Trane Tracer UC600
Building automation controller
A UC600 retrofit may already have a direct Ethernet route. Trane documents BACnet/IP on firmware 5.0 and later as well as a serial MS/TP connection. Ask for the installed firmware, active network and application before including a new field router in the quote.
Compatibility
Compatible with Edge through routed BACnet MS/TP or BACnet/IP
UC600 supports BACnet MS/TP through a site router. Firmware 5.0 or later also supports a direct BACnet/IP connection.
Use the object list from the commissioned equipment and its installed application.
Connect it with
For a UC600 on the MS/TP network
- BACnet
- Edge
- Platforms
For firmware 5.0 or later configured for BACnet/IP
- BACnet
- Edge
- Platforms
Models
| Models | Interface | Route into Edge |
|---|---|---|
| Tracer UC600 | BACnet MS/TP through a site router or BACnet/IP on firmware 5.0 and later. | The BTL listing names UC600 at software 5.0. |
Interface
Documented measurements and integration boundaries for Tracer UC600.
- For a Horizon air handler, ask which discharge-air temperature point represents the actual sensor. Preserve the project’s point names and units if it uses a custom application.
Assessment
Tracer UC600 on the documented building network.
- InteroperabilityWell supported
- Trane documents UC600 communication over the selected building network.3
- AccuracyNot yet assessed
- The installed equipment and the measurement source determine the meaning of the feedback.2
- SecurityNot yet assessed
- Consult the site controls owner for the permitted network route.1
- ReliabilityNot yet assessed
- Site operation depends on the installed controller and network.1
- RuggednessNot yet assessed
- Confirm the rating of the installed equipment enclosure.2
- ScalabilitySupported with conditions
- Group units by controller, network and loaded application before mapping points.1
- LifecycleSupported with conditions
- Retain the installed application and equipment identifiers with the point list.2
Setup
-
Identify the equipment tag, controller application and commissioned Device instance.
-
Compare a mapped discharge-air temperature with the local service reading while the fan runs steadily.
Include the Device instance and actual connection in the handover.
-
Record the object type and instance, Present_Value, Units and the timestamp alongside the comparison.
Sources
- Tracer SC catalogue BAS-PRC031T-EN (opens in a new tab) (PDF)
- Horizon Tracer UC600 programming guide OAU-SVP002A-EN (opens in a new tab) (PDF)
- UC600 BTL listing, software 5.0 (opens in a new tab) (PDF)