Andivi ANB-THPVCP

Indoor air quality sensor

For a meeting-room ventilation survey, specify CO₂ in ppm and whether the operator also needs a presence indication. The ANB-THPVCP adds presence detection to temperature, relative humidity, pressure, CO₂ and VOC sensing. Its dew point, enthalpy and moist-air density are calculated quantities. Include the room location and requested readings in the quote.

White Andivi Alledio room sensor with side ventilation openings
  • BACnet MS/TP
  • BACnet/IP
  • Modbus RTU

Indoor air quality sensor

Ask an engineer

Compatibility

Compatible with Edge through routed MS/TP or BACnet/IP over Wi-Fi

The ANB sensor supports BACnet MS/TP on RS-485 and BACnet/IP via the building wireless network. Edge reads the sensor using BACnet/IP on either route.

Confirm the ANB-THPVCP suffix and selected protocol. The ANM variants use Modbus. The object examples follow Andivi manual revision 3.1.

Connect it with

Route into Edge

For an ANB sensor configured for BACnet MS/TP

  • BACnet
  • Edge
  • Platforms
Indoor air quality sensor
Interface
Gateway
Edge
Output
ANB-THPVCPAlledio room sensor
BACnet routerRoutes the room sensor’s serial segment to the building IP network.
ZGW-20 GatewayHosts Edge locally
EpiSensor EdgeBACnet/IP client + object map
Customer platformMQTT · API · files
BACnet MS/TP
BACnet/IP
Runs locally
Optional onward data
Record the controls network number, router and Device instance for each room. The customer-platform output is optional; Edge remains the local system of record.

For an ANB sensor configured for BACnet/IP

  • Wired
  • Edge
  • Platforms
Indoor air quality sensor
Interface
Gateway
Edge
Output
ANB-THPVCPAlledio room sensor
Protected EthernetSegmented LAN
ZGW-20 GatewayHosts Edge locally
EpiSensor EdgeProtocol client + point model
Customer platformMQTT · API · files
Ethernet
Protected Ethernet
Runs locally
Optional onward data
Confirm wireless coverage at the mounting position and the approved route from Edge to the sensor. Include a local supply in the room survey. The customer-platform output is optional; Edge remains the local system of record.

Models

Download
ModelsInterfaceRoute into Edge
ANB-THPVCPRS-485 or BACnet/IP over Wi-Fi. The model has a presence sensor as well as air measurements.Include the presence point if the operator wants to distinguish a vacant room from an occupied one.
ANB-THPVCRelated variant with CO₂ and VOC measurements, without the presence option.Confirm the trailing P on an existing sensor before quoting a presence channel.

Interface

Documented measurements and integration boundaries for ANB-THPVCP.

  • Analog Input 4 reports CO₂ in ppm. Analog Input 3 is a VOC index. Keep separate units and fields for these two trends.
  • Binary Input 0 reports presence as a yes/no state. A room occupancy count requires a different measurement.

Assessment

ANB-THPVCP indoor sensor with the commissioned BACnet connection.

InteroperabilityWell supported
The manual lists both BACnet routes and publishes the CO₂ and presence objects.1
AccuracySupported with conditions
The exact suffix determines the measured variables and presence capability.2
SecurityNot yet assessed
The site network owner determines access to the sensor.1
ReliabilitySupported with conditions
The service-status property helps identify measurements unavailable on a fitted sensor variant.1
RuggednessSupported with conditions
Select a representative indoor wall location away from direct airflow.1
ScalabilitySupported with conditions
Document each sensor’s Device instance and, on a serial network, its local MAC address.1
LifecycleSupported with conditions
Keep the full model suffix and manual revision with the room point schedule.2

Setup

  1. Record the Device instance, room name and location.

    Andivi specifies a wall position around 1.5 m above the floor away from direct airflow.

  2. Using pages 9 and 10 of revision 3.1, read Present_Value and Units on Analog Input 4.

    Check Out_Of_Service and compare the ppm value with a reference CO₂ instrument in the same room after both readings settle.

  3. Where presence is in scope, observe Binary Input 0 during an agreed occupancy change.

    Record the time of the change independently of the CO₂ trend.