Daikin Applied MicroTech III chiller MS/TP
HVAC chiller controller
For a chilled-water plant retrofit, identify the chiller model and fitted communications module before pricing a connection. Daikin’s MS/TP module shares the controller’s measured entering and leaving evaporator temperatures through a BACnet router.
Compatibility
Compatible with Edge through a BACnet router
The MicroTech III MS/TP communications module exposes chiller objects to Edge through a BACnet router.
Identify the installed interface, MS/TP trunk and Device instance before comparing a read with the local display.
Connect it with
For the commissioned MS/TP interface
- BACnet
- Edge
- Platforms
Models
| Models | Interface | Route into Edge |
|---|---|---|
| AGZ, AMZ, AWS, AWV and ADS | MicroTech III MS/TP module for the listed air-cooled chillers. | Use the unit nameplate and the communications module label to identify the correct protocol documentation. |
| WWV and B-vintage WME | IM 967-4 also covers these water-cooled models. | Match the WME vintage. The replacement MS/TP module kit in table 4 is 350147414. |
Interface
Documented measurements and integration boundaries for MicroTech III chiller MS/TP.
- ED 15120-9 identifies AI 1 as entering evaporator fluid temperature and AI 2 as leaving fluid temperature. Both are read-only.
- Keep the two temperatures and their timestamps together for a chilled-water temperature difference. Cooling power also requires a flow measurement and the fluid properties.
Assessment
Daikin Applied MicroTech III chiller MS/TP module on a routed MS/TP network.
- InteroperabilitySupported with conditions
- The manufacturer documents the MS/TP interface.1
- AccuracySupported with conditions
- ED 15120-9 identifies AI 1 as entering evaporator fluid temperature and AI 2 as leaving fluid temperature. Both are read-only.2
- SecurityNot yet assessed
- Access to the IP-side router depends on the installation.1
- ReliabilityNot yet assessed
- The operating manual describes serial network commissioning.1
- RuggednessNot yet assessed
- The enclosure and plant-room conditions depend on the installation.1
- ScalabilityNot yet assessed
- Additional units need individual Device instances and sufficient trunk capacity.1
- LifecycleNot yet assessed
- The module manual gives a replacement kit number.1
Setup
-
Record the chiller model, module kit or label, Device instance and the temperature units selected on the controller.
-
Read Present_Value and Units from Analog Input 2 (LvgEvapWaterTempUnit).
Compare it with measured leaving evaporator temperature on the chiller display during steady operation.
-
Read AI 1 at the same time if the report also needs entering-water temperature.
Record the sensor names alongside both points.