Trane BCI-C

HVAC equipment interface

For a chilled-water plant survey, collect the chiller model, design sequence and local controller type. Trane describes this BCI-C as a UC400 running chiller interface software. Supply those details when asking whether an existing interface can serve a new monitoring project.

Trane BCI-C controller showing terminal rows and front service connector
  • BACnet MS/TP

HVAC equipment interface

Ask an engineer

Compatibility

Compatible with Edge through routed BACnet MS/TP

The BCI-C exposes equipment data over BACnet MS/TP. Edge reads it through a BACnet router on the site network.

Confirm the host, installed interface and sensor options using a dated point list from the unit.

Connect it with

For a CH530 chiller fitted with BCI-C

  • BACnet
  • Edge
  • Platforms
HVAC equipment interface
Interface
Gateway
Edge
Output
BCI-CCH530 chiller with BCI-C
BACnet routerRoutes the field segment to the building IP network.
ZGW-20 GatewayHosts Edge locally
EpiSensor EdgeBACnet/IP client + object map
Customer platformMQTT · API · files
BACnet MS/TP
BACnet/IP
Runs locally
Optional onward data
Record the Device instance and routed serial network number alongside the equipment tag. The customer-platform output is optional; Edge remains the local system of record.

Models

Download
ModelsInterfaceRoute into Edge
BCI-CBACnet MS/TP connection for the CH530 chiller.BTL listing 25120 names BCI-C at software 6.0. Use the version beside this model when preparing a tender submittal.

Interface

Documented measurements and integration boundaries for BCI-C.

  • Request the actual leaving-water temperature and active chilled-water setpoint as separate points. Their values can be close while the plant is running steadily.
  • Trane explains that the interface builds its points from the actual equipment configuration. Obtain a fresh object list after a change to that configuration.

Assessment

BCI-C on the CH530 chiller field network.

InteroperabilityWell supported
BTL identifies the MS/TP interface and software 6.0.3
AccuracyNot yet assessed
Available measurements depend on the installed sensors and equipment configuration.2
SecurityNot yet assessed
Network access is managed on site.3
ReliabilityNot yet assessed
The listing records protocol interoperability.3
RuggednessNot yet assessed
Match the module to the equipment and mounting location.1
ScalabilitySupported with conditions
Retain a point list per unit because similar models can have different options.2
LifecycleSupported with conditions
Review the equipment point list when the underlying unit configuration changes.2

Setup

  1. Match the unit nameplate to the interface model and the serial segment on the site drawing.

  2. Identify the leaving-water sensor in the CH530 display and the matching analog measurement in the installed BACnet object list.

    Compare the two at the same time and in the same temperature unit.

  3. Record the Device instance, object type and instance, Present_Value, Units and reference timestamp for handover.