Indoor environmental monitoring

A probe where people actually are, an outdoor reference to compare it with, and the ventilation state that explains the difference.

TES-21 Probe Temperature Sensor
TES-21Temperature sensing
ZGW-20 Gateway
ZGW-20Gateway with Edge
Measure
Occupied-zone temperature, an outdoor reference, the supply air and the ventilation plant's state
Good practice
An indoor air quality monitoring claim needs the instrument's own sensing principle stated
Sensors
TES-21, ±0.2 °C from 0 to 70 °C, 0.01 °C resolution Probe Temperature Sensor datasheet
On site
ZGW-20 Gateway, trends, alarms and integrations for the building Gateway datasheet

Name the decision before choosing a sensor

Comfort complaints, ventilation control, condensation risk and equipment protection need different variables, different locations and different response times. Write down the decision the measurement supports, then pick an instrument whose stated range and accuracy can support it.

Hardware for building temperature monitoring

Temperature comes from EpiSensor sensors. Humidity, carbon dioxide and air quality come from an instrument chosen for that job, read through an analogue or Modbus interface.

If the building needs more than temperature

If the plant has a controller with a register map

Where a room reading is representative

A sensor reports its own position. Choose positions that answer the question, and record what each one stands for.

From field measurement to Edge

Each field signal reaches its named EpiSensor interface, reports through the site Gateway and is handled locally in Edge.

  • Wired
  • Zigbee
  • Edge
  • Platforms
Field measurement
Interface
Gateway
Local Edge
Optional output
Occupied zone
Outdoor reference
Supply air or transmitter
Plant state
TES-21Probe Temperature Sensor
ZIO-20Analogue Signal Sensor
ZMB-31Modbus Interface
ZGW-20Gateway
EdgeLocal data, monitoring and rules
Customer platformOptional onward data
Probe measurement
Zigbee mesh
4–20 mA input
Modbus RTU · RS-485
Runs locally
Configured MQTTS / HTTPS
Customer platformOptional onward data
EdgeLocal data, monitoring and rules
ZGW-20Gateway
TES-21Probe measurement
Occupied zone
Outdoor reference
ZIO-204–20 mA input
Supply air or transmitter
ZMB-31Modbus RTU · RS-485
Plant state
Configured MQTTS / HTTPS
Runs locally
Zigbee mesh
Sending data on to a customer platform is optional; Edge keeps working on site without one.
Where a room reading is representative
PositionWhat it tells youReferenceSensor
Occupied zone What the people in the space actually experience Away from sun, supply jets, doors and local heat sources, unless one of those is the subject Probe Temperature Sensor datasheet TES-21 (on this page)
Outdoor reference How much of an indoor change came from the weather A shaded, weather-protected position, on the same clock as the indoor points TES-21 (on this page), outdoor
Supply air or transmitter What the ventilation is delivering, and any other variable being measured The instrument's own range, units and scaling, recorded with its model Analogue Signal Sensor datasheet ZIO-20 (on this page)
Plant state Whether the equipment that could explain a reading was running Proven states or current, rather than an inference from room temperature Modbus Interface datasheet ZMB-31 (on this page)
  • Co-locate before you trust a difference. Put two sensors side by side for long enough to see their offset and their time constants, then separate them.

  • Label inferred values as indications. A carbon dioxide figure derived from a volatile-organic-compound sensor is an indication. Keep the sensing principle visible wherever the number is shown.

Trends and alarms for an indoor environment

The building's readings sit together on the Gateway, with the plant state beside them.

A zone outside its range
A limit rule with a hold time, so a short excursion during a meeting does not become an alert.
A sensor that goes quiet
A no-data rule reports a silent sensor, so a flat line is never mistaken for a stable room.
Indoor against outdoor
A calculated sensor takes the difference between the zone and the outdoor reference, which is usually the useful number.
Control needs its own design
Edge can write to equipment, but a control action needs limits, interlocks, authority and a defined safe state for a stale reading.

Commissioning checks

These are the checks that stop a plausible reading being trusted too early.

  • Every point is recorded

    Write down the model, serial number, range, stated accuracy and calibration status of each measurement point.

    Pass when the list is complete, and any instrument without a stated accuracy is marked as indicative.

  • Co-located sensors agree

    Leave two sensors side by side for a day and compare their traces.

    Pass when the offset and the lag are known and written down before they are separated.

  • A known change appears

    Change the condition at one location deliberately and watch the trace and its timestamps.

    Pass when the change appears at the right place and time, and nowhere it should not.

  • A missing sensor is obvious

    Take one sensor off the network for longer than the no-data rule's time.

    Pass when the dashboard shows missing data, not a plausible default.

  • The positions still fit the use

    Re-walk the floor after a change of layout, partitioning or ventilation strategy.

    Pass when each sensor still answers the question it was installed for, or it moves.

Limits of this measurement

An environmental reading describes a position, at a time, with a stated instrument.

  • An indicative volatile-organic-compound or inferred carbon dioxide output is not a reference gas measurement.
  • Monitoring does not diagnose health effects, mould, ventilation compliance or a building defect.
  • One room does not characterise a building, and a corridor does not characterise a room.
  • Control from these readings needs its own limits, interlocks, authority and safe state.

Sources

  1. BME680 gas, pressure, temperature and humidity sensor (opens in a new tab) (opens in a new tab) Bosch Sensortec
  2. Probe Temperature Sensor datasheet (opens in a new tab) EpiSensor. Specifications, ranges and ordering codes.

Tell us what the readings have to decide

An engineer can propose the points and the instruments, and say plainly which variables EpiSensor measures and which come from a third party.

Build this system