Hager ECR300C
Three-phase energy meter
The ECR300C is a four-module, 3P+N meter for external 1 A or 5 A current transformers. Hager publishes the RS-485 settings, identity fields, instantaneous values and energy registers. Edge can read those operational values over Modbus RTU, but that monitoring path is not a revenue or settlement metering system.
- Modbus RTU
Three-phase energy meter
Compatibility
Compatible for read-only Modbus RTU monitoring
Hager publishes an exact ECR300C product record, a model manual and Modbus table revision 1.14. The table identifies the ECR300C as a 3P_CT Modbus model and documents function 03 reads for identity, instantaneous measurements and energy.
ECR300C with a verified product code, firmware revision and external CT ratio. Use one commissioned read-only Modbus RTU client path. Exclude tariff changes, network-setting changes, partial-energy resets and every other write. Preserve the meter and installation controls required for any legally relevant energy total.
Connect it with
-
Modbus Interface ZMB-3XFrom €399 ex VAT Configure Modbus Interface
-
Gateway ZGW-20From €899 ex VAT Configure Gateway
When the ECR300C RS-485 terminals can join a correctly engineered, read-only Modbus segment
- Modbus
- Edge
- Platforms
Models
| Models | Interface | Route into Edge |
|---|---|---|
| ECR300C | Screw-terminal Modbus RTU, 3P+N, external 1 A or 5 A CT input, MID variant | Use this guide only after identity registers return ECR300C and the installed CT ratio is recorded. |
| ECR301C and ECR302C | Related 3P_CT models with different market or three-phase energy-summation scope | Treat as separate variants. Do not infer billing scope or energy behaviour from ECR300C. |
| ECA300C family | Agardio RJ45 connection rather than the ECR300C screw-terminal interface | Use the exact ECA model and connection documentation instead of this wiring path. |
Specifications
The ECR300C is a CT-connected meter. Its displayed and primary-side Modbus values depend on the commissioned CT ratio, while the map also provides a separate secondary-side table. Mixing those two groups would create a large scaling error.23
- CT range
- Primary setting 1 to 1,200 A for /1 A CTs or 5 to 6,000 A for /5 A CTs2
- Voltage range
- 92 to 276 V phase-neutral and 160 to 480 V phase-phase1
- Serial interface
- Three-wire RS-485 Modbus RTU; address 1 to 247; 1,200 to 38,400 bit/s; configurable parity and stop bits12
- Energy calculation
- ECR300C uses the documented magnitude summation method for three-phase energy3
- Environment
- -25 to +55 °C operating range; IP20 device enclosure; DIN-rail installation1
Interface
Documented measurements and integration boundaries for ECR300C.
- Vendor, product code, software version, hardware version, serial number and production date from the identity block.
- Phase-to-neutral and phase-to-phase voltage, phase current, neutral current and frequency.
- Active, reactive and apparent power by phase and in total, with the documented sign convention retained.
- IEC and IEEE power-factor values kept distinct rather than merged into one unsigned percentage.
- Imported and exported active energy, reactive energy, tariff totals and partial totals supported by the installed firmware.
- CT primary and secondary configuration recorded beside every current, power and energy stream.
Assessment
Exact Hager ECR300C with verified firmware, CT configuration and Modbus RTU settings; no writes and no claim that Edge data is a legal billing or settlement record.
- InteroperabilitySupported with conditions
- The exact model and a revisioned Modbus map are published, subject to correct serial settings, identity and firmware.13
- AccuracySupported with conditions
- Electrical and energy groups are documented, but CT setup, primary-versus-secondary tables and legal-use boundaries must be retained.23
- SecurityLimited
- Modbus RTU provides no peer authentication or encryption and the map contains writable groups. Physical, serial and client write controls are required.23
- ReliabilitySupported with conditions
- The map defines identity, error values and firmware-dependent energy availability; the site must retain revision and detect invalid or stale reads.3
- RuggednessSupported with conditions
- Temperature and IP20 enclosure limits are published. The meter still requires a suitable panel and correctly rated measurement circuit.1
- ScalabilitySupported with conditions
- Addressed RS-485 supports a multi-device segment, subject to one leader, unique addresses, physical-layer design and bounded polling.2
Setup
Read the L1-N voltage without an address shift
Revision 1.14 places L1-N voltage at decimal address 45056, hexadecimal 0xB000, in the function 03 instantaneous-measurement block. It is one unsigned 16-bit register scaled by 100.
- Function
- 03, Read Holding Registers
- PDU address
- 45056 decimal (0xB000)
- Length and type
- 1 register, unsigned 16-bit integer
- Unit and scale
- V/100
- Example
- Raw 23004 means 230.04 V
Acceptance: Send the table's literal address once. If a commissioning tool displays 40001-style references, verify its conversion to PDU offset 45056 instead of adding or subtracting one by habit. Compare the result with the meter display.
-
Confirm the exact meter
Record ECR300C from the front and verify the identity block over Modbus. Keep the serial number, software version, hardware version and the retained revision 1.14 map with the point configuration.
-
Record the measurement circuit
Document the 3P+N voltage wiring, CT primary and secondary values, CT polarity and phase assignment. Confirm whether collected values are the primary-side or separate secondary-side registers.
-
Commission the RS-485 segment
Match address, baud rate, parity and stop bits. Use suitable cable, isolation and reference conductors, with 120 ohm termination at the two physical ends. Avoid duplicate addresses and a second Modbus leader.
-
Start with read-only identity and voltage
Read the identity block and one phase voltage with function 03. Compare the decoded value with the simultaneous display before importing current, power or energy groups.
-
Reconcile energy without changing the meter
Keep import, export, tariff and partial totals separate. Compare interval deltas with the display and an upstream reference. Do not issue partial-reset, tariff or communications writes from the monitoring client.
Common questions
- Can Edge read the Hager ECR300C over Modbus?
- Yes, as a read-only protocol integration. Hager publishes Modbus RTU identity, instantaneous-measurement and energy tables for the ECR300C family. The exact meter identity, firmware, CT ratio and address settings still need commissioning.13
- Does reading a MID meter through Edge create a billing meter?
- No. Hager limits the MID statement to active energy and states that only the total active-energy register is for billing. An Edge copy, interval series or calculation is operational monitoring data unless a separate legal-metrology design establishes otherwise.2
- Are ECR300C current and power values already scaled to the CT primary?
- The main instantaneous table reports primary-side current and power for 3P_CT meters, and the map also contains separate secondary-side tables. Record which table is used and do not apply the CT ratio twice.3
Sources
- ECR300C product page (opens in a new tab)
- ECR300C user instructions 6LE005422Ad (opens in a new tab) (PDF)
- Modbus Tables Summary revision 1.14 (opens in a new tab) (PDF)
Further reading
Product names and trademarks belong to their owners. Publication does not imply endorsement or a commercial relationship.






