Equipment performance

HVAC energy monitoring for commercial buildings

Use ZEM-65 meters to separate HVAC electricity by supply, see what runs outside the agreed schedule and choose which heating, cooling, fan or pump system needs a closer investigation.

ZEM-65 Wireless 3-Phase Electricity Monitor
ZEM-65HVAC supply metering
ZGW-20 Gateway
ZGW-20Gateway with Edge
Measure
Heating and cooling supplies, air-handling units and circulation pumps
Rule
HVAC submetering needs distinct electrical boundaries and an agreed operating schedule
Sensors
ZEM-65, electricity meters; optional ZMB-31 for documented controller registers
On site
ZGW-20 Gateway, Edge runs locally; onward platform connection is optional

Start with the HVAC end uses you can separate

A building supply meter cannot tell the facilities team which air handler runs overnight. Map the HVAC feeders and the equipment each serves, then meter the boundaries that answer a maintenance or scheduling question. A shared circuit remains a group measurement. A reversible heat pump has one electrical supply: use a validated operating-mode signal to split heating and cooling periods, without counting the same kWh twice.

Start with the HVAC end uses you can separate
Buyer decisionMeasurement neededWhat the result establishes
Which HVAC loads run outside the schedule? Separate electricity meters for heating or cooling plant, air handlers and pumpsConsumption by named supply during agreed occupied and unoccupied periods
Is a chiller, heat pump or boiler efficient? Electrical or fuel input plus delivered heating or cooling at the same boundaryAn equipment-performance calculation using the linked asset guide; electricity alone is insufficient
Can the controls be changed? Approved control sequence, suitable controller access and an accountable controls engineerA separate engineering task; this monitoring kit does not change plant commands

Hardware for HVAC electricity monitoring

Count independently metered supplies, then add controller acquisition only where the documented interface and site permissions permit it.

If the controller has documented registers and the segment allows this master

Keep heating, cooling and air movement identifiable

Build the point list around the electrical drawing, plant schedule and the question each reading answers. Keep electric input, fuel input and delivered heat as different quantities.

System architecture

From HVAC feeders to a local operating record

Electricity meters identify the supplies. A separate, optional Modbus path adds controller context. Both report through the Gateway to Edge.

Voltage + CT inputs
Zigbee mesh
Modbus RTU · RS-485
Zigbee mesh
Runs locally
Configured MQTTS / HTTPS
Field measurement
Interface
Gateway
Local Edge
Optional output
MeasurementHeating / cooling supply · Fans and circulation pumpsReversible heat pump or separately metered plant · A separate meter for each selected feeder
Third-party instrumentExisting HVAC controllerOptional documented mode, status and temperature registers
EpiSensor interfaceZEM-65Electricity per HVAC supply
Optional EpiSensor interfaceZMB-31Optional controller register interface
EpiSensor GatewayZGW-20Gateway
Local softwareEdgeLocal HVAC readings and trends
Optional receiving systemCustomer platformOptional portfolio analysis
Real EpiSensor products are shown. The ZEM-65 represents one meter per named supply, not one meter that separates every load. Existing controller points are third-party data; Edge runs on ZGW-20.
Sensor positions for keep heating, cooling and air movement identifiable
PositionWhat it tells youReferenceSensor
Heating and cooling electricity kW demand and cumulative kWh at each plant supply Record auxiliary heaters and packaged pumps included in the feeder; do not add them again as separate loads ZEM-65 (on this page)
Air-handling electricity Consumption and start and stop patterns by AHU If fans, reheat and other auxiliaries share the supply, name the value as AHU electricity rather than fan-only electricity ZEM-65 (on this page)
Circulation-pump electricity Whether the distribution circuit draws power during selected periods Electrical input alone does not establish water flow, head or pump efficiency ZEM-65 (on this page)
Controller operating context Heating or cooling mode, run state and temperatures where the exact controller exposes them Verify register meaning, units and timestamp against the controller; a command or enable flag is not proof that equipment is running ZMB-3X datasheet (PDF, opens in a new tab) ZMB-31 (on this page), optional
  • An occupied schedule is an input. Obtain opening hours, holidays, cleaning periods and permitted warm-up or setback operation from the site team. Record the time zone and daylight-saving treatment. Meter data does not identify occupancy by itself.

  • Gas-fired heating needs a fuel measurement. A boiler's electrical supply normally measures its auxiliaries, not its gas input. Use a separately specified fuel-meter path and the boiler performance guide for that boundary.

  • Temperature explains context, not efficiency. Use suitable outside-air and representative zone readings when they are available. A lower weekly kWh total may reflect milder weather or shorter occupancy; temperatures alone do not measure delivered heat.

