ONICON F-2600
Steam and liquid flow meter
The inline meter replaces a section of pipe. Identify the body from its nameplate and drawing before pricing a replacement. An existing transmitter with the serial option can instead be quoted for monitoring alone.
Compatibility
Compatible with Edge through a BACnet MS/TP router
ONICON offers a BACnet MS/TP option on this transmitter. Edge can read its flow objects through a BACnet/IP router.
Check the fitted communications option and obtain the installed object list. The Rev. D example covers the mass-flow configuration.
Connect it with
For a transmitter with BACnet MS/TP commissioned on its serial interface
- BACnet
- Edge
- Platforms
Models
| Models | Interface | Route into Edge |
|---|---|---|
| F-2600 inline body | Optional BACnet MS/TP on the transmitter. | Record the meter body size, wafer or flanged connection, and flange rating. Include the fluid and the desired reporting unit in the enquiry. |
Interface
Documented measurements and integration boundaries for F-2600.
- Analog Input 1 reports volume flow on the documented mass-flow configuration. Check whether a gallons-per-minute reading uses US or Imperial gallons.
- Temperature 1 is Analog Input 3. Read its engineering unit if temperature is included in the report.
Assessment
ONICON F-2600 inline vortex flow meter with its optional BACnet interface.
- InteroperabilityWell supported
- The manual identifies the BACnet input for volume flow and its engineering units.2
- AccuracySupported with conditions
- Record the meter body size, wafer or flanged connection, and flange rating.2
- SecurityNot yet assessed
- The site operator controls access to the routed segment.2
- ReliabilitySupported with conditions
- The local LCD provides a comparison for the collected rate.2
- RuggednessSupported with conditions
- Check the installed body and process connection against the line conditions. Record the meter body size, wafer or flanged connection, and flange rating.2
- ScalabilitySupported with conditions
- Collect the serial network and Device instance for each surveyed meter.2
- LifecycleSupported with conditions
- Use the model, process service and communications option when scoping replacement equipment.2
Setup
-
Record the meter body size, wafer or flanged connection, and flange rating.
-
Use section 4.3.3.2 of DOC-0003869 Rev.
D to read Present_Value and Units from Analog Input 1. Compare the volume rate with the local display during a steady operating interval.
-
Record the observed object instance, unit and timestamp with the meter identity for the reporting handover.
Sources
- ONICON F-2600 inline vortex flow meter (opens in a new tab)
- F-2600 and F-2700 installation and operation guide, DOC-0003869 Rev. D (opens in a new tab) (PDF)
Further reading