Neptronic EFCB11TU2 / EFCB11TU4

HVAC fan coil controller

For a 120 Vac fan coil with a remote room probe, record where that probe is mounted and which input receives it. A return-air sensor and a wall sensor can produce different readings while both are working correctly.

Neptronic EFCB series controller enclosure with removable terminal blocks along both sides
  • BACnet MS/TP
  • Modbus RTU

HVAC fan coil controller

Ask an engineer

Compatibility

Compatible with Edge over BACnet MS/TP or Modbus RTU

The EFCB serves the selected serial protocol. Edge reads BACnet points through a site BACnet router or collects Modbus RTU with a serial interface.

Confirm the installed protocol and the sensor selected in the fan coil configuration.

Connect it with

Route into Edge

For a controller on a BACnet MS/TP trunk

  • BACnet
  • Edge
  • Platforms
HVAC fan coil controller
Interface
Gateway
Edge
Output
EFCB11TU2 / EFCB11TU4EFCB11 controller
BACnet routerRoutes the field segment to the building IP network.
ZGW-20 GatewayHosts Edge locally
EpiSensor EdgeBACnet/IP client + object map
Customer platformMQTT · API · files
BACnet MS/TP
BACnet/IP
Runs locally
Optional onward data
Use the controller’s Device instance and the router for its field network. The wall unit reports to the controller through its own connection. The customer-platform output is optional; Edge remains the local system of record.

For an EFCB configured for Modbus RTU

  • Modbus
  • Edge
  • Platforms
HVAC fan coil controller
Interface
Gateway
Edge
Output
EFCB11TU2 / EFCB11TU4EFCB11 controller
Isolated serial interfaceApproved RS-485-to-host adapter
ZGW-20 GatewayHosts Edge locally
EpiSensor EdgeEdge Modbus client
Customer platformMQTT · API · files
Modbus RTU · RS-485
Isolated serial
Runs locally
Optional onward data
Request the installed unit address, serial settings and matching EFCB Modbus register list. The customer-platform output is optional; Edge remains the local system of record.

Models

Download
ModelsInterfaceRoute into Edge
EFCB11TU2120 Vac supply and 2 configurable relay outputs.Record which relay functions the installer assigned on the equipment schedule.
EFCB11TU4120 Vac supply and 4 configurable relay outputs.Record which relay functions the installer assigned on the equipment schedule.

Interface

Documented measurements and integration boundaries for EFCB11TU2 / EFCB11TU4.

  • Analog Input 1 (ExternTemp) reports the external temperature probe on AI 1, or on AI 3 when configured for that purpose. AI 7 reports the sensor in the wall unit.
  • MSV 21 identifies the configured source for the control temperature, including the wall sensor, external probe or a network value.

Assessment

EFCB11TU2 and TU4 controllers with the documented room interface.

InteroperabilityWell supported
The EFCB guide identifies the objects and the supported BACnet properties.2
AccuracySupported with conditions
The object selected must represent the sensor at the required physical location.2
SecurityNot yet assessed
Site access controls depend on the building network.1
ReliabilityNot yet assessed
The installation specification describes operating conditions.1
RuggednessSupported with conditions
Neptronic specifies IP30 and a 0 to 50 °C operating range for the controller.1
ScalabilitySupported with conditions
Controllers share a serial trunk with assigned addresses and common network settings.1
LifecycleSupported with conditions
Match the supply voltage, relay count and wall-unit interface when specifying service stock.1

Setup

  1. Record the controller and wall-unit codes, room served and selected serial protocol.

  2. Read Present_Value and Units on AI 1 after identifying the configured external probe.

    Compare with a reference at that probe and record whether the value is in °C or °F.

  3. Identify the measured location in the trend name.

    Record the corresponding device and object identifiers for handover.