Belimo 22DTM
Duct air quality sensor
Use a 22DTM when the ventilation survey needs carbon dioxide in the duct as well as temperature and humidity. Record whether the probe is in the supply, return or extract duct so the trend can be interpreted alongside the fan schedule.
Compatibility
Compatible with Edge through a BACnet router
Edge reads the sensor through a BACnet/IP-to-MS/TP router on the building network.
Belimo’s interface description covers firmware 2.3. Match the suffix and object to the installed sensor before adding the trend.
Connect it with
For an installed MS/TP segment
- BACnet
- Edge
- Platforms
Models
| Models | Interface | Route into Edge |
|---|---|---|
| 22DTM-16 and 22DTM-56 | Belimo specifies a 180 mm probe for the 22DTM-16. Confirm duct dimensions and access for inspection before specifying it. | Record the sensor Device instance, router and serial network number in the point list. |
Interface
Documented measurements and integration boundaries for 22DTM.
- AI 5 reports CO₂ in ppm. AI 0 and AI 1 report temperature and relative humidity. Keep the three readings separate when comparing ventilation performance.
Assessment
Read-only collection over the installed sensor network.
- InteroperabilityWell supported
- The PICS names the ordering variants and documents ReadProperty and ReadPropertyMultiple on MS/TP.1
- AccuracySupported with conditions
- The 22DTM-16 has a default CO₂ range of 0 to 2,000 ppm. The published accuracy is ±(50 ppm + 3% of the reading).2
- SecurityNot yet assessed
- Ask the site controls owner which clients may reach the trunk.1
- ReliabilityNot yet assessed
- Record the most recent successful reading when supervising the sensor.1
- RuggednessSupported with conditions
- IP65 / NEMA 4X housing on the 22DTM-16. Match the duct and enclosure environment separately.2
- ScalabilitySupported with conditions
- Belimo specifies up to 32 nodes without a repeater. Include existing devices when checking capacity on a shared segment.1
- LifecycleSupported with conditions
- Record the model suffix and application software version with the point list. Field models share an object table with different available measurements.1
Setup
-
Match the sensor label and its physical location to the building point schedule.
Record the Device instance as well as the object instance.
-
Read Present_Value for Analog Input 5.
Compare ppm against a reference instrument sampling the same air stream. On a changing fan duty, record the observation time and allow for probe response.
-
Check Out_Of_Service for the selected object.
The shared interface table includes measurements available only on other sensor types.
Sources
- Sensor BACnet object list and PICS, application software 2.3 (opens in a new tab) (PDF)
- 22DTM-16 duct CO₂ sensor datasheet (opens in a new tab) (PDF)
Further reading
Product names and trademarks belong to their owners. Publication does not imply endorsement or a commercial relationship.