Meter interfaces

Connecting ONICON flow and heat meters to BACnet

Identify the ONICON meter, network board and reporting units needed to quote flow or thermal energy monitoring on existing water, steam or gas lines.

Start with the quantity the customer wants to report. A facilities team investigating low chilled-water flow may need a rate in litres per second. A tenant allocation report needs the change in accumulated thermal energy over a billing period. A trend in instantaneous thermal power serves a third purpose. Agree the quantity, unit and reporting interval before counting points or specifying a router.

Identify the equipment on the branch

Equipment on siteWhat to record for the quote
System-10 calculatorPhotograph the full order code. Communications code 3 identifies the Ethernet BACnet board. Code 1 identifies serial MS/TP, so record the router serving that trunk.
System-20 calculator with separate flow meterIdentify the flow meter as well as the calculator. Ask whether heating and cooling use separate totals and which mode the site assigns to each.
System-40 inline thermal meterRecord the pipe size, operating flow range and temperature sensor pair. On a BACnet installation, identify the meter’s serial network and router.
F-1500 insertion turbine meterRecord the process fluid, whether the report needs mass or volume, and which compensation sensors are installed. A steam mass rate and a liquid volume rate require different units.
F-2600 inline vortex meterRecord the meter body size, wafer or flanged connection, and flange rating.
F-2700 insertion vortex meterRecord the pipe inside diameter, probe mounting connection and retractor arrangement.
F-4300 clamp-on flow meterIdentify the liquid and pipe dimensions, including wall thickness. The transducers mount outside the pipe. Request the transmitter’s serial protocol and a signal-strength reading alongside flow.
F-4600 with LCDRecord pipe size, flow range and the position of the nearest upstream valve. Check the LCD board and serial protocol for a network retrofit.
F-5500 gas flow meterRecord the calibration gas, flow unit and reference conditions for standard volume. Identify whether the transmitter has serial communications or scaled pulse output.
D-100 flow displayRecord the flow meter feeding the display, its signal and scaling, and the fitted network board. Confirm whether the report requires a rate, a total or separate totals for each flow direction.

Verify the requested quantity

On a single-mode System-20, read the present value and unit of Analog Value 1. Record the displayed cumulative energy at the same time. Repeat both readings after an interval with flow and compare the changes. On a dual-mode installation, Analog Values 2 and 3 hold the separate mode totals. Confirm which mode ran during the interval before interpreting an unchanged counter.

For a D-100 with the documented dual network interface, Analog Input 2 is the primary volume or mass rate. A reading in kilograms per hour needs a mass-flow field in the customer’s report. On a System-40, Analog Input 2 is volume flow and Analog Input 1 is thermal energy rate. Keep the meter model, device instance, object and unit together on the point list.

On a mixed site, identify the register separately for each make. The Belimo 22PEM-1UC has separate heating and cooling objects and a selection between certified and lifetime totals. Record that selection with the unit before comparing its readings with the plant report.

Scope the collection work

For each plant room, list the Ethernet meters, the serial meters grouped by trunk and the existing BACnet routers. Ask the controls operator which devices are reachable from the proposed Gateway location. Where the plant also needs electrical input monitoring, use the power meter retrofit guide to scope the feeder separately.

Include the branch schedule, one local reading per meter type, the number of reporting channels and the collection interval in the project enquiry. For a replacement quote, identify which flow sensors, temperature sensors and calculators the site plans to retain.