceptance
- Confirms the SunSpec endpoint, not measurement freshness or accuracy
Acceptance: Next read two registers at raw 40002 for the first model ID and length. Advance by 2 plus that length to the next model header; stop at ID 0xFFFF with length 0. Use the discovered meter model and compare its measurements with the local display.
-
Identify the circuit and exact meter
Record the full model, serial number, firmware where available, system wiring and whether the meter is primary or secondary. Select direct or transformer measurement from the circuit requirements.
-
Preserve the Fronius system connection
Record the inverter or Datamanager model, firmware, serial settings, meter address and termination. Do not add another polling master to a bus already operated by the Fronius system without an explicitly supported arrangement.
-
Verify the measurement configuration
For TS 5kA-3, record CT and VT ratios, CT burden, polarity and phase matching. For every model, verify meter location and import/export interpretation against the display and a known circuit condition.
-
Enable Datamanager TCP monitoring
In Datamanager Modbus settings select TCP data output and note the configured port, default 502. Leave inverter control via Modbus disabled and turn demo mode off, as demo mode returns fixed values without a connected device. Keep access on the protected site network.
-
Identify the meter and discover its map
For meter serial address 1 use TCP unit ID 240. Read holding registers at raw address 40000 to confirm the SunS marker, then scan model IDs and lengths. Choose the discovered meter model 201/202/203 or 211/212/213, rather than an inverter model or a copied fixed power address.
-
Compare a live monitoring series
Compare voltage and power with the Fronius display and verify direction under a known load. Check cumulative energy changes over a shared interval. Treat unavailable values as missing and test disconnection/recovery before relying on the series. Keep reset, export-limit and control commands outside this read-only setup.
Common questions
- Can Edge poll a Smart Meter TS directly?
- Use the documented Datamanager TCP route for a meter already connected to Fronius. The TS terminals remain an RS485 meter connection; this procedure leaves that bus under Fronius control. Direct serial polling needs the TS meter map and a separate bus arrangement.1234
- Can Datamanager SunSpec registers be used as the TS register map?
- No. The Datamanager manual describes meter data exposed by the Datamanager over Modbus TCP. Its selected SunSpec model, meter identity and sign convention belong to that endpoint. They cannot be copied to the direct TS serial connection.4
- Does TS 5kA-3 carry 5000 A through its terminals?
- No. The meter uses current transformers with nominal 1 A or 5 A secondary outputs; its maximum current input is 6 A. The primary circuit rating depends on the selected transformers and their configured ratios.2
Sources
- Fronius Smart Meter TS 65A-3 operating instructions (opens in a new tab)
- Fronius Smart Meter TS 5kA-3 operating instructions (opens in a new tab)
- Fronius Smart Meter TS 100A-1 operating instructions (opens in a new tab)
- Fronius Datamanager Modbus TCP and RTU operating instructions (opens in a new tab)
- SunSpec Device Information Model Specification v1.4 (opens in a new tab) (PDF)
Further reading
Product names and trademarks belong to their owners. Publication does not imply endorsement or a commercial relationship.