Use HVAC trends to choose the next investigation

Keep raw meter readings in Edge and review aligned periods with the site schedule. More detailed portfolio or weather analysis can use a separately configured receiving platform.

A worked schedule comparison
For the illustrative four-supply office, agree 15-minute analysis intervals, retain source timestamps and calculate kWh from valid cumulative-register differences. Suppose one complete week totals 1,200 kWh across the four non-overlapping supplies, with 300 kWh outside the agreed occupied windows. The outside-hours share is 300 ÷ 1,200 = 25%. This is a measured share to investigate, not a 25% saving forecast. The analysis interval is not a claim about default device reporting or a prebuilt HVAC report.
Check start-up and shutdown together
Compare AHU and pump power trends with permitted start-up, shutdown and frost-protection periods. Confirm any apparent overnight run with the responsible operator before changing a schedule.
Investigate apparent heating and cooling overlap
Use separate plant meters and validated mode and status points to locate overlapping operation. Different zones, dehumidification or heat recovery may explain it. Coincident electrical demand alone cannot prove simultaneous heating and cooling or diagnose a controls fault.
Keep missing data visible
Configure and test a no-data rule for each required input. Exclude incomplete intervals from comparisons and report the missing coverage. Never treat a stale mode flag as current or a missing electricity reading as zero consumption.

Commissioning checks

Commission the electrical boundaries first, then validate the context used to interpret them.

  • Match each meter to a feeder

    Have a competent electrical installer confirm the circuit, voltage connections, CT selection and orientation under an approved installation procedure. Observe an authorised load change.

    Pass when the named feeder responds on the expected meter, phase readings are plausible and the included equipment is recorded.

  • Read the controller without disturbing its bus

    Check the register map, serial settings, address, data type, scale and existing master arrangement. Compare a mode change and temperature with the controller display using read-only acquisition.

    Pass when the readings match and the proposed Modbus master does not conflict with an existing BMS master; no control writes are configured.

  • Agree the calendar and clock

    Record occupied windows, exceptions, warm-up and protection periods. Compare meter and controller timestamps and verify the local-time conversion across a daylight-saving transition.

    Pass when one documented schedule and time basis classify every analysis interval consistently.

  • Reconcile one complete period

    Calculate each feeder's cumulative kWh change over identical start and end times, check resets or gaps, then sum only non-overlapping supplies and classify their intervals against the schedule.

    Pass when occupied plus outside-hours energy equals the complete-period total, and the raw readings reproduce the reported share.

  • Test loss of a measurement path

    Use an approved communications test to interrupt one reporting path without interrupting plant control, then restore it.

    Pass when the no-data condition reaches the agreed recipient and missing intervals stay distinguishable from zero load.

What an HVAC energy profile leaves unanswered

The first result is an operating record with named boundaries. Further conclusions need additional evidence.

  • Outside-hours electricity is not automatically waste: warm-up, ventilation requirements, frost protection and critical spaces can justify operation.
  • This kit does not establish chiller COP, heat-pump seasonal performance or boiler efficiency; these require matched output and input measurements under the linked asset-specific methods.
  • Monitoring does not replace the BMS, optimise setpoints automatically or certify ventilation, indoor air quality or occupant comfort.
  • A shared feeder cannot separate its connected loads in software. Unmetered electric reheat, gas or district heat remains outside the reported electrical total.
  • Savings need a defensible comparison with weather, occupancy, service conditions and data coverage considered. No savings percentage follows from the illustrative example.

Sources and related guides

Sources

Related

  • Chiller performance monitoring Application guide Measure chiller electrical input and delivered cooling over the same interval, calculate COP and kW per ton in Edge, and prove the numbers before using them.
  • Heat pump performance monitoring Application guide Measure delivered heat and every electrical input inside one boundary, then calculate heat pump COP and a seasonal performance factor you can defend.
  • Boiler performance monitoring Application guide Fuel or electricity in, useful heat out, and the firing state that says which periods can be compared. What the ratio means and where it stops.
  • Pump performance monitoring Application guide Electrical input, flow and differential pressure on the same clock, so a change in pump power can be read as speed, demand or degradation.
  • Indoor environmental monitoring Application guide Temperature in the occupied zone, an outdoor reference and the plant state that explains both, with the limits of an indicative air-quality reading.
  • Equipment performance monitoring boundaries Knowledge Base Define input, useful output, operating state and time boundaries for pumps, compressors, boilers, chillers and heat pumps.

Reviewed by EpiSensor Engineering on . Revision 4.

Send the HVAC feeder list and operating schedule

Include the equipment served by each supply, CT access and ratings, controller model and register map if available, and the operating question the team needs to answer. We can then scope the metering and commissioning work.

Contact us