Lutron Vive Premium

Lighting controller

The HJS-2 Premium hub includes BACnet. For a floor-wide lighting report, obtain the Vive area schedule and the virtual BACnet device for each area. Two rooms on the same physical hub can both use Analog Value 18, each under its own Device instance.

White circular Lutron Vive wireless hub
  • BACnet/IP

Lighting controller

Ask an engineer

Compatibility

Compatible with Edge over BACnet/IP

Vive routes its virtual area devices to the building BACnet/IP network. Edge reads the points exposed for the commissioned area.

Confirm the area Device instance and the installed Vive software.

Connect it with

For a commissioned area on a BACnet-enabled hub

  • BACnet
  • Edge
  • Platforms
Lighting controller
Interface
Gateway
Edge
Output
Vive PremiumVive area device
Protected EthernetSegmented LAN
ZGW-20 GatewayHosts Edge locally
EpiSensor EdgeBACnet/IP client + object map
Customer platformMQTT · API · files
BACnet/IP
Protected Ethernet
Runs locally
Optional onward data
Use the network and Device instance assigned to the area. Keep the physical hub and the room name on the point schedule. The customer-platform output is optional; Edge remains the local system of record.

Models

Download
ModelsInterfaceRoute into Edge
HJS-2-FM and HJS-2-SMPremium hub with BACnet included. FM is flush mount and SM is surface mount.BTL listing 30803 names both order codes at version 1.07.
HJS regional model codesLutron specifies 433.05 to 434.79 MHz for the J frequency band.For a UK or US retrofit, copy the complete regional code from the installed hub before requesting a licence or replacement.

Interface

Documented measurements and integration boundaries for Vive Premium.

  • Analog Value 18 is instantaneous total lighting power for the area in watts. Lutron describes the quantity as calculated or measured.
  • Analog Value 19 is maximum connected lighting power for that area. Specify a separate meter if the project needs a metered circuit energy total.
  • To estimate how far an area is below its maximum connected load, subtract Total Power (AV 18) from Maximum Power (AV 19). For example, 900 W maximum and 600 W total give a 300 W difference at that instant. An energy report in kWh also needs elapsed time.

Assessment

Vive Premium hub with BACnet enabled.

InteroperabilityWell supported
Lutron documents BACnet/IP area devices and their object definitions.2
AccuracySupported with conditions
Area power can be calculated or measured. Occupancy reports a combined area state.2
SecurityNot yet assessed
Confirm access to the lighting network with the building operator.1
ReliabilityNot yet assessed
The occupancy point has a distinct unknown state.2
RuggednessNot yet assessed
Select a mounting adapter for the installation surface.1
ScalabilitySupported with conditions
Count wireless devices separately from the areas exposed over BACnet.1
LifecycleSupported with conditions
The ordering guide distinguishes BACnet eligibility, capacity and mounting options.1

Setup

  1. Record the installed model, software and area Device instance.

    Use the version 1.07 PICS as the reference for this check.

  2. Read Present_Value and Units of AV 18 on the area device and compare watts with the same area in the lighting system at the same time.

  3. Repeat on a second area and record its own Device instance before applying the point selection to other floors.