ONICON F-2700

Steam and liquid flow meter

The insertion probe samples the flow at a position set for the pipe geometry. Obtain the installation record for probe depth and flow direction before using a collected rate to investigate a process discrepancy.

ONICON F-2700. Insertion vortex meter with its long stem and blue transmitter.
  • BACnet MS/TP

Steam and liquid flow meter

Ask an engineer

Compatibility

Compatible with Edge through a BACnet MS/TP router

ONICON offers a BACnet MS/TP option on this transmitter. Edge can read its flow objects through a BACnet/IP router.

Check the fitted communications option and obtain the installed object list. The Rev. D example covers the mass-flow configuration.

Connect it with

For a transmitter with BACnet MS/TP commissioned on its serial interface

  • BACnet
  • Edge
  • Platforms
Steam and liquid flow meter
Interface
Gateway
Edge
Output
F-2700F-2700 serial transmitter
BACnet routerConnects the BACnet/IP collector to the serial meter trunk.
ZGW-20 GatewayHosts Edge locally
EpiSensor EdgeBACnet/IP client + object map
Customer platformMQTT · API · files
BACnet MS/TP
BACnet/IP
Runs locally
Optional onward data
Identify the meter Device instance, MS/TP network number and router address with the controls operator. The customer-platform output is optional; Edge remains the local system of record.

Models

Download
ModelsInterfaceRoute into Edge
F-2700 insertion bodyOptional BACnet MS/TP on the transmitter.Record the pipe inside diameter, probe mounting connection and retractor arrangement. Include the fluid and the desired reporting unit in the enquiry.

Interface

Documented measurements and integration boundaries for F-2700.

  • Analog Input 2 reports mass flow on the documented mass-flow configuration. Record whether the transmitter reports kilograms or pounds per hour.
  • Temperature 1 is Analog Input 3. Read its engineering unit if temperature is included in the report.

Assessment

ONICON F-2700 insertion vortex flow meter with its optional BACnet interface.

InteroperabilityWell supported
The manual identifies the BACnet input for mass flow and its engineering units.2
AccuracySupported with conditions
Record the pipe inside diameter, probe mounting connection and retractor arrangement.2
SecurityNot yet assessed
The site operator controls access to the routed segment.2
ReliabilitySupported with conditions
The local LCD provides a comparison for the collected rate.2
RuggednessSupported with conditions
Check the installed body and process connection against the line conditions. Record the pipe inside diameter, probe mounting connection and retractor arrangement.2
ScalabilitySupported with conditions
Collect the serial network and Device instance for each surveyed meter.2
LifecycleSupported with conditions
Use the model, process service and communications option when scoping replacement equipment.2

Setup

  1. Record the pipe inside diameter, probe mounting connection and retractor arrangement.

  2. Use section 4.3.3.2 of DOC-0003869 Rev.

    D to read Present_Value and Units from Analog Input 2. Compare the mass rate with the local display during a steady operating interval.

  3. Record the observed object instance, unit and timestamp with the meter identity for the reporting handover.