Johnson Controls CGM04060 / CGE04060

Building automation controller

For a small plant panel, check the input schedule before specifying another controller. This size provides three universal inputs and one binary input. A pressure transducer and a dry contact need different input configurations. Ask which channels are already in use and which measured values are shared over BACnet.

CGM04060 at front left and CGE04060 at front right in the Metasys controller family
  • BACnet MS/TP
  • BACnet/IP

Building automation controller

Ask an engineer

Compatibility

Compatible with Edge over routed MS/TP or BACnet/IP

CGM uses a BACnet MS/TP field bus in this configuration. CGE can expose points directly to Edge on BACnet/IP.

Record the installed order code, commissioned protocol and Device instance. Confirm the controller’s network mode before selecting the Ethernet route.

Connect it with

Route into Edge

For a CGM commissioned on BACnet MS/TP

  • BACnet
  • Edge
  • Platforms
Building automation controller
Interface
Gateway
Edge
Output
CGM04060 / CGE04060CGM04060
BACnet routerRoutes the field segment to the building IP network.
ZGW-20 GatewayHosts Edge locally
EpiSensor EdgeBACnet/IP client + object map
Customer platformMQTT · API · files
BACnet MS/TP
BACnet/IP
Runs locally
Optional onward data
Record the field network number and router serving this controller. The customer-platform output is optional; Edge remains the local system of record.

For a CGE commissioned on BACnet/IP

  • BACnet
  • Edge
  • Platforms
Building automation controller
Interface
Gateway
Edge
Output
CGM04060 / CGE04060CGE04060
Protected EthernetSegmented LAN
ZGW-20 GatewayHosts Edge locally
EpiSensor EdgeBACnet/IP client + object map
Customer platformMQTT · API · files
BACnet/IP
Protected Ethernet
Runs locally
Optional onward data
Request the active BACnet/IP settings. The manufacturer also documents BACnet/SC, which is a different network configuration. The customer-platform output is optional; Edge remains the local system of record.

Models

Download
ModelsInterfaceRoute into Edge
M4-CGM04060-0BACnet MS/TP via a site router.BTL listing 31507 names M4-CGM04060-0 at 12.0.1.34.
M4-CGE04060-0BACnet/IP over Ethernet. Confirm that the site uses BACnet/IP for this route.BTL listing 31511 names M4-CGE04060-0 at 12.0.1.34.

Interface

Documented measurements and integration boundaries for CGM04060 / CGE04060.

  • The universal inputs accept a 4–20 mA signal. To trend a pressure transducer, obtain the transmitter span and the range programmed into the application.

Assessment

Metasys CG 04060 series on the installed network.

InteroperabilityWell supported
Separate listings identify the serial and Ethernet model variants.23
AccuracyNot yet assessed
The point table describes the available hardware. The installed application determines the BACnet measurement.1
SecurityNot yet assessed
Network mode and access controls are site-specific.1
ReliabilityNot yet assessed
The listings cover protocol operation.23
RuggednessNot yet assessed
Identify the installed enclosure and terminal or panel location.1
ScalabilitySupported with conditions
Match the I/O schedule to the hardware model before adding equipment.1
LifecycleSupported with conditions
Record model suffix, application version and commissioned connection with the point list.1

Setup

  1. Trace the required measurement from the panel or terminal to its project-assigned BACnet object.

  2. Read Present_Value and Units on the analog object for that input.

    Compare the pressure with the local reference at the same taps during steady operation.

  3. Record the Device instance, object identifier, timestamp, Present_Value and applicable units in the handover.