Vaisala GMW95 series
Indoor air quality sensor
The GMW95 and GMW95D measure room CO₂ and temperature. The GMW95R and GMW95RD add relative humidity. D denotes a visible display. For existing rooms, inventory the suffix and installed software before grouping instruments into a single monitoring quote.
Compatibility
Compatible with Edge through BACnet MS/TP or Modbus RTU
Vaisala guide M211659EN-C documents BACnet MS/TP on digital GMW95 variants. Datasheet B211296EN-F specifies Modbus RTU for the same four order codes. Edge can collect over the protocol fitted to the unit.
For a replacement, request the protocol in writing with the order. For an installed unit, match its software and interface to the applicable guide before using the BACnet example.
Connect it with
For an instrument operating on a BACnet MS/TP trunk
- BACnet
- Edge
- Platforms
For a digital unit specified for Modbus RTU
- Modbus
- Edge
- Platforms
Models
| Models | Interface | Route into Edge |
|---|---|---|
| GMW95 and GMW95D | CO₂ and temperature. The D version adds a display. | For a room without a visible display, include a reference CO₂ instrument in the handover plan. |
| GMW95R and GMW95RD | CO₂, temperature and humidity. The RD version includes a display. | For tenders, BTL listing 30086 specifically names GMW95R at software 1.1.0.0. |
Interface
Documented measurements and integration boundaries for GMW95 series.
- On the BACnet implementation in M211659EN-C, Analog Input 1 reports CO₂ in ppm and Analog Input 3 reports temperature.
- Analog Input 2 reports relative humidity on humidity-equipped models. A room with a GMW95D provides a display but has no humidity measurement.
Assessment
GMW95 series with the documented serial interface.
- InteroperabilityWell supported
- The manufacturer publishes read-only measurement objects and units for the documented BACnet implementation.1
- AccuracySupported with conditions
- Only the R and RD versions include relative humidity.1
- SecurityNot yet assessed
- The controls owner determines access to the building network.1
- ReliabilitySupported with conditions
- Compare against a local reference during steady operating conditions.1
- RuggednessSupported with conditions
- The datasheet specifies an IP30 housing for room installation.2
- ScalabilitySupported with conditions
- Record serial settings and Device instance for each sensor on the trunk.1
- LifecycleSupported with conditions
- Match the protocol on replacement stock to the installed network and application.2
Setup
-
Identify the suffix, software and commissioned serial protocol.
Appendix A of M211659EN-C documents the BACnet implementation for this example.
-
Read Present_Value and Units on Analog Input 1 and compare ppm with the visible CO₂ display or a reference instrument sampling the same room air.
Allow the reference to settle.
-
For an R or RD unit, check relative humidity at AI 2 separately before adding the room to a humidity report.
Sources
- GMW90 user guide M211659EN-C, Appendix A (opens in a new tab)
- GMW90 series datasheet B211296EN-F (opens in a new tab)
- BTL listing 30086, XMW90 software 1.1.0.0 (opens in a new tab) (PDF)