Eastron SDM220/230
Single-phase energy meter
Two single-phase DIN-rail energy meters, two modules wide, for direct connection up to 100 A, with import and export energy, demand values and an RS-485 Modbus RTU port on one shared register map.
Also sold asSDM220-ModbusSDM230-ModbusSDM230M
Compatibility
Compatible with EpiSensor Edge over Modbus RTU.
Connect its RS-485 port to a Modbus Interface or to a serial interface on the Gateway. Edge polls it with its Modbus client.
Edge reads 24 values from it, listed under Interface.
Connect it with
-
Modbus Interface ZMB-3XFrom €399 ex VAT Configure Modbus Interface
-
Gateway ZGW-20From €899 ex VAT Configure Gateway
Specifications
The SDM220-Modbus and SDM230-Modbus are single-phase, two-wire energy meters in 36 mm DIN-rail housings, connected directly to circuits up to 100 A. Both measure voltage, current, active, apparent and reactive power, power factor and frequency, keep import, export and total counters for active and reactive energy, and record maximum power demand. The SDM230 adds resettable energy counters and a running-hours counter.23
- Power
- Self-powered from the measured supply. Draws less than 2 W and 10 VA from the circuit it measures.2
- Nominal voltage
- 230 V AC, 176 to 276 V operating range2
- Current (SDM220)
- 5(100) A direct connected3
- Current (SDM230)
- 10(100) A direct connected2
- Active energy accuracy
- Class 1 (IEC 62053-21); Class B (EN 50470-1/3)2
- Reactive energy accuracy
- Class 2 (IEC 62053-23)2
- Voltage and current accuracy
- 0.5 %2
- Legal metrology (SDM230)
- MID B+D certified, certificate 0120/SGS0206; 50 Hz for MID4
- Baud rate (SDM220)
- 1200, 2400, 4800 or 9600 bit/s, default 24003
- Baud rate (SDM230)
- 1200 to 38400 bit/s, default 96002
- RS-485 bus (SDM230)
- Up to 64 meters and 1,000 m per bus4
- Pulse outputs
- Two passive outputs: one configurable, one fixed at 1000 imp/kWh2
- Dimensions (SDM220)
- 36 × 92 × 65 mm (W × H × D)3
- Dimensions (SDM230)
- 36 × 100 × 63 mm (W × H × D)2
- Protection
- IP51, indoor use2
- Operating temperature
- -25 to 55 °C, 0 to 95 % RH non-condensing2
Where it is used
Solar PV generation, export and battery storage metering on single-phase supplies, from the import, export and net energy counters.
Solar PV monitoringTenant and departmental submetering up to 100 A, with the MID-certified SDM230 where a billing-grade kWh reading is needed.
Tenant submetering and cost allocationSingle-phase EV charger metering for load management.
EV charging load management
Interface
This register map applies to the SDM220-Modbus and SDM230-Modbus.
Communication settings
- Protocol
- Modbus RTU over two-wire RS-485
- Unit address
- 1 to 247, default 1
- Baud rate
- 1200, 2400, 4800 or 9600 bit/s, default 9600 on the SDM230
- Parity and stop bits
- None, even or odd parity with 1 stop bit, or no parity with 2 stop bits; default no parity, 1 stop bit
- Read functions
- FC04 for measurements, FC03 for settings; FC16 writes one setting per message
- Request size
- An even number of registers, up to 30 values (60 registers)
- Read with
- FC04 (input registers)
- Word order
- High word first on every value
- Addresses
- Zero-based PDU addresses, as sent on the bus
From SDM230Modbus protocol V1.11.
