Schneider Electric iEM3165

63 A direct-connected electricity meter

For a tenant board within the 63 A direct measurement rating, the iEM3165 can report imported energy to the building system without a separate current transformer. Confirm the design current for the outgoing circuit and whether there is an existing BACnet trunk at the board.

Schneider Electric iEM3165 DIN rail energy meter with LCD and upper terminal block
  • BACnet MS/TP

63 A direct-connected electricity meter

Ask an engineer

Compatibility

Compatible with Edge through a BACnet router

The meter is a BACnet MS/TP field device. Edge reads its objects through the router connecting the serial trunk to BACnet/IP.

Match the full order code and the installed Device instance. The BTL listing identifies software 2.0.0 and the B-ASC profile.

Connect it with

When the meter is on the board’s MS/TP segment

  • BACnet
  • Edge
  • Platforms
63 A direct-connected electricity meter
Interface
Gateway
Edge
Output
iEM3165iEM3165
BACnet routerRoutes between the serial meter segment and the IP network.
ZGW-20 GatewayHosts Edge locally
EpiSensor EdgeBACnet/IP client + object map
Customer platformMQTT · API · files
BACnet MS/TP
BACnet/IP
Runs locally
Optional onward data
Ask the controls contractor for the router and the BACnet network number assigned to this board. Record the meter’s Device instance with its feeder name. The customer-platform output is optional; Edge remains the local system of record.

Models

Download
ModelsInterfaceRoute into Edge
iEM3165 / A9MEM3165Direct measurement from 0.5 to 63 A. The load current passes through the meter.Route the MS/TP meter through the building’s BACnet/IP router. For a circuit that exceeds the direct rating, compare the 125 A iEM3365 and the CT-input iEM3265.

Interface

Documented measurements and integration boundaries for iEM3165.

  • AI 27 reports cumulative active energy imported in Wh. AI 28 is the separate export counter. Select the import counter for a tenant consumption trend.

Assessment

Read-only electrical measurement through an existing MS/TP network.

InteroperabilityWell supported
BTL tested the MS/TP master interface, including ReadProperty and ReadPropertyMultiple, with software 2.0.0.2
AccuracySupported with conditions
Direct measurement from 0.5 to 63 A. The load current passes through the meter.1
SecurityNot yet assessed
Use the building operator’s approved network route for collection.1
ReliabilitySupported with conditions
Schneider states that energy and tariff measurements are retained through a power failure. Track sample timestamps to identify a gap in collection.1
RuggednessSupported with conditions
Schneider gives IP40 for the front panel. Check the complete installed enclosure against the board location.1
ScalabilitySupported with conditions
The meter supports up to 14 active change-of-value subscriptions. Count existing subscriptions before sizing another collector.1
LifecycleSupported with conditions
Retain the catalogue reference and installation settings. The shared user manual includes other meter variants that use a different protocol.1

Setup

  1. Identify A9MEM3165 on the board schedule and confirm the Device instance against the front-panel settings.

  2. Read Present_Value for Analog Input 27 twice and record both times.

    Divide Wh by 1,000 when comparing with a front-panel reading in kWh. Confirm the change over the interval agrees to the resolution of the display.

  3. Save the object identifier, units and timestamp with the board and feeder reference.