Trane Tracer UC210
Building automation controller
For a floor of variable-air-volume boxes, request the box tag, inlet size and most recent balancing record for each terminal. The UC210 air-volume reading becomes much easier to check when the controls contractor can match it to the measured flow for that box.
Compatibility
Compatible with Edge through routed BACnet MS/TP
UC210 supports BACnet MS/TP through a site router.
Use the object list from the commissioned equipment and its installed application.
Connect it with
For a UC210 on the MS/TP network
- BACnet
- Edge
- Platforms
Models
| Models | Interface | Route into Edge |
|---|---|---|
| Tracer UC210 | BACnet MS/TP through a site router. | The BTL listing names UC210 at software 2.0. |
Interface
Documented measurements and integration boundaries for Tracer UC210.
- Ask for the actual terminal airflow and its unit. Keep minimum ventilation flow and maximum flow settings as separate quantities.
Assessment
Tracer UC210 on the documented building network.
- InteroperabilityWell supported
- Trane documents UC210 communication over the selected building network.3
- AccuracyNot yet assessed
- The installed equipment and the measurement source determine the meaning of the feedback.2
- SecurityNot yet assessed
- Consult the site controls owner for the permitted network route.1
- ReliabilityNot yet assessed
- Site operation depends on the installed controller and network.1
- RuggednessNot yet assessed
- Confirm the rating of the installed equipment enclosure.2
- ScalabilitySupported with conditions
- Group units by controller, network and loaded application before mapping points.1
- LifecycleSupported with conditions
- Retain the installed application and equipment identifiers with the point list.2
Setup
-
Identify the equipment tag, controller application and commissioned Device instance.
-
Compare actual airflow with a simultaneous balancing measurement or compare a saved trend against a time-matched balancing record.
Check whether the instrument reports L/s or cfm.
-
Record the object type and instance, Present_Value, Units and the timestamp alongside the comparison.
Sources
- Tracer SC catalogue BAS-PRC031T-EN (opens in a new tab) (PDF)
- VAV terminal installation and balancing guide VAV-SVN09E-EN (opens in a new tab) (PDF)
- UC210 BTL listing, software 2.0 (opens in a new tab) (PDF)