A tender that asks for a “BACnet air quality sensor” leaves two purchasing decisions open. What does the project need to measure, and how will the sensor reach the building network? Two models with the same display can require different cabling and installation work.
Match the ordering code to the room
| Model | What the choice means on site |
|---|---|
| Siemens QNA2700D.BA1, S55720-S572 | Choose the BACnet/IP version where the room has an Ethernet drop. Check whether the switch provides the Power over Ethernet supply specified by Siemens. |
| Siemens QNA2700D.BA2, S55720-S573 | Choose the BACnet MS/TP version for a serial trunk. Include a local supply and check the route from the supervising IP network to that trunk. |
| Andivi Alledio ANB-THPVCP | Choose this suffix for CO₂ and a separate yes/no presence point. Confirm the routed serial connection or building Wi-Fi at the room. |
| Vaisala GMW95 series | R adds humidity and D adds a display. Confirm the installed serial protocol. Vaisala’s earlier guide documents BACnet while the later datasheet lists Modbus RTU. |
| Belimo 22RTH-5U00D | This room unit measures temperature and relative humidity and has a local ePaper display. Select BACnet MS/TP when joining a BACnet serial trunk. A requirement for measured CO₂ calls for a different model. |
| BAST-221C staged heating and cooling thermostat | For a rooftop unit with separate heat and cool calls, record the number of stages and fan outputs. For a heat pump that accepts the same calls, obtain its wiring schedule and confirm the unit handles its own reversing valve. |
| BAST-221CH humidity-sensing thermostat | Choose the CH version when the room report needs humidity as well as temperature. It measures relative humidity and calculates dew point. Its humidity measurement supports monitoring even where the equipment has no humidity control sequence. |
| BAST-321HP heat pump thermostat | Check who operates the reversing valve before quoting a heat pump retrofit. The 321HP suits a thermostat-operated O/B valve and supports up to two compressor stages and auxiliary heat. Ask for the unit wiring diagram and auxiliary heat arrangement. |
Use the Siemens QNA2700D model guide to identify the connection and points for each suffix. Record the complete suffix on the purchase schedule. Siemens also offers QNA2820D regional variants using LoRaWAN. Substituting one changes the network equipment the project needs.
Check the existing fan coil controller
A Neptronic TFL or TDF wall unit can already provide a room measurement through its EFCB controller. Match the supply on the controller nameplate: 24 Vac EFCB10, 120 Vac EFCB11 or 240 Vac EFCB12. The TU2 and TU4 suffixes specify two or four configurable relays. Ask which temperature the operator needs. The wall sensor, external probe and water changeover sensor have separate BACnet objects.
Price the complete connection
For a room with Ethernet, ask the network owner to confirm the switch port, power provision and permitted route to the collector. For a serial installation, ask the controls contractor for the trunk network number and the existing router model. If the building controller already routes between MS/TP and BACnet/IP, the contractor can confirm whether Edge can use that route. If it cannot, include a router and its commissioning in the quote. A USB serial adapter alone does not provide BACnet routing.
For an existing Titan Products NetMaster TP-NM-D, record the trunk network number and the room controller’s Device instance. The temperature object belongs to the room controller.
Check a measurement before handover
Siemens documents particulate matter PM2.5 as Analog Input instance 4 on these BACnet multi-sensors. At the installed sensor, record its model, Device instance and time. Read Present_Value and Units for Analog Input 4, then compare the result in micrograms per cubic metre with the PM2.5 value on the room display. Allow for the display and network values updating at different times. If the unit or measurement differs, check the instance against the installed model's object table before logging a trend.
On the Belimo 22RTH-5U00D, read Analog Input 2 and compare it with the relative humidity percentage on its display. Carry the room name, object identifier, unit and observation time into the BACnet point list. Include that list and the number of rooms when requesting a system configuration.