Contemporary Controls BAScontrol22D and 22S

Building automation controller

Choose the 22D for a panel with two switched Ethernet ports. Choose the 22S when the controller application must also read instruments on a local MS/TP trunk. An existing serial meter adds two commissioning records: its own object and the value that the controller makes available to Edge.

BAScontrol22D controller with numbered terminals and its Ethernet ports
  • BACnet/IP
  • BACnet MS/TP

Building automation controller

Ask an engineer

Compatibility

Compatible with Edge over BACnet/IP

Edge reads the controller’s commissioned objects using BACnet/IP over Ethernet.

Obtain the installed point schedule. For an upstream reading, verify the source device and the object exposed to Edge.

Connect it with

Route into Edge

For a BASC-22DR or BASC-22SR connected to the building Ethernet network

  • Wired
  • Edge
  • Platforms
Building automation controller
Interface
Gateway
Edge
Output
BAScontrol22D and 22SBAScontrol22D and 22S panel
Protected EthernetSegmented LAN
ZGW-20 GatewayHosts Edge locally
EpiSensor EdgeProtocol client + point model
Customer platformMQTT · API · files
Ethernet
Protected Ethernet
Runs locally
Optional onward data
Use the panel Device instance and its exposed BACnet object type and instance. The customer-platform output is optional; Edge remains the local system of record.

For an installed 22S application that publishes a value collected from MS/TP

  • BACnet
  • Edge
  • Platforms
Building automation controller
Interface
Gateway
Edge
Output
BAScontrol22D and 22SMS/TP instrument
BAScontrol22S applicationIts client reads the instrument. Its server exposes the commissioned application value to Edge.
ZGW-20 GatewayHosts Edge locally
EpiSensor EdgeProtocol client + point model
Customer platformMQTT · API · files
BACnet MS/TP
BACnet/IP
Runs locally
Optional onward data
Ask for the application mapping between the instrument and the exported value. Price any missing mapping as controls engineering. The customer-platform output is optional; Edge remains the local system of record.

Models

Download
ModelsInterfaceRoute into Edge
BASC-22DRTwo switched Ethernet portsTrace a downstream serial instrument through the existing BACnet router if the controller reads it.
BASC-22SROne Ethernet port and one MS/TP portRecord which network owns each point and how the application exposes it.

Interface

Documented measurements and integration boundaries for BAScontrol22D and 22S.

  • In the version 4 manual’s UI1 analog-input example, the channel has object instance 1. The input defaults to volts. Obtain the actual scaling if the operator wants pressure, flow or another engineering quantity.

Assessment

BAScontrol22D and 22S collection from the installed application.

InteroperabilityWell supported
The ordering code identifies the network interfaces and BACnet client capability.1
AccuracySupported with conditions
Identify the configured input and engineering unit before using it in a report.3
SecurityNot yet assessed
Confirm network access with the building operator.1
ReliabilitySupported with conditions
Compare a known point with the controller’s local channel reading.3
RuggednessNot yet assessed
Confirm the cabinet environment against the fitted controller specifications.1
ScalabilitySupported with conditions
The family has 22 physical channels and 24 virtual points. Count the application exports required by the project.1
LifecycleSupported with conditions
Record the exact variant, application backup and assigned points for the handover.2

Setup

  1. Obtain the panel order code, Device instance and one input or virtual point used by the operator.

  2. Read Present_Value on Analog Input 1 if UI1 matches the version 4 manual example.

    Compare the reading in volts with the channel page.

  3. For a field device read by the application, compare its local value with the controller export and document the mapping and update interval.