Contemporary Controls BAScontrol20

Building automation controller

Both BAScontrol20 models are discontinued. For an installed panel with working sensors, ask for its Ethernet connection and one configured input before pricing replacement equipment. For a panel renewal, inventory the output loads. The BASC-20R uses relays and the BASC-20T uses triacs.

Contemporary Controls BAScontrol20 relay controller with labelled I/O and network terminals
  • BACnet/IP

Building automation controller

Ask an engineer

Compatibility

Compatible with Edge over BACnet/IP

The BAScontrol20 serves its configured points over Ethernet. Edge can read a physical input or an exposed virtual point through the site IP network.

Match the object to its channel configuration. A voltage at a terminal and the scaled reading requested by the operator can have different units.

Connect it with

For an installed BASC-20R or BASC-20T

  • Wired
  • Edge
  • Platforms
Building automation controller
Interface
Gateway
Edge
Output
BAScontrol20BAScontrol20
Protected EthernetSegmented LAN
ZGW-20 GatewayHosts Edge locally
EpiSensor EdgeProtocol client + point model
Customer platformMQTT · API · files
Ethernet
Protected Ethernet
Runs locally
Optional onward data
Obtain the Device instance and identify the monitored input with the controls contractor. Record its configured object type and instance. The customer-platform output is optional; Edge remains the local system of record.

Models

Download
ModelsInterfaceRoute into Edge
BASC-20REthernet and four normally open relay outputs.Record the relay loads if the project includes a panel replacement.
BASC-20TEthernet and four isolated triac outputs.Record the switched AC loads and their ratings before estimating replacement work.

Interface

Documented measurements and integration boundaries for BAScontrol20.

  • The controller has eight configurable universal inputs. A temperature input depends on the fitted thermistor and the curve selected in the controller.
  • The application can expose up to 24 virtual points. Ask which represent the requested measurements in the commissioned application.

Assessment

Read-only collection from commissioned BAScontrol20 Ethernet panels.

InteroperabilityWell supported
The Ethernet interface supports BACnet/IP and the application can expose virtual points.1
AccuracySupported with conditions
Check the thermistor curve and configured units against the fitted sensor.2
SecurityNot yet assessed
Confirm site network access with the controls contractor.1
ReliabilitySupported with conditions
Read the assigned object instance from the channel page and retain a matching local observation.2
RuggednessSupported with conditions
The manufacturer specifies operation from −40 to 75 °C. Check the enclosure and panel conditions.1
ScalabilitySupported with conditions
Count the required physical and application points against the installed configuration.1
LifecycleSupported with conditions
Both models are discontinued. The manufacturer names BASC-22DR as a replacement. Check output loads and application migration before pricing the change.1

Setup

  1. For a thermistor channel, ask for its terminal label, sensor curve and temperature shown on the controller page.

  2. In the channel configuration described in UM-BASC2000-AA1, note the assigned BACnet object instance and the selected temperature unit.

    Read Present_Value for that input over BACnet/IP and compare it with the controller value at the same time.

  3. Retain the room or plant label, object identifier and Celsius or Fahrenheit unit on the point schedule.

    Obtain a separate schedule for any new physical inputs.