Belimo 22ADP
Differential air pressure sensor
Select the 22ADP pressure range for the expected filter drop. The pressure ports, tube routing and unit setting determine whether the trend represents a clean filter, a loaded filter or reversed connections.
Compatibility
Compatible with Edge through a BACnet router
Edge reads the sensor through a BACnet/IP-to-MS/TP router on the building network.
Belimo’s interface description covers firmware 2.3. Match the suffix and object to the installed sensor before adding the trend.
Connect it with
For an installed MS/TP segment
- BACnet
- Edge
- Platforms
Models
| Models | Interface | Route into Edge |
|---|---|---|
| 22ADP-164, 22ADP-164L, 22ADP-56Q, 22ADP-56QB, 22ADP-564L and 22ADP-566L | The 22ADP-164 and 22ADP-164L cover selectable ranges within −100 to 2,500 Pa. The L version has an LCD. The 22ADP-56Q covers a different range, −150 to 250 Pa. Match the exact suffix to the expected filter drop. | Record the sensor Device instance, router and serial network number in the point list. |
Interface
Documented measurements and integration boundaries for 22ADP.
- AI 8 carries the first differential pressure channel. Use the unit reported for the configured system, typically Pa or inches of water column. A calculated flow requires a separate flow relationship.
Assessment
Read-only collection over the installed sensor network.
- InteroperabilityWell supported
- The PICS names the ordering variants and documents ReadProperty and ReadPropertyMultiple on MS/TP.1
- AccuracySupported with conditions
- Using an unnecessarily wide range reduces the practical value of a small filter-drop reading. Check the selected span and the accuracy specified for that span.2
- SecurityNot yet assessed
- Ask the site controls owner which clients may reach the trunk.1
- ReliabilityNot yet assessed
- Record the most recent successful reading when supervising the sensor.1
- RuggednessSupported with conditions
- Belimo rates the 22ADP-164 series enclosure IP65 / NEMA 4X. Protect the tubing and pressure taps as well as the enclosure.2
- ScalabilitySupported with conditions
- Belimo specifies up to 32 nodes without a repeater. Include existing devices when checking capacity on a shared segment.1
- LifecycleSupported with conditions
- Record the model suffix and application software version with the point list. Field models share an object table with different available measurements.1
Setup
-
Match the sensor label and its physical location to the building point schedule.
Record the Device instance as well as the object instance.
-
At steady fan duty, compare Analog Input 8 with a differential manometer connected across the same pressure taps.
Record the high and low sides, sign, unit and fan condition before accepting the reading.
-
Check Out_Of_Service for the selected object.
The shared interface table includes measurements available only on other sensor types.
Sources
- Sensor BACnet object list and PICS, application software 2.3 (opens in a new tab) (PDF)
- 22ADP-164 and 22ADP-164L pressure ranges (opens in a new tab) (PDF)
- 22ADP-56Q differential pressure datasheet (opens in a new tab) (PDF)
Further reading
Product names and trademarks belong to their owners. Publication does not imply endorsement or a commercial relationship.






