GoodWe GW100K-ET-G10
Commercial hybrid inverter
A 100 kW three-phase hybrid inverter with eight MPPTs and two high-voltage battery inputs. This guide covers its documented EMS RS-485 monitoring path.
- Modbus RTU
Commercial hybrid inverter
Compatibility
Compatible through Modbus RTU
GoodWe documents the EMS RS-485 connection and publishes a read-only monitoring table within its third-party EMS protocol. This is a documented integration path, not a physical qualification or downloadable Edge template.
GW100K-ET-G10 in the July 2026 EMEA datasheet, ET 50–100kW user manual V1.2 of 2 July 2026, and Third-Party EMS Protocol MODBUS V1.1.1 linked by GoodWe for this family. No minimum firmware version is specified in the retained protocol. Confirm installed firmware and map availability during commissioning; older ET, ET G2, BT and other regional variants are separate scopes.
Connect it with
-
Modbus Interface ZMB-3XFrom €399 ex VAT Configure Modbus Interface
-
Gateway ZGW-20From €899 ex VAT Configure Gateway
For local monitoring through the dedicated EMS communication port
- Modbus
- Edge
- Platforms
Models
| Models | Interface | Route into Edge |
|---|---|---|
| GW100K-ET-G10, EMEA | 100 kW, three-phase; eight MPPTs; two battery inputs | This exact model and the documented EMS RTU route are the scope of the worked read. |
| GW80K-ET-G10 / GW99.99K-ET-G10 | Related regional models with different power ratings | Use their own rated limits and identity; a shared document does not make these the same device. |
| Legacy ET / ET G2 / BT / other regions | Different generations, topology or regional specifications | Do not carry over this map or connection procedure without matching manufacturer documentation. |
Specifications
GW100K-ET-G10 is the 100 kW selection in the EMEA ET 80–100kW hybrid range. It has eight MPPTs with two PV strings per MPPT and two high-voltage battery inputs. The July 2026 regional datasheet specifies 300–800 V battery operation and 110 A maximum continuous charge or discharge current per battery input. These are inverter limits, not permission to use an arbitrary battery: the battery system and BMS must also be compatible. Backup operation needs the separately specified STS box or cabinet.13
- Regional scope
- GW100K-ET-G10, EMEA July 2026 datasheet3
- Nominal AC power
- 100 kW, three-phase 220/380, 230/400 or 240/415 V3
- PV inputs
- Eight MPPTs, two strings per MPPT; 1000 V maximum input3
- PV voltage boundary
- 160–950 V MPPT operating range; 950–1000 V enters standby under datasheet footnote 13
- Battery inputs
- Two; 300–800 V operating range; 110 A maximum continuous current per input3
- Local EMS connection
- Port E: pin 1 RS485-A1, pin 2 RS485-B11
- Serial defaults
- 9600 baud, 8 data bits, no parity, 1 stop bit; address 247 before configuration2
- Protection and environment
- IP66; -35 to +60 °C; stated maximum operating altitude 4000 m3
- Backup topology
- Requires the specified separate STS box or cabinet3
Interface
Documented measurements and integration boundaries for GW100K-ET-G10.
- PV input voltage and current with the scaling stated for each register.
- Individual MPPT power, distinguished from total inverter and grid power.
- Battery and system operating status where supported by the installed firmware.
- Device serial number and external model name for identity checks.
Assessment
GW100K-ET-G10 in the July 2026 EMEA datasheet, ET 50–100kW user manual V1.2 of 2 July 2026, and Third-Party EMS Protocol MODBUS V1.1.1 linked by GoodWe for this family. No minimum firmware version is specified in the retained protocol. Confirm installed firmware and map availability during commissioning; older ET, ET G2, BT and other regional variants are separate scopes.
- InteroperabilitySupported with conditions
- The dedicated EMS RTU interface and monitoring table are documented; model, installed settings and firmware still bound the integration.12
- AccuracySupported with conditions
- The protocol states types, widths, scales and read cycles. It does not establish billing-meter accuracy for these inverter measurements.2
- SecurityNot yet assessed
- The RTU documents do not establish authentication, encryption or a guaranteed security-maintenance period.2
- ReliabilityNot yet assessed
- No measured availability or historical backfill contract is established for this monitoring path.12
- RuggednessSupported with conditions
- The regional datasheet specifies IP66 and -35 to +60 °C; installation limits and operating derating still apply.3
- ScalabilitySupported with conditions
- Addressed RTU monitoring supports integration, but an existing EMS must retain bus ownership and point read cycles must be respected.12
- LifecycleNot yet assessed
- Current dated documentation is available, without a stated guaranteed product support lifetime.1
Setup
Read PV1 voltage
The manufacturer’s monitoring table defines 35103 as a one-register U16 PV1 voltage, scale factor 10, in volts. The read cycle is one second.
