ONICON System-10
Thermal energy meter
On an existing System-10, photograph the full SYS-10-ABCD-EFGG label and locate the communications board. Position C identifies the interface: 1 is BACnet MS/TP, 3 is BACnet/IP and 0 means the meter was supplied without serial communications. Position B identifies the supply and GG the temperature sensor option. These details matter when two visually similar calculators serve different water circuits.
Compatibility
Compatible with Edge over BACnet/IP or routed BACnet MS/TP
The System-10-BAC interface guide documents distinct Ethernet and RS-485 boards and lists the measurement objects. Edge reads these objects using its BACnet/IP client.
Match the installed interface to guide 0652-12. Record the Device instance, displayed flow unit and one reading from the same circuit.
Connect it with
For a System-10 with communications code 3
- BACnet
- Edge
- Platforms
For communications code 1 on a shared MS/TP trunk
- BACnet
- Edge
- Platforms
Models
| Models | Interface | Route into Edge |
|---|---|---|
| SYS-10-ABCD-EFGG | Communications code 1 selects RS-485 BACnet MS/TP; code 3 selects BACnet/IP. Code 5 denotes the separate DualNet option. | For a DualNet installation request the fitted interface documentation and site network schedule before selecting a route. |
Interface
Documented measurements and integration boundaries for System-10.
- Analog Input 2 is volume flow. Its configured units may be US gallons per minute, litres per second or cubic metres per hour, among others. Use the object’s Units property.
- Analog Input 1 reports energy rate. Inputs 3 and 4 report the supply and return temperatures. Keep the measured rate separate from cumulative consumption in the reporting schedule.
Assessment
System-10 meters with the BACnet board documented in guide 0652-12.
- InteroperabilityWell supported
- The interface guide identifies two BACnet transports and gives the flow and temperature object identifiers.2
- AccuracySupported with conditions
- Record the temperature sensor range and source flow meter when assessing the branch measurement.1
- SecurityNot yet assessed
- Access to the collector network depends on the installed controls design.2
- ReliabilitySupported with conditions
- Check the input supply option on the label and compare the displayed flow with the network reading.1
- RuggednessSupported with conditions
- The model code distinguishes NEMA 13 and NEMA 4 enclosures. Record the installed enclosure for a replacement quote.1
- ScalabilitySupported with conditions
- Serial installations need a trunk and router inventory. Ethernet boards need an appropriate switch connection per meter.2
- LifecycleSupported with conditions
- Keep the complete order code with the flow and temperature sensor details when replacing a calculator.1
Setup
-
Identify the branch served by the flow sensor and record the complete calculator code and network settings from the operator.
-
Using section 2.4 of guide 0652-12, read Present_Value and Units on Analog Input 2.
Compare with the flow display at the same time, using the same units.
-
Read supply and return temperatures on the same Device instance.
Confirm these correspond to the two sensors on the surveyed loop before collecting a plant trend.
Sources
- System-10 installation and operation guide, DOC-0002341 (opens in a new tab) (PDF)
- System-10-BAC network interface installation guide, 0652-12 (opens in a new tab) (PDF)
Further reading
- GuideConnecting ONICON flow and heat meters to BACnet
- GuideMonitoring heat meter data
- GuideConnecting existing meters to BACnet
- GuideGateway for BACnet/IP monitoring
- GuideSystem-20 thermal energy meter
- GuideSystem-40 with integral flow sensor
- ManufacturerONICON devices
- ProtocolBACnet/IP building controllers