Measurlogic DTS 305
Power and energy meter
For a panel retrofit, identify the output of the existing current transformers. The 305 can be ordered for 333 mV or 5 A inputs. The choice affects whether the installed transformers can stay. A separate front-panel display is available when the operator needs a local reading.
Compatibility
Compatible with Edge over BACnet/IP or routed MS/TP
Measurlogic offers Ethernet and serial BACnet versions. Edge reads an Ethernet meter directly or reaches a serial meter through the site BACnet router.
The serial example applies to a label showing BACnet MS/TP ML. For other versions use the map corresponding to the installed interface.
Connect it with
For a meter commissioned for BACnet MS/TP
- BACnet
- Edge
- Platforms
For a meter commissioned for BACnet/IP
- Wired
- Edge
- Platforms
Models
| Models | Interface | Route into Edge |
|---|---|---|
| DTS 305 ordering options | Verify the CT secondary rating, feeder wiring and any remote display on the installed unit. | BTL listing 30593 covers the 3D4B serial ordering pattern at firmware 3.0a-1.0300. Match the full suffix and firmware for a project submittal. |
Interface
Documented measurements and integration boundaries for DTS 305.
- AI 5513 reports current on phase one in amperes.
Assessment
DTS 305 monitoring using the installed communications option.
- InteroperabilityWell supported
- The BTL listing identifies a defined serial order pattern and tested firmware.3
- AccuracySupported with conditions
- Check the CT secondary rating, feeder wiring and any remote display against the site requirements.1
- SecurityNot yet assessed
- Confirm the approved network route with the operator.1
- ReliabilitySupported with conditions
- Match the Device object identity and interface option before assigning readings to a circuit.2
- RuggednessNot yet assessed
- Confirm the enclosure and installation environment for the ordered meter.1
- ScalabilitySupported with conditions
- Each meter on the trunk needs a distinct MAC address and network-wide Device instance.2
- LifecycleSupported with conditions
- Retain the complete model code and fitted measurement options in the replacement schedule.1
Setup
-
Match the serial number and connected feeder to the operator’s point list.
Record the CT secondary rating, feeder wiring and any remote display.
-
On the ML serial version described in R23A, compare AI 5513 with the operator’s phase-one current reading at a stable load.
-
Record the observed object type, instance, engineering unit and time with the reference reading.
Sources
- DTS 305 specifications and ordering options (opens in a new tab)
- DTS BACnet MS/TP ML map, revision R23A (opens in a new tab) (PDF)
- BTL 30593, DTS serial meter ordering patterns and firmware (opens in a new tab) (PDF)
- DTS BACnet/IP map, version 2.0U (opens in a new tab) (PDF)