Contemporary Controls BASRT-B BASrouter

BACnet router

Specify the BASRT-B for ongoing readings from serial BACnet instruments when the switchboard has 35 mm DIN rail, a 24 V AC or DC supply and Ethernet to the collector. First check whether the controls installation already has a router serving that trunk. An existing reachable route can avoid adding panel hardware.

Contemporary Controls BASRT-B DIN-rail BACnet router with field terminals and status indicators
  • BACnet/IP
  • BACnet MS/TP

BACnet router

Ask an engineer

Compatibility

Compatible with Edge through routed BACnet/IP

Edge uses BACnet/IP on Ethernet. The BASRT-B routes the request to the instrument on its MS/TP network.

Match the network number and serial rate to the controls schedule, then compare a known meter object with the operator display.

Connect it with

For a permanent monitoring connection

  • Wired
  • Edge
  • Platforms
BACnet router
Interface
Gateway
Edge
Output
BASRT-B BASrouterField meter on MS/TP
Protected EthernetSegmented LAN
ZGW-20 GatewayHosts Edge locally
EpiSensor EdgeProtocol client + point model
Customer platformMQTT · API · files
Ethernet
Protected Ethernet
Runs locally
Optional onward data
The panel router stays powered independently of a service laptop. Record the meter device instance and its serial network number in the point schedule. The customer-platform output is optional; Edge remains the local system of record.

Models

Download
ModelsInterfaceRoute into Edge
BASRT-BEthernet and EIA-485 for BACnet MS/TPConnect an existing BACnet MS/TP meter trunk to the Gateway through a panel-mounted Ethernet router with a 24 V supply. For a tender requiring independent BACnet testing, match the installed software to BTL listing 30266. It covers the BASRT-B at 3.0.3, tested in January 2018.

Interface

Documented measurements and integration boundaries for BASRT-B BASrouter.

  • Use a measurement from the field meter’s own object list. The router transports that reading; the instrument determines its units and accuracy.

Assessment

BACnet routing between Ethernet and an existing serial meter trunk.

InteroperabilityWell supported
Routes BACnet/IP requests to BACnet MS/TP devices.13
AccuracyNot applicable
The field instrument determines measurement accuracy.1
SecurityNot yet assessed
Site access controls require project-specific review.
ReliabilitySupported with conditions
Check panel power capacity against 2 W at 24 V DC or 4 VA at 24 V AC.1
RuggednessSupported with conditions
IP30 enclosure rated for operation from −40 to 75 °C.1
ScalabilitySupported with conditions
Size the trunk for the installed serial rate and polling interval. The supported rates range from 9.6 to 76.8 kbit/s.1
LifecycleSupported with conditions
The order code and datasheet revision identify the router for the commissioning record.1

Setup

  1. Obtain the approved network numbers, serial rate and a known field device instance from the operator.

  2. Read Present_Value and Units on a documented field object from the Ethernet side.

    Compare both with the operator display for the same circuit.

  3. Include the panel location, 24 V supply and field point schedule in the handover.