Contemporary Controls BAST-321HP
Room thermostat
Check who operates the reversing valve before quoting a heat pump retrofit. The 321HP suits a thermostat-operated O/B valve and supports up to two compressor stages and auxiliary heat. Ask for the unit wiring diagram and auxiliary heat arrangement.
Compatibility
Compatible with Edge over BACnet/IP or routed MS/TP
The B2 suffix identifies wired MS/TP. BW2 identifies BACnet/IP over Wi-Fi. Match the route to the installed suffix.
The example uses the wired B2 manual. Confirm the installed object list and sensing configuration at the thermostat.
Connect it with
For a transmitter with BACnet MS/TP commissioned on its serial interface
- BACnet
- Edge
- Platforms
For the BW2 suffix
- Wired
- Edge
- Platforms
Models
| Models | Interface | Route into Edge |
|---|---|---|
| BAST-321HP-B2 | BACnet MS/TP on EIA-485 | Identify the existing router and serial network number. |
| BAST-321HP-BW2 | BACnet/IP over Wi-Fi | Record wireless coverage and the permitted IP route at the room location. |
Interface
Documented measurements and integration boundaries for BAST-321HP.
- Analog Input 0 reports the active temperature. Compare it with the display when interpreting a heat pump call. A temperature trend alone cannot establish compressor electricity consumption.
Assessment
BAST-321HP room monitoring with the ordered network interface.
- InteroperabilityWell supported
- Both orderable network variants have a documented BACnet route.1
- AccuracySupported with conditions
- Analog Input 0 reports the active temperature. Compare it with the display when interpreting a heat pump call. A temperature trend alone cannot establish compressor electricity consumption.2
- SecurityNot yet assessed
- Site network admission and access depend on the controls operator.1
- ReliabilitySupported with conditions
- Use the room display and selected temperature source to check the trend at handover.2
- RuggednessNot yet assessed
- Obtain the environmental limits for the intended room location.3
- ScalabilitySupported with conditions
- Count the wired trunks and wireless devices separately when estimating collection work.1
- LifecycleSupported with conditions
- Retain the HVAC wiring schedule and complete ordering suffix with the project records.1
Setup
-
Record the model suffix, room and served equipment on the point schedule.
Check who operates the reversing valve before quoting a heat pump retrofit.
-
On a B2 thermostat, read Present_Value of Analog Input 0 and compare with the local display.
Record the active temperature and °C or °F alongside the Device instance.
-
Include the observed room value, timestamp and network route in the monitoring handover.
Sources
- Selecting a heat pump thermostat, AN-BSTATHP0-AA0 (opens in a new tab) (PDF)
- BAST-321HP-B2 user manual, BACnet objects (opens in a new tab) (PDF)
- BASstat thermostat sensing and control options (opens in a new tab)
Further reading
Product names and trademarks belong to their owners. Publication does not imply endorsement or a commercial relationship.