Lutron Vive Premium
Lighting controller
The HJS-2 Premium hub includes BACnet. For a floor-wide lighting report, obtain the Vive area schedule and the virtual BACnet device for each area. Two rooms on the same physical hub can both use Analog Value 18, each under its own Device instance.
Compatibility
Compatible with Edge over BACnet/IP
Vive routes its virtual area devices to the building BACnet/IP network. Edge reads the points exposed for the commissioned area.
Confirm the area Device instance and the installed Vive software.
Connect it with
For a commissioned area on a BACnet-enabled hub
- BACnet
- Edge
- Platforms
Models
| Models | Interface | Route into Edge |
|---|---|---|
| HJS-2-FM and HJS-2-SM | Premium hub with BACnet included. FM is flush mount and SM is surface mount. | BTL listing 30803 names both order codes at version 1.07. |
| HJS regional model codes | Lutron specifies 433.05 to 434.79 MHz for the J frequency band. | For a UK or US retrofit, copy the complete regional code from the installed hub before requesting a licence or replacement. |
Interface
Documented measurements and integration boundaries for Vive Premium.
- Analog Value 18 is instantaneous total lighting power for the area in watts. Lutron describes the quantity as calculated or measured.
- Analog Value 19 is maximum connected lighting power for that area. Specify a separate meter if the project needs a metered circuit energy total.
- To estimate how far an area is below its maximum connected load, subtract Total Power (AV 18) from Maximum Power (AV 19). For example, 900 W maximum and 600 W total give a 300 W difference at that instant. An energy report in kWh also needs elapsed time.
Assessment
Vive Premium hub with BACnet enabled.
- InteroperabilityWell supported
- Lutron documents BACnet/IP area devices and their object definitions.2
- AccuracySupported with conditions
- Area power can be calculated or measured. Occupancy reports a combined area state.2
- SecurityNot yet assessed
- Confirm access to the lighting network with the building operator.1
- ReliabilityNot yet assessed
- The occupancy point has a distinct unknown state.2
- RuggednessNot yet assessed
- Select a mounting adapter for the installation surface.1
- ScalabilitySupported with conditions
- Count wireless devices separately from the areas exposed over BACnet.1
- LifecycleSupported with conditions
- The ordering guide distinguishes BACnet eligibility, capacity and mounting options.1
Setup
-
Record the installed model, software and area Device instance.
Use the version 1.07 PICS as the reference for this check.
-
Read Present_Value and Units of AV 18 on the area device and compare watts with the same area in the lighting system at the same time.
-
Repeat on a second area and record its own Device instance before applying the point selection to other floors.
Sources
- Vive hub specification 369902, ordering codes and licences (opens in a new tab) (PDF)
- Vive BACnet object definitions for version 1.07 (opens in a new tab) (PDF)
- BTL listing 30803, Vive Wireless Hub 1.07 (opens in a new tab) (PDF)
Further reading