ONICON F-4600 with LCD

Water flow meter

The F-4600 measures flow in the pipe. Its model code identifies the meter size, connection and display option. Record the code before quoting a replacement: the catalog lists the 2½-inch model with an ANSI Class 150 flange, while the smaller sizes use NPT threads. For an existing LCD meter, check the selected serial protocol and the router serving the trunk.

ONICON F-4600 inline flow meter with LCD, front buttons and pipe connections
  • BACnet MS/TP

Water flow meter

Ask an engineer

Compatibility

Compatible with Edge via a BACnet MS/TP router

The LCD interface provides the RS-485 network connection on TB4. When the meter uses BACnet MS/TP, Edge reads the volume flow object through a site BACnet/IP router.

Match the installed display and interface to DOC-0003880. Record the displayed flow unit and the serial network number before configuring the collection point.

Connect it with

For an F-4600 LCD interface configured for BACnet MS/TP

  • BACnet
  • Edge
  • Platforms
Water flow meter
Interface
Gateway
Edge
Output
F-4600 with LCDMeter LCD interface, TB4
BACnet routerRoutes from the collector network to the meter trunk.
ZGW-20 GatewayHosts Edge locally
EpiSensor EdgeBACnet/IP client + object map
Customer platformMQTT · API · files
BACnet MS/TP
BACnet/IP
Runs locally
Optional onward data
The LCD interface carries the BACnet connection for this model. Obtain the meter Device instance and the IP route from the controls operator. The customer-platform output is optional; Edge remains the local system of record.

Models

Download
ModelsInterfaceRoute into Edge
F-4600-AAA-BCD-EF with C = 1Detachable LCD interface, RS-485 (E = 1), pulse input, pulse output and analog output (F = 6).Confirm the display and communications fields on the order code. Compare the fitted protocol with the building point schedule.

Interface

Documented measurements and integration boundaries for F-4600 with LCD.

  • Analog Input 2 reports volume flow. Read Units to distinguish gallons per minute from litres per second or cubic metres per hour.
  • Analog Input 6 reports ultrasonic signal strength. Analog Input 7 reports signal quality on a scale from 3 to 31, with 3 the best value. These are diagnostic readings.

Assessment

Inline F-4600 with LCD on a routed serial BACnet connection.

InteroperabilityWell supported
The manual identifies the serial network port and documents the volume-flow and diagnostic objects.1
AccuracySupported with conditions
The straight-run table specifies 10 upstream pipe diameters after a control valve for ½ to 1 inch meters and 15 for 1¼ to 2½ inch meters, using the manufacturer’s couplings.1
SecurityNot yet assessed
Confirm read access with the operator of the building network.1
ReliabilitySupported with conditions
The meter exposes separate signal quality and signal strength objects for checking an unexpected flow trend.1
RuggednessSupported with conditions
The catalog specifies an IP65 enclosure for the detachable LCD option. Verify the location when specifying a replacement.2
ScalabilitySupported with conditions
Group meters by serial trunk and provide the Device instance of each LCD interface.1
LifecycleSupported with conditions
The ¾-inch and 1-inch sizes have standard and high-flow order codes. Retain the entire size field for replacement.2

Setup

  1. Identify the pipe size, process connection, flow direction and nearest upstream obstruction.

    Record the distance to the meter in pipe diameters.

  2. Read Present_Value and Units for Analog Input 2 using manual section 6.4.

    Compare the reading with the local flow display at the same time.

  3. If the rate is unexpected, record signal strength and quality alongside the reading.

    Check the straight-run requirement for that size and obstruction before interpreting the result.