Schneider Electric iEM3265
CT-operated electricity meter
The iEM3265 reads a feeder through external current transformers with 1 A or 5 A nominal secondaries. On an existing board, record the CT nameplate ratio and the meter’s configured ratio before using its readings for a load survey.
Compatibility
Compatible with Edge through a BACnet router
The meter is a BACnet MS/TP field device. Edge reads its objects through the router connecting the serial trunk to BACnet/IP.
Match the full order code and the installed Device instance. The BTL listing identifies software 2.0.0 and the B-ASC profile.
Connect it with
When the meter is on the board’s MS/TP segment
- BACnet
- Edge
- Platforms
Models
| Models | Interface | Route into Edge |
|---|---|---|
| iEM3265 / A9MEM3265 | External current transformers, nominal 1 A or 5 A secondary. Include the transformer specification and available panel space in a new installation quote. | Route the MS/TP meter through the building’s BACnet/IP router. Use AI 27 for imported active energy in Wh. Keep the CT ratio and feeder identity with the trend when replacing the meter. |
Interface
Documented measurements and integration boundaries for iEM3265.
- AI 7 reports phase 1 current in amperes. AI 53 and AI 54 identify the configured CT primary and secondary currents. These two configuration objects are specific to the iEM3265 in this family.
Assessment
Read-only electrical measurement through an existing MS/TP network.
- InteroperabilityWell supported
- BTL tested the MS/TP master interface, including ReadProperty and ReadPropertyMultiple, with software 2.0.0.2
- AccuracySupported with conditions
- External current transformers, nominal 1 A or 5 A secondary. Include the transformer specification and available panel space in a new installation quote.1
- SecurityNot yet assessed
- Use the building operator’s approved network route for collection.1
- ReliabilitySupported with conditions
- Schneider states that energy and tariff measurements are retained through a power failure. Track sample timestamps to identify a gap in collection.1
- RuggednessSupported with conditions
- Schneider gives IP40 for the front panel. Check the complete installed enclosure against the board location.1
- ScalabilitySupported with conditions
- The meter supports up to 14 active change-of-value subscriptions. Count existing subscriptions before sizing another collector.1
- LifecycleSupported with conditions
- Retain the catalogue reference and installation settings. The shared user manual includes other meter variants that use a different protocol.1
Setup
-
Identify A9MEM3265 on the board schedule and confirm the Device instance against the front-panel settings.
-
Read Analog Input 7 at a stable load and compare the value and unit with phase 1 current on the front panel.
Compare AI 53 and AI 54 with the recorded CT ratio before applying any scaling in the collector.
-
Save the object identifier, units and timestamp with the board and feeder reference.
Sources
- iEM3100, iEM3200 and iEM3300 user manual, DOCA0005EN-16, May 2026 (opens in a new tab) (PDF)
- BTL listing 24079 for software 2.0.0 (opens in a new tab) (PDF)
Further reading
Product names and trademarks belong to their owners. Publication does not imply endorsement or a commercial relationship.