ONICON F-5500

Gas flow meter

A boiler-house gas report may use standard cubic feet per hour, while a process report may need kilograms per hour. Request the calibration gas and a photograph of the displayed rate and unit. For standard or normal volume, retain the reference conditions used by the site.

ONICON F-5500. The manufacturer shows the insertion and inline configurations together.
  • BACnet MS/TP

Gas flow meter

Ask an engineer

Compatibility

Compatible with Edge through a BACnet MS/TP router

The standard transmitter includes an RS-485 interface configurable for BACnet MS/TP. A BACnet/IP router links the serial trunk to Edge.

ONICON also supplies a current and pulse output version. Confirm the fitted outputs and the serial protocol before quoting network collection.

Connect it with

For a transmitter with BACnet MS/TP commissioned on its serial interface

  • BACnet
  • Edge
  • Platforms
Gas flow meter
Interface
Gateway
Edge
Output
F-5500F-5500 serial transmitter
BACnet routerConnects the BACnet/IP collector to the serial meter trunk.
ZGW-20 GatewayHosts Edge locally
EpiSensor EdgeBACnet/IP client + object map
Customer platformMQTT · API · files
BACnet MS/TP
BACnet/IP
Runs locally
Optional onward data
Identify the meter Device instance, MS/TP network number and router address with the controls operator. The customer-platform output is optional; Edge remains the local system of record.

Models

Download
ModelsInterfaceRoute into Edge
Inline F-5500ONICON recommends the inline body for pipes smaller than 1½ inches.For a replacement quote, record the pipe size, gas and expected minimum and maximum flow.
Insertion F-5500An insertion probe measures gas flow within the existing pipe.For an existing meter, record the pipe dimensions, mounting arrangement and transmitter option.

Interface

Documented measurements and integration boundaries for F-5500.

  • Analog Input 1 reports the flow rate and Analog Input 2 reports gas temperature.
  • Analog Input 3 reports the accumulated flow. Analog Input 4 gives elapsed time since reset, which helps interpret a discontinuity in a consumption trend.

Assessment

Gas monitoring through the F-5500 serial interface.

InteroperabilityWell supported
ONICON publishes distinct objects for rate, temperature, total and elapsed time.1
AccuracySupported with conditions
The meter is calibrated for the specified application. Record the gas when assessing suitability.2
SecurityNot yet assessed
Confirm network access with the site controls operator.1
ReliabilitySupported with conditions
The totalizer rollover limit varies with the selected unit. Retain reset timing when interpreting interval consumption.1
RuggednessSupported with conditions
The manual specifies a NEMA 4X aluminum enclosure. Check installation conditions against the fitted meter.1
ScalabilitySupported with conditions
Use the documented Device discovery response to identify each transmitter on a routed trunk.1
LifecycleSupported with conditions
Record the body type and output option when specifying a replacement. A pulse-output configuration changes the collection hardware.2

Setup

  1. Obtain the configured gas, flow unit, BACnet Device instance and serial network number from the controls operator.

  2. Using section 5.2 of DOC-0005059 Rev.

    K, read Present_Value on Analog Input 1. Compare the reading with the local flow display during a steady interval and record its configured unit.

  3. For interval consumption, collect two readings of Analog Input 3 and record elapsed time since reset alongside each.

    The totalizer rollover depends on the selected unit.