Distech Controls ECB-VAV

Building automation controller

The ECB-VAV serves dual-duct and fan-powered boxes as well as cooling and reheat applications. Record the terminal type and the drawing reference before quoting a floor of boxes. Its integrated airflow sensor and damper actuator give the controls contractor distinct signals to identify.

Distech ECB-VAV controller with integrated damper actuator
  • BACnet MS/TP

Building automation controller

Ask an engineer

Compatibility

Compatible with Edge through routed BACnet MS/TP

The ECB-VAV serves BACnet objects over MS/TP. Edge reaches the field network through a BACnet router.

Request the assigned Device instance, router network number and the commissioned object list for this controller.

Connect it with

For a controller on the building MS/TP field network

  • BACnet
  • Edge
  • Platforms
Building automation controller
Interface
Gateway
Edge
Output
ECB-VAVECB-VAV
BACnet routerRoutes the field segment to the building IP network.
ZGW-20 GatewayHosts Edge locally
EpiSensor EdgeBACnet/IP client + object map
Customer platformMQTT · API · files
BACnet MS/TP
BACnet/IP
Runs locally
Optional onward data
Record the network number for the serial segment and the object identifier assigned to the required feedback. The customer-platform output is optional; Edge remains the local system of record.

Models

Download
ModelsInterfaceRoute into Edge
ECB-VAV4 universal inputs, 4 TRIAC outputs and 2 universal outputs.BTL listing 31024 names this model at application version 2.17.20287.2 on MS/TP.

Interface

Documented measurements and integration boundaries for ECB-VAV.

  • The onboard flow sensor measures the terminal airflow and the actuator positions the damper. A damper position expressed as a percentage cannot replace an airflow reading.
  • Request the object type, instance, unit and update interval for each measurement in the project.

Assessment

ECB-VAV on a routed BACnet field network.

InteroperabilityWell supported
The BTL listing identifies the controller model and tested MS/TP implementation.2
AccuracyNot yet assessed
Match the measurement source to the application and compare the exported engineering units.1
SecurityNot yet assessed
Access to the building network depends on the site configuration.2
ReliabilityNot yet assessed
The listing covers tested protocol behaviour.2
RuggednessNot yet assessed
Identify the enclosure and location before specifying replacement equipment.1
ScalabilitySupported with conditions
Count the required inputs and outputs against the published hardware configuration.1
LifecycleSupported with conditions
Record the installed application version with the model and its point schedule.2

Setup

  1. Identify the terminal or plant tag and the MS/TP segment that serves it.

  2. For a fan-powered box, identify the airflow feedback in the commissioned point list.

    Compare it with the balancing instrument at the same operating condition and record which air stream the reading covers.

  3. Read Present_Value and Units from the selected analog object and retain the reference reading, equipment tag and timestamp together.