Veris Industries E50H2 and E50H5
Power and energy meter
For a feeder with existing voltage-output current transformers, record the CT primary rating and whether the output is 0.333 V or 1 V. Pick the H2 if the panel requires its phase-loss alarm contact. The H5 adds onboard logging for projects that need a local history.
Compatibility
Compatible with Edge through a BACnet MS/TP router
The two-wire RS-485 port serves BACnet MS/TP. Edge reads the meter through the building’s BACnet/IP router.
Use the object table for ZL0071-0F and confirm the suffix on the installed meter before commissioning.
Connect it with
For a meter commissioned for BACnet MS/TP
- BACnet
- Edge
- Platforms
Models
| Models | Interface | Route into Edge |
|---|---|---|
| E50H2 | BACnet MS/TP, one pulse contact input and a phase-loss alarm output. | Choose the channels needed for live monitoring. For a tender, BTL listing 23941 identifies E50H2 at software 1.026. |
| E50H5 | BACnet MS/TP, onboard logging and two pulse contact inputs. | Ask for the configured trend objects and logging interval if historical readings are in scope. |
Interface
Documented measurements and integration boundaries for E50H2 and E50H5.
- AI 2 reports total active power in kW. AI 1 reports cumulative active energy consumption in kWh.
Assessment
E50H2 and E50H5 serial BACnet collection.
- InteroperabilityWell supported
- The installation guide lists BACnet object instances, properties and engineering units.13
- AccuracySupported with conditions
- Match the 0.333 V or 1 V secondary and primary rating to the installed CTs.1
- SecurityNot yet assessed
- Confirm access to the serial network with the controls contractor.1
- ReliabilitySupported with conditions
- Use the local LCD for a parallel reading when accepting the trend.1
- RuggednessSupported with conditions
- Veris specifies an operating range of −30 to 70 °C. Check the actual panel temperature.1
- ScalabilitySupported with conditions
- The guide specifies serial rates from 9600 to 115200 bit/s. Record the trunk rate for the meter group.1
- LifecycleSupported with conditions
- Retain the exact model suffix and distinguish alarm contacts from onboard trend logging when quoting a replacement.2
Setup
-
Match the Device instance, meter suffix and CT type to the named feeder on the panel schedule.
-
Read Present_Value on Analog Input 2 at steady load.
Compare the total kW with the meter’s LCD and record the CT output setting, time and feeder label.
-
Keep the measurement name, object type, instance and unit with the reporting channel.
The same instance can represent a different quantity on another Veris family.
Sources
- E50H2 and E50H5 installation guide, ZL0071-0F (opens in a new tab) (PDF)
- E5x series ordering and feature comparison (opens in a new tab) (PDF)
- BTL listing 23941 for the E50H2 and E51H2 (opens in a new tab) (PDF)