Trane BCI-R
HVAC equipment interface
For a ReliaTel airside monitoring quote, request the unit model and installed sensors. Trane’s interface catalogue includes discharge air temperature, mixed air temperature and duct static pressure. The installed unit determines which points an operator can collect.
Compatibility
Compatible with Edge through routed BACnet MS/TP
The BCI-R exposes equipment data over BACnet MS/TP. Edge reads it through a BACnet router on the site network.
Confirm the host, installed interface and sensor options using a dated point list from the unit.
Connect it with
For a ReliaTel rooftop unit fitted with BCI-R
- BACnet
- Edge
- Platforms
Models
| Models | Interface | Route into Edge |
|---|---|---|
| BCI-R | BACnet MS/TP connection for the ReliaTel rooftop unit. Trane identifies field kit KIT15864 for Voyager, Odyssey and Precedent rooftop units. | BTL listing 25120 names BCI-R at software 6.0. Use the version beside this model when preparing a tender submittal. |
Interface
Documented measurements and integration boundaries for BCI-R.
- For a mixed-air check, identify the outdoor, return and mixed-air measurements that the unit exposes. A supply fan speed command expresses a requested speed; use a separate feedback point if the report needs actual operation.
- Trane explains that the interface builds its points from the actual equipment configuration. Obtain a fresh object list after a change to that configuration.
Assessment
BCI-R on the ReliaTel rooftop unit field network.
- InteroperabilityWell supported
- BTL identifies the MS/TP interface and software 6.0.3
- AccuracyNot yet assessed
- Available measurements depend on the installed sensors and equipment configuration.2
- SecurityNot yet assessed
- Network access is managed on site.3
- ReliabilityNot yet assessed
- The listing records protocol interoperability.3
- RuggednessNot yet assessed
- Match the module to the equipment and mounting location.1
- ScalabilitySupported with conditions
- Retain a point list per unit because similar models can have different options.2
- LifecycleSupported with conditions
- Review the equipment point list when the underlying unit configuration changes.2
Setup
-
Match the unit nameplate to the interface model and the serial segment on the site drawing.
-
Read the installed discharge-air temperature object.
Record its units and compare it with the same sensor on the service display during steady fan operation.
-
Record the Device instance, object type and instance, Present_Value, Units and reference timestamp for handover.
Sources
- ReliaTel interface product catalogue BAS-PRC060C-EN (opens in a new tab) (PDF)
- How the interface builds its equipment point list (opens in a new tab)
- BTL listing 25120, Trane equipment interfaces (opens in a new tab) (PDF)
- BCI-R installation guide RF-SVN03F-EN, KIT15864 (opens in a new tab)
Further reading
Product names and trademarks belong to their owners. Publication does not imply endorsement or a commercial relationship.