Distech Controls ECB-203
Building automation controller
For a small air handling unit, ask whether the duct pressure transducer is already wired to the ECB-203. Distech provides a 15 V DC supply for transducers such as a 4–20 mA pressure transmitter. Obtain the transmitter span and programmed input scaling before pricing a new measurement.
Compatibility
Compatible with Edge through routed BACnet MS/TP
The ECB-203 serves BACnet objects over MS/TP. Edge reaches the field network through a BACnet router.
Request the assigned Device instance, router network number and the commissioned object list for this controller.
Connect it with
For a controller on the building MS/TP field network
- BACnet
- Edge
- Platforms
Models
| Models | Interface | Route into Edge |
|---|---|---|
| ECB-203 | 6 universal inputs, 5 TRIAC outputs and 3 universal outputs. | BTL listing 31024 names this model at application version 2.17.20287.2 on MS/TP. |
Interface
Documented measurements and integration boundaries for ECB-203.
- Identify the source sensor and programmed engineering range behind each input. A spare physical input can provide a new measurement only when a suitable sensor is connected and configured.
- Request the object type, instance, unit and update interval for each measurement in the project.
Assessment
ECB-203 on a routed BACnet field network.
- InteroperabilityWell supported
- The BTL listing identifies the controller model and tested MS/TP implementation.2
- AccuracyNot yet assessed
- Match the measurement source to the application and compare the exported engineering units.1
- SecurityNot yet assessed
- Access to the building network depends on the site configuration.2
- ReliabilityNot yet assessed
- The listing covers tested protocol behaviour.2
- RuggednessNot yet assessed
- Identify the enclosure and location before specifying replacement equipment.1
- ScalabilitySupported with conditions
- Count the required inputs and outputs against the published hardware configuration.1
- LifecycleSupported with conditions
- Record the installed application version with the model and its point schedule.2
Setup
-
Identify the terminal or plant tag and the MS/TP segment that serves it.
-
For an installed duct pressure transmitter, read its mapped analog object.
Compare the value and units with a reference at the same pressure taps under steady fan duty.
-
Read Present_Value and Units from the selected analog object and retain the reference reading, equipment tag and timestamp together.
Sources
- ECB-203 equipment and application specifications (opens in a new tab)
- BTL listing 31024, ECB ASC Series (opens in a new tab) (PDF)
Further reading