Daikin Applied MicroTech III chiller MS/TP

HVAC chiller controller

For a chilled-water plant retrofit, identify the chiller model and fitted communications module before pricing a connection. Daikin’s MS/TP module shares the controller’s measured entering and leaving evaporator temperatures through a BACnet router.

Daikin Applied MicroTech III chiller BACnet MS/TP communications module
  • BACnet MS/TP

HVAC chiller controller

Ask an engineer

Compatibility

Compatible with Edge through a BACnet router

The MicroTech III MS/TP communications module exposes chiller objects to Edge through a BACnet router.

Identify the installed interface, MS/TP trunk and Device instance before comparing a read with the local display.

Connect it with

For the commissioned MS/TP interface

  • BACnet
  • Edge
  • Platforms
HVAC chiller controller
Interface
Gateway
Edge
Output
MicroTech III chiller MS/TPMicroTech III chiller MS/TP
BACnet routerRoutes the field segment to the building IP network.
ZGW-20 GatewayHosts Edge locally
EpiSensor EdgeBACnet/IP client + object map
Customer platformMQTT · API · files
BACnet MS/TP
BACnet/IP
Runs locally
Optional onward data
Match the field Device instance to the equipment tag and obtain the route to its MS/TP network. The customer-platform output is optional; Edge remains the local system of record.

Models

Download
ModelsInterfaceRoute into Edge
AGZ, AMZ, AWS, AWV and ADSMicroTech III MS/TP module for the listed air-cooled chillers.Use the unit nameplate and the communications module label to identify the correct protocol documentation.
WWV and B-vintage WMEIM 967-4 also covers these water-cooled models.Match the WME vintage. The replacement MS/TP module kit in table 4 is 350147414.

Interface

Documented measurements and integration boundaries for MicroTech III chiller MS/TP.

  • ED 15120-9 identifies AI 1 as entering evaporator fluid temperature and AI 2 as leaving fluid temperature. Both are read-only.
  • Keep the two temperatures and their timestamps together for a chilled-water temperature difference. Cooling power also requires a flow measurement and the fluid properties.

Assessment

Daikin Applied MicroTech III chiller MS/TP module on a routed MS/TP network.

InteroperabilitySupported with conditions
The manufacturer documents the MS/TP interface.1
AccuracySupported with conditions
ED 15120-9 identifies AI 1 as entering evaporator fluid temperature and AI 2 as leaving fluid temperature. Both are read-only.2
SecurityNot yet assessed
Access to the IP-side router depends on the installation.1
ReliabilityNot yet assessed
The operating manual describes serial network commissioning.1
RuggednessNot yet assessed
The enclosure and plant-room conditions depend on the installation.1
ScalabilityNot yet assessed
Additional units need individual Device instances and sufficient trunk capacity.1
LifecycleNot yet assessed
The module manual gives a replacement kit number.1

Setup

  1. Record the chiller model, module kit or label, Device instance and the temperature units selected on the controller.

  2. Read Present_Value and Units from Analog Input 2 (LvgEvapWaterTempUnit).

    Compare it with measured leaving evaporator temperature on the chiller display during steady operation.

  3. Read AI 1 at the same time if the report also needs entering-water temperature.

    Record the sensor names alongside both points.