ONICON F-4300
Water flow meter
The F-4300 measures flow from transducers mounted on the outside of a full pipe. It uses the difference in ultrasonic transit time to measure liquid velocity and direction. For a retrofit, identify the liquid, pipe size, material and wall thickness before selecting the transducers. Photograph the intended mounting area so the supplier can assess access and advise on the mounting arrangement.
Compatibility
Compatible with Edge through a BACnet MS/TP router
The meter’s RS-485 interface serves flow and diagnostic objects over BACnet MS/TP. Edge accesses the serial segment through the building BACnet/IP router.
Confirm BACnet is selected on the fitted serial card. Record the meter Device instance, configured flow unit and router serving the plant room.
Connect it with
For the RS-485 card configured for BACnet MS/TP
- BACnet
- Edge
- Platforms
Models
| Models | Interface | Route into Edge |
|---|---|---|
| F-4300 with clamp-on transducers and RS-485 | Transducer selection depends on the pipe dimensions and material. The meter’s configurable serial interface supports BACnet MS/TP or Modbus RTU. | For an existing installation, identify the transmitter, transducer series and active serial protocol. For a new quote, include pipe wall thickness and the liquid service. |
Interface
Documented measurements and integration boundaries for F-4300.
- Analog Input 2 reports volume flow rate. Analog Input 1 reports flow velocity. Leave each in its own unit when preparing the point schedule.
- Analog Input 3 reports the speed of sound through the liquid. Analog Input 4 reports transducer signal strength. Compare signal strength with the local reading when investigating an unexpected flow trend.
Assessment
F-4300 ultrasonic flow transmitter with clamp-on transducers and serial BACnet.
- InteroperabilityWell supported
- The manual documents BACnet MS/TP, the flow-rate object and engineering-unit property.1
- AccuracySupported with conditions
- The ordering guide specifies full pipes carrying relatively clean liquids. Pipe material, size and wall thickness determine transducer selection.2
- SecurityNot yet assessed
- Confirm which collector may read the meter with the controls operator.1
- ReliabilitySupported with conditions
- The transmitter exposes signal strength and liquid sound velocity so a site engineer can compare diagnostic values with the flow trend.1
- RuggednessSupported with conditions
- The ordering guide distinguishes transducer connectors for wet and outdoor locations. Record the actual connector and exposure.2
- ScalabilitySupported with conditions
- The serial interface supports 9600, 19200, 38400 and 76800 bit/s. Inventory the other devices using the same trunk before specifying a polling interval.1
- LifecycleSupported with conditions
- Retain the pipe dimensions and transducer series so a replacement can be selected for the same acoustic path.2
Setup
-
Record the measured circuit, transducer locations, pipe data and expected direction of flow.
Obtain one display reading during normal circulation.
-
Using section 5.1, Table 2a of DOC-0003010, read Present_Value and Units on Analog Input 2.
Compare the unit, sign and magnitude with the displayed flow on the same meter.
-
Record Analog Input 4 at the same time.
If flow is implausible, the signal reading and transducer installation record give the site engineer a starting point for a physical check.