Distech Controls ECB-VAVS
Building automation controller
The ECB-VAVS serves cooling-only and cooling-with-reheat terminal boxes. For a comfort investigation, request airflow feedback and room temperature separately. A reheat output signal can show demand while leaving the actual discharge temperature unknown.
Compatibility
Compatible with Edge through routed BACnet MS/TP
The ECB-VAVS serves BACnet objects over MS/TP. Edge reaches the field network through a BACnet router.
Request the assigned Device instance, router network number and the commissioned object list for this controller.
Connect it with
For a controller on the building MS/TP field network
- BACnet
- Edge
- Platforms
Models
| Models | Interface | Route into Edge |
|---|---|---|
| ECB-VAVS | 3 universal inputs, 3 TRIAC outputs and 1 universal output. | BTL listing 31024 names this model at application version 2.17.20287.2 on MS/TP. |
Interface
Documented measurements and integration boundaries for ECB-VAVS.
- The onboard flow sensor measures the terminal airflow and the actuator positions the damper. A damper position expressed as a percentage cannot replace an airflow reading.
- Request the object type, instance, unit and update interval for each measurement in the project.
Assessment
ECB-VAVS on a routed BACnet field network.
- InteroperabilityWell supported
- The BTL listing identifies the controller model and tested MS/TP implementation.2
- AccuracyNot yet assessed
- Match the measurement source to the application and compare the exported engineering units.1
- SecurityNot yet assessed
- Access to the building network depends on the site configuration.2
- ReliabilityNot yet assessed
- The listing covers tested protocol behaviour.2
- RuggednessNot yet assessed
- Identify the enclosure and location before specifying replacement equipment.1
- ScalabilitySupported with conditions
- Count the required inputs and outputs against the published hardware configuration.1
- LifecycleSupported with conditions
- Record the installed application version with the model and its point schedule.2
Setup
-
Identify the terminal or plant tag and the MS/TP segment that serves it.
-
For a reheat box, check the airflow reading against a local airflow measurement.
If discharge temperature is required, locate the physical sensor and its separate object before including that trend.
-
Read Present_Value and Units from the selected analog object and retain the reference reading, equipment tag and timestamp together.
Sources
- ECB-VAVS equipment and application specifications (opens in a new tab)
- BTL listing 31024, ECB ASC Series (opens in a new tab) (PDF)
Further reading