ONICON F-5500
Gas flow meter
A boiler-house gas report may use standard cubic feet per hour, while a process report may need kilograms per hour. Request the calibration gas and a photograph of the displayed rate and unit. For standard or normal volume, retain the reference conditions used by the site.
Compatibility
Compatible with Edge through a BACnet MS/TP router
The standard transmitter includes an RS-485 interface configurable for BACnet MS/TP. A BACnet/IP router links the serial trunk to Edge.
ONICON also supplies a current and pulse output version. Confirm the fitted outputs and the serial protocol before quoting network collection.
Connect it with
For a transmitter with BACnet MS/TP commissioned on its serial interface
- BACnet
- Edge
- Platforms
Models
| Models | Interface | Route into Edge |
|---|---|---|
| Inline F-5500 | ONICON recommends the inline body for pipes smaller than 1½ inches. | For a replacement quote, record the pipe size, gas and expected minimum and maximum flow. |
| Insertion F-5500 | An insertion probe measures gas flow within the existing pipe. | For an existing meter, record the pipe dimensions, mounting arrangement and transmitter option. |
Interface
Documented measurements and integration boundaries for F-5500.
- Analog Input 1 reports the flow rate and Analog Input 2 reports gas temperature.
- Analog Input 3 reports the accumulated flow. Analog Input 4 gives elapsed time since reset, which helps interpret a discontinuity in a consumption trend.
Assessment
Gas monitoring through the F-5500 serial interface.
- InteroperabilityWell supported
- ONICON publishes distinct objects for rate, temperature, total and elapsed time.1
- AccuracySupported with conditions
- The meter is calibrated for the specified application. Record the gas when assessing suitability.2
- SecurityNot yet assessed
- Confirm network access with the site controls operator.1
- ReliabilitySupported with conditions
- The totalizer rollover limit varies with the selected unit. Retain reset timing when interpreting interval consumption.1
- RuggednessSupported with conditions
- The manual specifies a NEMA 4X aluminum enclosure. Check installation conditions against the fitted meter.1
- ScalabilitySupported with conditions
- Use the documented Device discovery response to identify each transmitter on a routed trunk.1
- LifecycleSupported with conditions
- Record the body type and output option when specifying a replacement. A pulse-output configuration changes the collection hardware.2
Setup
-
Obtain the configured gas, flow unit, BACnet Device instance and serial network number from the controls operator.
-
Using section 5.2 of DOC-0005059 Rev.
K, read Present_Value on Analog Input 1. Compare the reading with the local flow display during a steady interval and record its configured unit.
-
For interval consumption, collect two readings of Analog Input 3 and record elapsed time since reset alongside each.
The totalizer rollover depends on the selected unit.
Sources
- F-5500 installation and operation guide, DOC-0005059 Rev. K (opens in a new tab) (PDF)
- F-5500 thermal mass flow meters and output options (opens in a new tab)
Further reading
Product names and trademarks belong to their owners. Publication does not imply endorsement or a commercial relationship.