Contemporary Controls BAST-221CH

Room thermostat

Choose the CH version when the room report needs humidity as well as temperature. It measures relative humidity and calculates dew point. Its humidity measurement supports monitoring even where the equipment has no humidity control sequence.

BASstat-221 thermostat front with room temperature display and mode and fan buttons
  • BACnet MS/TP
  • BACnet/IP

Room thermostat

Ask an engineer

Compatibility

Compatible with Edge over BACnet/IP or routed MS/TP

The B2 suffix identifies wired MS/TP. BW2 identifies BACnet/IP over Wi-Fi. Match the route to the installed suffix.

The example uses the wired B2 manual. Confirm the installed object list and sensing configuration at the thermostat.

Connect it with

Route into Edge

For a transmitter with BACnet MS/TP commissioned on its serial interface

  • BACnet
  • Edge
  • Platforms
Room thermostat
Interface
Gateway
Edge
Output
BAST-221CHBAST-221CH-B2
BACnet routerConnects the BACnet/IP collector to the serial meter trunk.
ZGW-20 GatewayHosts Edge locally
EpiSensor EdgeBACnet/IP client + object map
Customer platformMQTT · API · files
BACnet MS/TP
BACnet/IP
Runs locally
Optional onward data
Identify the meter Device instance, MS/TP network number and router address with the controls operator. The customer-platform output is optional; Edge remains the local system of record.

For the BW2 suffix

  • Wired
  • Edge
  • Platforms
Room thermostat
Interface
Gateway
Edge
Output
BAST-221CHBAST-221CH-BW2
Protected EthernetSegmented LAN
ZGW-20 GatewayHosts Edge locally
EpiSensor EdgeProtocol client + point model
Customer platformMQTT · API · files
Ethernet
Protected Ethernet
Runs locally
Optional onward data
Ask the network operator for the route from the Gateway to the thermostat on the building wireless network. The customer-platform output is optional; Edge remains the local system of record.

Models

Download
ModelsInterfaceRoute into Edge
BAST-221CH-B2BACnet MS/TP on EIA-485Identify the existing router and serial network number.
BAST-221CH-BW2BACnet/IP over Wi-FiRecord wireless coverage and the permitted IP route at the room location.

Interface

Documented measurements and integration boundaries for BAST-221CH.

  • Analog Input 4 is measured relative humidity in percent. Analog Input 5 is calculated dew point. Keep these as separate channels in the room report.

Assessment

BAST-221CH room monitoring with the ordered network interface.

InteroperabilityWell supported
Both orderable network variants have a documented BACnet route.1
AccuracySupported with conditions
Analog Input 4 is measured relative humidity in percent. Analog Input 5 is calculated dew point. Keep these as separate channels in the room report.2
SecurityNot yet assessed
Site network admission and access depend on the controls operator.1
ReliabilitySupported with conditions
Use the room display and selected temperature source to check the trend at handover.2
RuggednessNot yet assessed
Obtain the environmental limits for the intended room location.3
ScalabilitySupported with conditions
Count the wired trunks and wireless devices separately when estimating collection work.1
LifecycleSupported with conditions
Retain the HVAC wiring schedule and complete ordering suffix with the project records.1

Setup

  1. Record the model suffix, room and served equipment on the point schedule.

    Choose the CH version when the room report needs humidity as well as temperature.

  2. On a B2 thermostat, read Present_Value of Analog Input 4 and compare with the local display.

    Record the room humidity and percent RH alongside the Device instance.

  3. Include the observed room value, timestamp and network route in the monitoring handover.