- Read PDU
- 03 89 1F 00 01: FC03, literal address 35103 (0x891F), quantity 1.
- Synthetic response data
- 18 38 represents unsigned 6200. Divide by 10 to obtain 620.0 V.
- Identity first
- Read serial number 35003 across all eight registers; external model name 35060 spans sixteen registers.
- RTU envelope
- The client adds the configured address and standard Modbus CRC16. The PDU shown is not a complete RTU frame.
Acceptance: This is a synthetic decoding check, not a captured inverter response. Accept a measurement only after the identity, complete response, scaling and simultaneous reference agree. Successful monitoring does not qualify control or protection settings.
-
Identify model, region and firmware
GW100K-ET-G10 in the July 2026 EMEA datasheet, ET 50–100kW user manual V1.2 of 2 July 2026, and Third-Party EMS Protocol MODBUS V1.1.1 linked by GoodWe for this family. No minimum firmware version is specified in the retained protocol. Confirm installed firmware and map availability during commissioning; older ET, ET G2, BT and other regional variants are separate scopes.
-
Use the EMS port
Follow the installation manual for the dedicated EMS port E, pin 1 RS485-A1 and pin 2 RS485-B1. Verify bus ownership before adding a client. Do not attach the polling client to the battery CAN, meter or transfer-switch communication connections.
-
Match the configured serial settings
The protocol specifies 9600 baud with 8 data bits, no parity and one stop bit. Addresses are 1–247, with 247 as the factory default. Read the installed setting instead of assuming a default address is still valid.
-
Begin with identity and one monitoring read
Read the serial number at 35003 as eight registers and the external model name at 35060 as sixteen registers. Then use FC03 at literal decimal address 35103, quantity 1, for PV1 voltage. Do not subtract one from the documented address.
-
Check scaling and freshness
Decode the selected value as unsigned 16-bit, most significant byte first, and divide by the stated scale factor of 10 to obtain volts. The table lists a one-second read cycle for this point. Compare with a simultaneous local reading and keep stale or unavailable responses separate from zero.
-
Keep the first integration read-only
Use only the monitoring table. Do not copy the protocol’s third-party control sequences, heartbeat settings, charge/discharge commands or RTC writes into a monitoring client. The protocol includes inconsistent CRC wording beside CRC frame fields; use standard Modbus RTU CRC16 through the client, never disable frame integrity checking.
Common questions
- Is this a guide for the older 10 kW ET?
- No. GW100K-ET-G10 belongs to the current commercial platform. Legacy ET and ET G2 ratings and protocol maps must be matched separately.13
- Does WiFi or SEMS+ access provide this local Modbus connection?
- No. Vendor remote monitoring and the dedicated EMS RS-485 connection are different paths. The datasheet also lists Modbus TCP, but this guide does not infer TCP settings from a cloud connection.13
- Can I add this client beside an existing EMS?
- Not as a competing master on the same serial bus. Coordinate with the existing EMS owner or obtain measurements through its supported interface. Meter, battery and transfer-switch communication are separate connections with their own roles.1
- Why does the guide avoid control registers?
- The published document contains operating-mode and battery dispatch commands as well as measurements. Reading voltage does not validate their safety or the interaction with site controls. This guide stays within the read-only monitoring table.2
- Is there a documented minimum firmware version?
- The retained V1.1.1 simplified protocol does not state a minimum inverter firmware. Record the installed firmware and verify the intended monitoring entries during commissioning rather than inventing a universal firmware floor.2
Sources
- ET 50–100kW user manual V1.2, 2 July 2026 (opens in a new tab) (PDF)
- Third-Party EMS Protocol MODBUS V1.1.1, simplified version (opens in a new tab) (PDF)
- ET 80–100kW EMEA datasheet, July 2026 (opens in a new tab) (PDF)
- ET 50–100kW solution manual V1.3, June 2026 (opens in a new tab) (PDF)
Further reading
- GuideSungrow SH10RT
- GuideSolis 50 kW commercial hybrid: monitoring access and port roles
- ToolModbus data decoder
- ToolPV string sizing
- ToolModbus register address converter
- ToolRS-485 termination and bias
- ManufacturerGoodWe devices
- ProtocolModbus devices and register maps
- CategoryInverters and charge controllers
Product names and trademarks belong to their owners. Publication does not imply endorsement or a commercial relationship.