Register map
| Point | Address | Hex | Format | Scale | Unit |
|---|---|---|---|---|---|
| Voltage | 0 | 0x0000 |
FLOAT32 | ×1 | V |
| Current | 6 | 0x0006 |
FLOAT32 | ×1 | A |
| Active Power | 12 | 0x000C |
FLOAT32 | ×1 | W |
| Apparent Power | 18 | 0x0012 |
FLOAT32 | ×1 | VA |
| Reactive Power | 24 | 0x0018 |
FLOAT32 | ×1 | VAr |
| Power Factor | 30 | 0x001E |
FLOAT32 | ×1 | - |
| Phase Angle | 36 | 0x0024 |
FLOAT32 | ×1 | ° |
| Frequency | 70 | 0x0046 |
FLOAT32 | ×1 | Hz |
| Import Active Energy | 72 | 0x0048 |
FLOAT32 | ×1 | kWh |
| Export Active Energy | 74 | 0x004A |
FLOAT32 | ×1 | kWh |
| Import Reactive Energy | 76 | 0x004C |
FLOAT32 | ×1 | kVArh |
| Export Reactive Energy | 78 | 0x004E |
FLOAT32 | ×1 | kVArh |
| Total Power Demand | 84 | 0x0054 |
FLOAT32 | ×1 | W |
| Maximum Total Power Demand | 86 | 0x0056 |
FLOAT32 | ×1 | W |
| Import Power Demand | 88 | 0x0058 |
FLOAT32 | ×1 | W |
| Maximum Import Power Demand | 90 | 0x005A |
FLOAT32 | ×1 | W |
| Export Power Demand | 92 | 0x005C |
FLOAT32 | ×1 | W |
| Maximum Export Power Demand | 94 | 0x005E |
FLOAT32 | ×1 | W |
| Current Demand | 258 | 0x0102 |
FLOAT32 | ×1 | A |
| Maximum Current Demand | 264 | 0x0108 |
FLOAT32 | ×1 | A |
| Total Active Energy | 342 | 0x0156 |
FLOAT32 | ×1 | kWh |
| Total Reactive Energy | 344 | 0x0158 |
FLOAT32 | ×1 | kVArh |
| Resettable Total Active Energy | 384 | 0x0180 |
FLOAT32 | ×1 | kWh |
| Resettable Total Reactive Energy | 386 | 0x0182 |
FLOAT32 | ×1 | kVArh |
Download the SDM220-Modbus / SDM230-Modbus register map as CSV
Edge template
This JSON file supplies the register map. Applying it to an existing meter replaces its sensor list while retaining the site connection, unit ID and enable state.
| Model | Connection | Points | Version | Updated | Download |
|---|---|---|---|---|---|
| SDM220-Modbus / SDM230-Modbus | Modbus RTU over two-wire RS-485 | 24 | 1.0.0 | Download |
Downloads need a signed-in account with Edge download access.
Use the template in Edge
- Import the JSON file
On the target Gateway in Edge, open Settings, then Device Templates. Choose Import and select the downloaded JSON file. Confirm that the model and template name match your device.
- Load the map for your meter
In the Modbus device wizard, choose the site connection and unit ID, then use Load Template to select the imported map. For an existing device, apply the template to that exact model. Its connection, unit ID and enable state are retained.
- Test a reading
Use Test in the wizard and compare a known reading with the meter display. Check its unit, sign and scale, then confirm that timestamps keep advancing. These starter maps are read-only and leave exports off until you configure them.
Setup
-
Check the model
Only the Modbus versions have the RS-485 port: SDM220-Modbus, SDM230-Modbus and the dual-tariff SDM230-2T. The SDM230-Mbus speaks M-Bus and the SDM230-Pulse has pulse outputs only.5
-
Wire the bus
Daisy-chain the A and B terminals of every meter with screened twisted-pair cable, A to A and B to B, and fit a 120 Ω resistor at each end of the line.1
-
Set the address and speed on an SDM230
Hold Enter for 3 seconds, enter the password (1000 by default), then set a unique address from 1 to 247, the baud rate and the parity. The defaults are address 1, 9600 bit/s and no parity.2
-
Match Edge on an SDM220
An SDM220 ships at 2400 bit/s, not 9600. Set the Edge Modbus client to the address, baud rate and parity shown on the meter's display at start-up.3
-
Read one register
Import the Edge template and read Voltage at input register 0, two registers from an even address. Compare it with the display before you enable the rest of the map.1
Common questions
- Do the SDM220 and SDM230 use the same registers?
- The core measurements do. Voltage, current, power, power factor, phase angle, frequency and the import, export and total energy counters sit at the same addresses in Eastron's SDM230 protocol and in the mbmd register list for the SDM220.16
- What baud rate should I set?
- Whatever the meter shows at start-up. An SDM230 ships at 9600 bit/s and supports up to 38400 bit/s. An SDM220 ships at 2400 bit/s and tops out at 9600 bit/s.23
- What does the total active energy register count?
- It follows the measurement mode in holding register F920 hex: import plus export by default, import only, or import minus export. Check the mode before you bill from the total.1
- Why does the meter return an exception?
- Every value is two registers, so a request must ask for an even number of registers, and no more than 30 values at once. An odd count or a longer request returns an exception.1
- Can the SDM230 be used for billing?
- The MID version is certified under the Measuring Instruments Directive with certificate 0120/SGS0206, Class B for active energy, and works at 50 Hz only.4
Sources
- SDM230Modbus protocol V1.1 (opens in a new tab) (PDF)
- SDM230-Modbus user manual V1.8 (opens in a new tab) (PDF)
- SDM220-Modbus user manual V2.0 (opens in a new tab) (PDF)
- SDM230 series DIN rail mounted, single phase, 100A datasheet (opens in a new tab) (PDF)
- SDM230M series product page (opens in a new tab)
- SDM220 register driver (opens in a new tab)
- Eastron SDM220/230 device template (opens in a new tab)
- Eastron SDM220/230 register driver (opens in a new tab)
Further reading
Product names and trademarks belong to their owners. Publication does not imply endorsement or a commercial relationship.