ONICON System-20

Thermal energy meter

The System-20 is a heat calculator that can be ordered with an inline, insertion or clamp-on ONICON flow meter. Temperature inputs can use precision current-based sensors or a matched pair of platinum RTDs. For a central plant survey, record the flow meter model and the temperature sensor type along with the calculator serial number. These details determine which equipment a replacement quote must cover.

ONICON System-20. Front view of the System-20 display and four buttons.
  • BACnet MS/TP

Thermal energy meter

Ask an engineer

Compatibility

Compatible with Edge through a BACnet router

On a System-20 configured for BACnet MS/TP, Edge reaches the calculator through the site BACnet/IP router. The calculator provides the thermal total and its unit.

Check the installed serial protocol and whether the meter is set up for one or two energy modes. Choose the corresponding total before comparing it with the display.

Connect it with

For an RS-485 connection configured for BACnet MS/TP

  • BACnet
  • Edge
  • Platforms
Thermal energy meter
Interface
Gateway
Edge
Output
System-20System-20 BTU calculator
BACnet routerRoutes the IP collector to the serial meter network.
ZGW-20 GatewayHosts Edge locally
EpiSensor EdgeBACnet/IP client + object map
Customer platformMQTT · API · files
BACnet MS/TP
BACnet/IP
Runs locally
Optional onward data
Give the controls operator the calculator identity and request the MS/TP network number, Device instance and energy mode. Individual sensors feed the calculator and do not need separate BACnet addresses. The customer-platform output is optional; Edge remains the local system of record.

Models

Download
ModelsInterfaceRoute into Edge
System-20 with an external flow meterRS-485 plus configurable analog and pulse signals. The product can be paired with insertion, inline or clamp-on flow measurement.Specify the commissioned BACnet route for the calculator. Record the fitted flow sensor when the project also requires sensor replacement or verification.

Interface

Documented measurements and integration boundaries for System-20.

  • Analog Value 1 is the single-mode energy total. For a dual-mode installation, Analog Values 2 and 3 hold the totals for modes 1 and 2. Ask which mode the site uses for heating and which for cooling.
  • Analog Input 1 is the instantaneous energy rate. Analog Input 2 reports volume flow. The separate year-to-date energy totals begin at Analog Value 4.

Assessment

Thermal totals and measurements from a System-20 using BACnet MS/TP.

InteroperabilityWell supported
The manufacturer lists the total and rate objects separately and publishes their BACnet properties.1
AccuracySupported with conditions
Select the flow meter style and temperature sensor pair for the circuit. Record the configuration used to calculate energy.2
SecurityNot yet assessed
Review collector access with the building operator.1
ReliabilitySupported with conditions
The local display provides energy and flow values for checking readings after a collection interruption.2
RuggednessNot yet assessed
Survey the calculator location separately from the pipe-mounted sensors.2
ScalabilitySupported with conditions
One calculator can expose two energy-mode totals. Size reporting and reconciliation for each mode used by the site.1
LifecycleSupported with conditions
Capture the separate flow meter and temperature sensor identities when preparing the replacement schedule.2

Setup

  1. Confirm the energy mode and display unit with the site operator.

    Record the meter identity and time of the first comparison.

  2. For single-mode operation read Present_Value and Units from Analog Value 1 using section 6.5 of DOC-0003557.

    Compare with the cumulative energy total on the display.

  3. Repeat after an interval with known flow.

    For a dual-mode meter record both totals separately, and check the change in the mode that was active during the interval.