Schneider Electric iEM3365

125 A direct-connected electricity meter

Choose the iEM3365 when the board design calls for direct metering up to 125 A. It suits a larger direct-connected feeder than the 63 A iEM3165. Check panel space, conductor requirements and the network route on the as-built board schedule.

Schneider Electric iEM3365 DIN rail energy meter with LCD and upper terminal block
  • BACnet MS/TP

125 A direct-connected electricity meter

Ask an engineer

Compatibility

Compatible with Edge through a BACnet router

The meter is a BACnet MS/TP field device. Edge reads its objects through the router connecting the serial trunk to BACnet/IP.

Match the full order code and the installed Device instance. The BTL listing identifies software 2.0.0 and the B-ASC profile.

Connect it with

When the meter is on the board’s MS/TP segment

  • BACnet
  • Edge
  • Platforms
125 A direct-connected electricity meter
Interface
Gateway
Edge
Output
iEM3365iEM3365
BACnet routerRoutes between the serial meter segment and the IP network.
ZGW-20 GatewayHosts Edge locally
EpiSensor EdgeBACnet/IP client + object map
Customer platformMQTT · API · files
BACnet MS/TP
BACnet/IP
Runs locally
Optional onward data
Ask the controls contractor for the router and the BACnet network number assigned to this board. Record the meter’s Device instance with its feeder name. The customer-platform output is optional; Edge remains the local system of record.

Models

Download
ModelsInterfaceRoute into Edge
iEM3365 / A9MEM3365Direct measurement from 1 to 125 A. For a feeder outside that range, assess a CT-operated meter and suitable transformers.Route the MS/TP meter through the building’s BACnet/IP router. For an energy report, separately record AI 27 and its timestamp at both ends of the interval. Subtract the readings and convert Wh to kWh.

Interface

Documented measurements and integration boundaries for iEM3365.

  • AI 22 reports total active power in kW. AI 27 reports cumulative imported active energy in Wh. Use the first for a load trend and the second for consumption over a reporting interval.

Assessment

Read-only electrical measurement through an existing MS/TP network.

InteroperabilityWell supported
BTL tested the MS/TP master interface, including ReadProperty and ReadPropertyMultiple, with software 2.0.0.2
AccuracySupported with conditions
Direct measurement from 1 to 125 A. For a feeder outside that range, assess a CT-operated meter and suitable transformers.1
SecurityNot yet assessed
Use the building operator’s approved network route for collection.1
ReliabilitySupported with conditions
Schneider states that energy and tariff measurements are retained through a power failure. Track sample timestamps to identify a gap in collection.1
RuggednessSupported with conditions
Schneider gives IP40 for the front panel. Check the complete installed enclosure against the board location.1
ScalabilitySupported with conditions
The meter supports up to 14 active change-of-value subscriptions. Count existing subscriptions before sizing another collector.1
LifecycleSupported with conditions
Retain the catalogue reference and installation settings. The shared user manual includes other meter variants that use a different protocol.1

Setup

  1. Identify A9MEM3365 on the board schedule and confirm the Device instance against the front-panel settings.

  2. Read Present_Value and Units for Analog Input 22 while the feeder load is stable.

    Compare with total active power on the meter display at the same time. Confirm that both readings cover all phases.

  3. Save the object identifier, units and timestamp with the board and feeder reference.