Schneider Electric CCTFR6100Z3

Radiator thermostat

A battery-powered Zigbee radiator valve head from Schneider Electric’s Wiser range, set from 5 to 30 °C in 0.5 °C steps, with an M30 × 1.5 ring nut and a Danfoss RA adapter in the box.

Also sold asWiser Radiator Thermostat Z3

Schneider Electric CCTFR6100Z3
  • Zigbee

Radiator thermostat

Compatibility

Compatible with EpiSensor Edge over Zigbee.

Pair it with the Zigbee radio on an EpiSensor Gateway. Edge reads it locally on the Gateway.

Edge reads 5 values from it, listed under Interface.

Connect it with

Specifications

It is built for wet heating systems: Schneider rates it for water at 73 °C continuously and 110 °C at most, on a valve whose surface stays at or below 93 °C. It works in rooms from 0 to 45 °C and is rated IP30, so it belongs indoors in dry rooms.1

Power
Battery. Two 1.5 V AA alkaline cells, supplied with the thermostat.1
Setpoint range
5 to 30 °C, 0.5 °C steps1
Local adjustment
Twist cap, ±2 °C1
Valve connection
M30 × 1.5 ring nut; adapter for Danfoss RA valves1
Heating water
73 °C continuous, 110 °C maximum1
Valve surface temperature
93 °C maximum1
Operating temperature
0 to 45 °C1
Storage temperature
-10 to 55 °C1
Relative humidity
25 to 90 % operating1
Wireless
Zigbee, 2.4 GHz, 13 dBm (20 mW) maximum1
Radio range
0 to 30 m1
Protection
IP30, pollution degree 21
Dimensions
51 mm diameter, 93 mm high1
Standards
EN 60730-1, EN 60730-2-7, EN 60730-2-9, EN 300 3281

Where it is used

  • Room-by-room radiator control in offices, schools and housing, with schedules and set-backs held centrally in Edge automations.

    Indoor environmental monitoring
  • Reading heating demand from every radiator to see which rooms keep the boiler running, and setting them back outside occupied hours.

    Boiler performance monitoring

Interface

Readings and settings, with units and ranges where Schneider Electric publishes them. readable, readable and writable.

Download
ReadingUnitRange or valuesAccess
Measurements 4
Climate - - Read only
Local temperature °C - Read only
Running state - idleheat Read only
Pi heating demand % 0 to 100 % Read only
Controls 1
Occupied heating setpoint °C 7 to 30 °C Read and write

The thermostat reports its model as CCTFR6100 and uses the standard Zigbee thermostat cluster: local temperature, occupied heating setpoint, PI heating demand and running state.3

Its Zigbee definition writes the setpoint from 7 to 30 °C in 1 °C steps, a narrower range than the 5 to 30 °C the head accepts locally.13

Heating demand is the valve position: 0 % is fully closed and 100 % fully open. Running state reads heat while it is calling for heat and idle otherwise.2

Setup

  1. Fit it to the valve

    Screw the supplied M30 × 1.5 ring nut onto the valve, or fit the Danfoss RA adapter first on an RA valve, then mount the head.1

  2. Insert the batteries

    Fit the two AA alkaline cells supplied with it.1

  3. Open pairing in Edge

    In Edge, open pairing on the Gateway’s Zigbee network and put the thermostat into pairing mode as its leaflet describes. A thermostat already joined to another Zigbee network, such as a Wiser system, has to leave it or be reset first.

  4. Check one reading and one setting

    Confirm Edge identifies it as Schneider Electric CCTFR6100Z3. Compare the local temperature with a thermometer in the room, then write a setpoint a few degrees above it and check the heating demand rises.